54.3 Drywall Installation
Key Takeaways
Standard 1/2-inch board can go on a 24-inch-on-center ceiling when perpendicular, subject to the table footnotes and the relevant application.
Without adhesive, the wall screw row at 16-inch framing permits 16-inch spacing. The 5/8-inch Type X garage ceiling row beneath habitable rooms separately calls for 6-inch spacing.
Use the R702.3.5.1 material and depth for wood, thin steel or thicker steel. Follow the panel instructions for edge clearances and seating.
GA-214 Level 4 uses two separate coats over flat joints and one over angles after tape embedment, and three coats on fastener heads and accessories. Level 5 adds a full skim coat.
Select a listed backer and waterproofing system for tub and shower work. Check the intended fire or bracing assembly independently of its decorative finish level.
54.3 Drywall Installation
Gypsum board is the substrate for almost every interior finish in a Michigan house, and it does two jobs at once: it provides a surface for decoration and can contribute to required protection or wall bracing when installed as specified for that assembly. The MRC regulates the board and its fasteners in Chapter 7, and the fire-resistance role reappears in R302.6 for the garage separation.
Board types and thicknesses
| Board | Typical use | Limits and notes |
|---|---|---|
| 1/4 inch | Curved walls, overlay over existing board | Not a structural or standard ceiling surface |
| 3/8 inch | Repair work, light partitions | Ceilings only perpendicular at 16 inches; not under water-based texture |
| 1/2 inch | Standard walls and ceilings | See orientation and spacing rows below |
| 1/2 inch sag-resistant | Ceilings at 24 inches on center | Engineered core resists sag |
| 5/8 inch | Wall and ceiling applications | Check table orientation and load limits |
| 5/8 inch Type X | Specified fire-resistance assemblies and garage separation | Check the assembly and attachment schedule |
| Water-resistant gypsum backing board | Approved tile bases in the permitted setting | Check direct water/high humidity limits and the particular wet-area backer |
The application table, MRC Table R702.3.5, pairs thickness with framing spacing and orientation. Standard 1/2-inch board may be applied to walls with framing at 16 or 24 inches on center; on ceilings it is permitted at 16 inches on center in either direction, or at 24 inches when applied perpendicular to framing. A water-based texture requires perpendicular application. The minimum is 1/2 inch at 16-inch framing. At 24-inch framing use 5/8 inch or 1/2-inch sag-resistant ceiling board. The same footnote prohibits 3/8-inch single-ply ceiling board when it must support insulation.
For the garage separation, Table R302.6 specifies at least 1/2-inch gypsum or equivalent on the garage side separating the residence and attics, and 5/8-inch Type X or equivalent separating habitable rooms above the garage. Structures supporting the separating floor-ceiling assembly take at least 1/2 inch or equivalent. For a garage less than 3 feet from a dwelling on the same lot, the specified exterior wall portions require 1/2 inch or equivalent on the interior. Apply the perpendicular-wall exception and Table R702.3.5 attachments where applicable.
Moisture-resistant board has a narrow job. MRC R702.3.7 permits water-resistant gypsum backing board as the base for adhesive-set tile if it conforms to ASTM C1396, C1178 or C1278; it may be used on ceilings, it may not be installed over a Class I or II vapor retarder inside a shower or tub compartment, and cut edges must be sealed as the manufacturer directs. R702.3.7.1 then limits it: it may not be used where there will be direct exposure to water or continuous high humidity. For tiled tub and shower walls, use a backer identified in Table R702.4.2, following the approved product instructions and its role in the waterproof assembly.
Fastening schedule
The fastener schedule is the most testable table in the chapter. Without adhesive, MRC Table R702.3.5 sets these maximums:
| Board and location | Framing maximum | Nails | Screws |
|---|---|---|---|
| 1/2 inch wall | 16 inches | 8 inches | 16 inches |
| 1/2 inch wall | 24 inches | 8 inches | 12 inches |
| 1/2 inch ceiling | 16 inches, either direction | 7 inches | 12 inches |
| 1/2 inch ceiling | 24 inches, perpendicular | 7 inches | 12 inches |
| 5/8 inch wall | 16 inches | 8 inches | 16 inches |
| 5/8 inch wall | 24 inches | 8 inches | 12 inches |
| 5/8 inch ordinary ceiling | 16 inches, either direction | 7 inches | 12 inches |
| 5/8 inch ordinary ceiling | 24 inches, perpendicular | 7 inches | 12 inches |
| 5/8 inch Type X, garage ceiling beneath habitable rooms | 24 inches, perpendicular | 6 inches | 6 inches |
These are maximum fastener spacings without adhesive. Select the actual row, including the separate garage ceiling row. The table lists certain adhesive installations separately. For example, it permits 24-inch screw spacing on 1/2-inch or 5/8-inch wallboard with the specified adhesive and framing. Follow the required rated or bracing assembly where applicable.
Under R702.3.5.1, screws to wood framing can be Type W or Type S under ASTM C1002, with at least 5/8 inch of penetration. Cold-formed steel requires at least No. 6 screws. For steel thinner than 0.033 inch, use Type S under ASTM C1002 or the permitted ASTM C1513 bugle-head style with at least 3/8 inch of penetration. From 0.033 through 0.112 inch steel, use ASTM C954 or the permitted ASTM C1513 bugle-head style. Select the exact nail dimensions and type from the table. The special Type X ceiling row calls for 1-7/8-inch 6d coated nails or equivalent screws.
Follow board instructions for edges and fastening. For example, USG calls for a 3/8-inch edge and end clearance on its gypsum fiber panels. Set the head just below the face without tearing it. Add an effective fastener as the manufacturer directs if a head breaks the face.
Layout and hanging
Hanging ceilings first can simplify the ceiling-to-wall joint. Match the board layout to the required framing orientation. R702.3.5 requires edges and ends on framing except where perpendicular to framing. Follow the system's blocking, seam offsets and opening cutout details. Keep board clear of standing moisture, including at the bottom of walls.
Taping and finishing
Select tape, compound and beads as a compatible system. Where you use mesh, follow the manufacturer's compound requirements. Embed tape and apply progressively wider coats per the finish level. Follow the product for coat drying, bead attachment, sanding and primer. Remove dust before decoration.
GA-214-2021 finish levels
| Level | Joint and surface treatment | Typical use |
|---|---|---|
| 0 | No taping or finishing | Temporary work or decoration still undecided |
| 1 | Embed tape at joints and interior angles | Concealed or utility spaces where specified |
| 2 | Wipe embedded tape to leave a thin coat; apply one coat to fastener heads and accessories | Approved tile substrate or utility area |
| 3 | Add one coat over flat joints and interior angles after embedding tape; use two coats on heads and accessories | Medium or heavy texture or heavy-duty wallcovering |
| 4 | Add two coats over flat joints and one over interior angles after embedding tape; use three on heads and accessories | Smooth walls with flat paint or other suitable decoration |
| 5 | Complete Level 4 and apply a skim coat over the entire surface | Sheen, deep tones or critical lighting |
Choose the specified finish for the decoration and lighting. For Levels 3–5, leave compound smooth and free of tool marks. A skim coat reduces differences between the board face and joint treatment. A GA-214 level specifies surface finish. For a required fire-resistance rating, follow the tested assembly or other approved design, including its joint treatment.
Moisture and garage protection
R702.3.5 bars ordinary interior gypsum board where directly exposed to weather or water. Under R702.3.7 and R702.3.7.1, check the particular gypsum backing product and the moisture exposure, including the direct water and continuous humidity limits. Use Table R702.4.2 for tub and shower tile backers and follow the waterproofing system. Store board dry and allow the room and materials to meet the compound and coating requirements before finishing.
The prescriptive garage separation in R302.6 has specified materials and attachments. Its garage ceiling row applies beneath habitable rooms. GA-214 does not create a universal Level 1 requirement for these separations. Follow required approved plans and any assembly-specific instructions for joint treatment. Under R302.5.2, ducts serving the stated location have material and opening restrictions. For other penetrations, R302.5.3 points to the approved fireblocking material at annular spaces under R302.11, Item 4. The separate R302.7 rule requires 1/2-inch gypsum board on the enclosed side of walls, the under-stair surface and any soffits of accessible enclosed under-stair space.
Using screws without adhesive, what is the maximum fastener spacing for 1/2-inch gypsum board applied to walls with framing at 16 inches on center?
8 inches on center
12 inches on center
24 inches on center
16 inches on center
Which GA-214 level is typically specified for a smooth wall with flat paint in ordinary lighting, when no skim coat is specified?
Level 2
Level 4
Level 5
Level 1
What backer is acceptable for ceramic tile on a tub or shower wall?
1/2-inch moisture-resistant gypsum board alone
5/8-inch Type X gypsum board
A listed backer such as fiber-cement board or a cementitious backer unit
Regular 1/2-inch gypsum board with paint