51.2 Egress & Escape Openings

Key Takeaways

  • R310 requires an operable emergency escape and rescue opening in basements, habitable attics and every sleeping room, with stated exceptions. A qualifying window or door can serve the opening.

  • R310.2.1 requires 5.7 ft² net clear, or 5.0 ft² for grade-floor or below-grade openings. The 20-inch minimum width and 24-inch minimum height still apply.

  • Check both reference levels. The window sill is limited to 44 inches above the interior floor, and exterior finished ground determines grade-floor or below-grade classification.

  • A below-grade escape window needs a clear well. Provide at least 9 ft² with 36 inches of width and projection, required drainage, and a permanently affixed ladder or steps when well depth exceeds 44 inches.

  • Use normal operation from the inside to measure the opening. Check any covers, bars or opening control devices against their separate operation and clearance rules.

Last updated: November 2026

When the opening is required

The emergency escape and rescue opening (EERO) provides another way for occupants to get out and rescuers to get in. For a new dwelling, R310.1 calls for an operable opening in each sleeping room, basement and habitable attic. If the basement contains sleeping rooms, provide the opening in each sleeping room. An opening across the hall cannot serve one of those rooms. The opening must lead directly to a public way or to a yard or court that opens to one.

Storm shelters and basements used exclusively for mechanical equipment totaling 200 ft² or less are excepted. Under R310.5, an addition needs an opening in each new sleeping room and, ordinarily, in a new basement. The new basement does not need a separate opening if one is provided in its sleeping room or in an existing basement accessible from the new basement. R310.6 does not require adding an EERO for alterations or repairs to an existing basement unless the work creates a new sleeping room there.

Measure the escape path

Test2015 MRC criterion
Net clear opening areaAt least 5.7 ft², or 5.0 ft² at a grade-floor or below-grade opening
Net clear height and widthAt least 24 inches high and 20 inches wide
Interior window sillNo more than 44 inches above the floor
Exterior referenceGrade-floor opening sill within 44 inches above or below the adjacent finished ground under R202
OperationObtain the clear opening by normal operation from inside. The opening must operate without a key, tool or special knowledge.

The 2015 area exception names both grade-floor and below-grade openings. A deeper below-grade opening can qualify for 5.0 ft². Its window well still has to comply, and the interior sill measurement is separate.

Worked clear-opening checks

At 20 × 24 inches, a rectangular opening provides only 480 ÷ 144 = 3.33 ft², which fails even the smaller area requirement. For a window exactly 20 inches clear in width, the clear height must reach 41.04 inches at 5.7 ft², or 36 inches at 5.0 ft². For a window exactly 24 inches clear in height, the corresponding widths are 34.2 inches and 30 inches. These figures are based on the unrounded target areas of 820.8 in² and 720 in².

Consider a window that provides a clear 30 × 24-inch passage. At 5.0 ft², the window meets the area requirement when the sill is below exterior grade, assuming a compliant well, interior sill height and operation. The same unit in an ordinary upper-floor opening fails the 5.7 ft² test. A rectangular 25 × 34-inch clear opening provides 850 ÷ 144 ≈ 5.90 ft² and meets the standard dimensional minima.

Test Your Knowledge

What minimum net clear opening area applies to a new second-story bedroom escape window with a sill more than 44 inches above the adjacent exterior finished ground?

A

5.0 square feet

B

5.7 square feet

C

6.0 square feet

D

8.0 square feet

Wells, decks and bulkheads

A below-grade EERO window needs a well under R310.2.2 and R310.2.3. The well must provide at least 9 ft² of horizontal area and 36 inches in both projection and width, with room for the window to open fully. The required ladder or steps may intrude up to 6 inches into those dimensions.

A well deeper than 44 inches needs a permanently affixed ladder or steps usable with the window fully open. Use at least 12 inches of inside rung width and 3 inches of projection from the wall, with rung spacing no greater than 18 inches vertically throughout the well. Drain to the R405.1 foundation drainage system or an approved alternative. The drainage exception applies to the foundation on well-drained Group I soils described in Table R405.1. An opening under a deck or porch must remain fully operable and have a path at least 36 inches high to a yard or court.

A side-hinged or sliding door can serve under R310.3. If that escape opening is below adjacent ground, provide a bulkhead enclosure giving direct basement access and a net clear opening at least equal to the fully open door. The bulkhead drainage rule has the corresponding well-drained Group I soils exception. The dwelling’s ordinary required exit door is a separate provision. Michigan Rule 518 requires that door to be side-hinged and at least 36 inches wide by 80 inches high.

Keep the opening usable

Check the actual sash and hardware at the normal open position. A casement may swing largely clear, depending on its hinge geometry. In a double-hung window, measure the actual opening with the sash raised, including the limits imposed by the stops and frame. A slider’s usable width depends on sash travel. An awning’s projecting sash and hardware can restrict passage. A fixed pane has no operable opening. See Section 51.4 for published opening dimensions for two configurations of a double-hung unit.

Under R310.4, bars, screens, grilles and covers must preserve the required clear passage and release from the inside without a key, tool, special knowledge or greater force than normal opening. R310.1.1 permits ASTM F2090 window opening control devices. Under R312.2.2, releasing such a device must preserve the required net clear opening area. Operate the window and any cover together to confirm that one does not block the other.

Test Your Knowledge

What are the minimum horizontal dimensions of a window well serving a below-grade EERO, and when is a ladder required?

A

6 ft² area and 30-inch projection; ladder if deeper than 36 inches

B

9 ft² area and 24-inch projection; ladder if deeper than 60 inches

C

12 ft² area and 36-inch projection; ladder if deeper than 30 inches

D

9 ft² area with 36-inch projection and width; permanently affixed ladder or steps when the well is deeper than 44 inches

Test Your Knowledge

A new basement bedroom’s below-grade escape window opens to exactly 20 inches of clear width and 24 inches of clear height. Does it pass the clear-opening size test?

A

Yes, because it meets the separate width and height minima

B

Yes, because any operable below-grade window in a well passes

C

No, because its 3.33 square feet of net clear area is less than the 5.0 square feet required here

D

No, because the clear width must always be at least 30 inches