38.2 House Wrap & the Weather-Resistive Barrier
Key Takeaways
R703.2 specifies intact ASTM D226 Type I No. 15 asphalt felt or another approved WRB. The horizontal course lap is at least 2 inches and felt joints overlap at least 6 inches. Use the approved alternative’s installation details.
R703.1.1 requires a WRB behind the veneer and a means to drain water out of the exterior wall assembly, subject to its specific exceptions.
Lap upper layers over lower layers, and integrate window, door and other flashings with the drainage outlet. Follow the approved detail for the opening or transition.
A WRB controls liquid water. A continuous air barrier controls airflow. A vapor retarder limits vapor diffusion. An approved assembly can combine these functions.
For a Michigan deck ledger, install the approved corrosion-resistant flashing above the ledger. For anchored masonry veneer, integrate the WRB with the support flashing and keep the weeps immediately above it open.
How the Wall Drains
Cladding sheds much of the rain. Water that gets past joints or openings needs a route down and out before it reaches water-sensitive framing. The water-resistive barrier (WRB) behind the cladding forms part of that drainage path.
| Layer or function | Examples | Job |
|---|---|---|
| Cladding | Vinyl, fiber cement, wood or brick veneer | Sheds most rain and protects the assembly |
| Drainage plane | House wrap, felt, approved liquid-applied membrane or coated sheathing system | Directs liquid water to an exit over integrated flashing |
| Sheathing and framing | Wood structural panels, studs and other approved components | Support cladding and carry structural loads where designed to do so |
| Thermal control | Cavity batts or foam, or continuous exterior insulation | Limits heat flow |
| Air control | Continuous sealed sheathing, approved WRB system or detailed interior gypsum | Restricts airflow at seams, transitions and penetrations |
| Vapor control | Tested facing, coating or membrane | Limits vapor diffusion according to the wall design |
R703.1 ordinarily requires a weather-resistant exterior wall envelope with flashing per R703.4. ICC 400 log walls have a separate exception. Under R703.1.1, place a WRB behind the veneer and provide a route to drain water back outside. The exception for Chapter 6 concrete or masonry walls requires the appropriate flashing. A separate ASTM E331 exception addresses the drainage, WRB and flashing provisions for a qualifying tested assembly. Check the representative opening, joint, eave and sill details and the specified minimum specimen size, pressure and two-hour exposure before relying on that exception.
Code and Product Laps
R703.2 lists one layer of intact No. 15 asphalt felt meeting ASTM D226 Type I or another approved WRB over studs or sheathing. Run the courses horizontally with the upper material overlapping the lower by at least 2 inches. At felt joints, overlap by at least 6 inches. Carry the barrier to the wall top and terminate it at penetrations and appendages so the envelope still drains. R703.2 exempts detached accessory buildings from its WRB requirement.
Use the approval and instructions for an alternative system. A wrap relies on the specified seams and attachment. A fluid-applied WRB relies on its approved substrate, application and transitions. A factory-coated sheathing system relies on the approved seam and penetration treatments. The applicable product instructions can require more overlap than a general code provision.
For example, DuPont’s single-family Tyvek HomeWrap guide shows bottom-up courses with at least 6 inches of overlap and horizontal installation with 6 to 12 inches at vertical seams. On the guide’s conventional nail-base detail, it shows compatible cap fasteners spaced 6 to 18 inches vertically along stud lines. Its fastening schedule and opening clearances depend on the substrate and detail. Match the approved fasteners and seam tape to the specific system. Follow the required fastening and sealing for the selected exposure and for water-only or air-barrier use.
Bulk Water, Air and Vapor
A WRB controls liquid water. An approved WRB can also serve as the air barrier if the material qualifies for air control and its seams, perimeter and penetrations maintain continuity. Air can carry moisture through gaps. Vapor diffusion through materials is a different transport mechanism. WRBs vary in vapor permeance. Check the wall’s drying path and the product’s approval rather than selecting a barrier on permeance alone.
For interior vapor control, Michigan enforces R601.3 as amended by Rule 522a. The ordinary requirement for frame walls in Zones 5 through 8 and Marine 4 is Class I or II on the interior. Apply the specific exceptions, including qualifying Table R702.7.1 assemblies and the separate below-grade provisions. A sheet approved for vapor control alone does not establish a drainage assembly. For the Michigan prescriptive air leakage test, the limit is 4 air changes per hour at 50 pascals. Trace the intended air-barrier connections between walls, openings, floors and roof before concealment.
Which material meets the ordinary 2015 MRC R703.2 water-resistive barrier requirement over exterior studs or sheathing?
A double layer of 6-mil polyethylene film sealed at all seams
One layer of intact No. 15 asphalt felt meeting ASTM D226 Type I or another approved WRB, installed as a continuous barrier
One layer of 15-pound roofing underlayment applied vertically with capped fasteners
A fluid-applied waterproof membrane with a perm rating of 0.1 or less
Which statement about the WRB, the air barrier and the interior vapor retarder is correct?
The WRB and the interior vapor retarder are the same layer installed from opposite sides of the studs
Because house wrap is vapor-permeable, it cannot function as part of the air barrier
An approved, continuously detailed WRB can perform the air-barrier function. Vapor diffusion control is a separate function.
The WRB belongs between the cavity insulation and the studs so it can stop vapor before it reaches the sheathing
Connect the Barrier to the Drainage Outlet
Start with the actual wall base and cladding termination. Where a base flashing forms the outlet, lap the barrier onto its exterior-facing leg and maintain the specified clearance above grade. Work up the wall with upper courses shedding over lower courses. Attach and repair the material using the approved details. Inspect for tears, incompatible materials, reversed laps and open bypasses before covering the wall.
R703.4 calls for approved corrosion-resistant flashing that sheds water away from the wall cavity and structural framing. It covers exterior openings, listed masonry intersections, copings and sills, projecting wood trim, wood-frame deck and stair attachments, roof-to-wall intersections and built-in gutters. Self-adhered flashing membranes meet AAMA 711, and fluid-applied wall flashing membranes meet AAMA 714. Mechanically attached flexible flashing at window and door openings meets AAMA 712.
Under R703.4 Item 1, exterior window and door flashing drains to the exterior finish or to the WRB for further drainage. Follow the fenestration instructions and use the flashing manufacturer’s instructions for applications the fenestration instructions leave open. The section also allows a registered design professional’s detail or another approved method. Where instructions or details are absent, the sill gets pan flashing sealed or sloped to drain, plus head and side protection.
| Transition | Drainage detail to check |
|---|---|
| Flanged window with a drained sill | Install the specified pan before setting the unit. Turn it up at the jambs as detailed and connect the outlet over the lower WRB or to the exterior. Keep the designated drainage gaps or outlets clear. |
| Window jambs and head in the approved WRB-first example | Jamb flashing covers the side flanges and overlaps the pan flashing. Head flashing covers the head flange and extends over the jamb flashing. Bring the upper WRB flap down over the head flashing and seal as specified. |
| Shingle roof sidewall | Integrate the step flashing with the drainage plane and shingles. Lap the upper WRB over the flashing upstands or the integrated counterflashing as detailed. At the downhill eave termination divert runoff clear of the cladding. |
| Attached deck ledger | Michigan Rule 523a adds R507.2.4. Use approved corrosion-resistant flashing above the ledger per the corrected Figure R507.2.1(2) or another approved detail. Bring water off the WRB over that flashing. |
| Pipe, box or vent | Use the approved boot, flashing or block. In a shingle-lapped detail, the top of the flashing goes behind the upper WRB and the outlet goes over the lower WRB. Keep product outlets functional. |
| Anchored masonry veneer | Follow Table R703.8.4 for the backing and tie system. The common wood-stud and corrugated-tie detail has a nominal 1-inch airspace. Integrate support flashing with the WRB, and keep weeps open immediately above the flashing. |
For anchored masonry veneer, R703.8.5 places flashing under the first course above finished grade and at applicable supports such as shelf angles and lintels. R703.8.6 sets 33 inches on center as the maximum weep spacing and 3/16 inch as the minimum diameter. Michigan’s Rule 545 figures show the barrier, cavity, support flashing and weep relationship. Rule 509 places masonry inspection after the base-course flashing and WRB installation and after completion of masonry construction. Coordinate inspection visibility with the enforcing agency before concealment.
Worked Repair and Material Layout
A siding remodel has three flanged windows set without the sill pan called for in their approved detail. The lower seam was taped shut and the head flashing never tied into the upper WRB. Expose enough undamaged material to rebuild the laps. Where the sill cannot be flashed continuously in place, remove and reset the affected window. Install the selected pan so it drains out, place the unit with the approved sill-seal pattern, flash the jambs onto the pan, and place head flashing over both jamb flashings. Lap the upper WRB over the head detail and keep the exterior sill drainage outlets open. A separate interior perimeter seal can connect the frame to the air barrier without damming the sill pan. Use the applicable instructions for whether the window or WRB is installed first. DuPont publishes details for both sequences.
Roll takeoff. Assume a straight run 40 feet long and 16 feet high, with two horizontal courses of 9-foot HomeWrap and one 6-inch overlap between courses. The two courses cover 9 + 9 − 0.5 = 17.5 feet in height before trimming. Allow 6 inches at each end of each course for the specified overlaps into adjacent sheets, making each cut 41 feet long. Two full-length cuts use 82 linear feet, so one 9-by-100-foot roll supplies that run and leaves 18 linear feet before other cuts. The wall’s three openings do not shorten these full-run cuts. Check corner layout, opening returns and repairs before applying the remainder to another wall.
In the approved WRB-first flanged-window detail described in this lesson, how are the layers at the head arranged?
Head flashing covers the head flange and laps the jamb flashing, and the upper WRB flap laps over the head flashing
Upper house-wrap course first, then head flashing over the wrap, then the flange over the flashing
Head flashing behind the sheathing with the wrap tucked under the flange and the flange caulked to the wrap
Head flashing over the wrap with the flange sealed to the flashing using construction adhesive and no tape