48.3 Blown-In Insulation
Key Takeaways
Select the chart for the installed product and application. Open-attic and dense-pack values differ.
FTC loose-fill labels list initial and settled thickness, quantity and coverage. Verify the installed depth and the chart’s required material loading.
Set the required attic markers before blowing. Use baffles to preserve soffit and eave airflow without sacrificing required eave coverage.
Verify lighting and flue clearances, existing wiring and the ceiling air barrier before installing loose fill.
Record the installed quantities and thicknesses. The Michigan 4 ACH50 prescriptive envelope test measures a different property.
Match the Material and Method
Blowing equipment moves loose fibers through a hose into open attics, irregular spaces and, with the correct setup, enclosed cavities. Fiberglass uses glass fibers. Cellulose products use treated paper fiber. Select the product by the approved application, such as open attic, dense-pack wall or stabilized installation. A wall density or a stabilized depth cannot substitute for the open-attic row. Correct active leaks before covering the work. In an existing attic, check the condition and position of the insulation before treating it as a usable layer.
16 CFR 460.12(b)(2) requires the coverage chart for all loose-fill home insulation to show initial installed thickness, minimum settled thickness, maximum net coverage per bag, bags per 1,000 square feet and minimum weight per square foot for listed R-values. It also requires the minimum package net weight and the machine and settings used to determine initial installed depth. Compare the chart for the bags actually delivered. Different products can have different depths and settling at the same R-value.
Prepare the Attic Before Blowing
- Seal gaps at the ceiling air barrier with materials allowed at that location, including the hatch and top-plate and penetration details. Michigan's Table N1102.4.1.1 does not let air-permeable insulation act as a sealing material.
- For air-permeable insulation in a vented attic, install baffles next to soffit and eave vents under N1102.2.3. Preserve an opening at least as large as the vent and extend the baffle above the fill. Where eave or cornice vents are installed, R806.3 also requires at least 1 inch between insulation and the roof sheathing and at the vent.
- For blown or sprayed fiberglass or cellulose roof and ceiling insulation under 2015 MRC N1101.12.1.1, attach at least one marker for every 300 ft² throughout the attic to trusses or joists, face the marks toward the attic access, and mark minimum initial depth in digits at least 1 inch high. A 1,200 ft² attic needs at least four markers. Check distribution and actual depth as well as material quantity.
- Keep required clearances at vents, chimneys and heat-producing equipment. Under E4004.9, keep insulation out of the space above and within 3 inches of a recessed luminaire’s enclosure, wiring compartment, ballast, transformer, LED driver or power supply unless the luminaire is identified for insulation contact (Type IC). For fixtures in the thermal envelope, amended N1102.4.4 requires IC rating, an air-leakage label of no more than 2.0 cfm at 75 Pa under ASTM E283, and a gasket or caulk at the housing-to-finish joint.
- If active knob-and-tube wiring is found, stop work in that area and have the electrical condition evaluated before covering it. NEC 394.12 prohibits surrounding that wiring with insulation in the specified hollow spaces.
Fill Open Attics and Closed Cavities Differently
Use the prescribed machine and settings, and spread the material evenly to the required initial thickness and weight. Check the edges, short bays and spaces around framing for inadequate fill. Do not cover the eave air channel to gain depth. As work proceeds, record the bags actually used.
For a retrofit wall, locate framing and its obstructions so each accessible portion can be filled. Use the manufacturer's dense-pack settings and confirm the installed density by the method specified for that system. For example, Greenfiber lists 3.5 lb/ft³ minimum installed density for the named SANCTUARY dry dense-pack wall and floor application. Airflow resistance in a dense-packed cavity does not replace the code-required air barrier.
Worked Example — 1,200 ft² to R-49
A Zone 6A attic project uses the R-49 prescriptive component value. Assume 1,200 ft² of net area and use the unadjusted loose-fill columns. For each product, check both chart quantity measures, round up to whole bags, and check minimum mass and actual depth at installation. The two manufacturers' sample charts show:
| Loose-fill product, open attic | Minimum initial depth | Minimum settled depth | Maximum net coverage per bag | Bags per 1,000 ft² | Minimum weight per ft² |
|---|---|---|---|---|---|
| Owens Corning AttiCat fiberglass, U.S. chart | 17 in. | 17 in. | 39.9 ft² | 25 | 0.688 lb |
| Greenfiber SANCTUARY cellulose, 25-lb nominal bag | 14.3 in. | 13.3 in. | 14.1 ft² | 70.8 | 1.80 lb |
For fiberglass, the per-bag limit gives 1,200 ÷ 39.9 ≈ 30.08 bags, or 31 bags rounded up. The rounded rate of 25 per 1,000 gives 30. For cellulose, 1,200 ÷ 14.1 ≈ 85.11, or 86 bags rounded up. The rounded rate of 70.8 per 1,000 gives 84.96 before rounding. Those are the lower bounds from the two coverage figures. The displayed minimum installed masses are 1,200 × 0.688 = 825.6 lb for fiberglass and 1,200 × 1.80 = 2,160 lb for cellulose. Verify the loading using the actual bag weights and revise the takeoff if needed. For example, with 25 lb per bag, 86 cellulose bags yield only 2,150 lb, so plan for at least 87 at that bag weight to meet all three displayed quantities. The Greenfiber example calls for 14.3 inches at application, with 13.3 inches as the settled minimum. A fixed depth allowance or generic R-value per inch would miss those product-specific conditions. If the product or chart revision changes, recompute the quantity and depth.
Verify the Installed Work
Under N1101.12.1, the insulation installer signs, dates and posts a certification at the job site. For blown fiberglass or cellulose, include initial and settled thickness, settled R-value, installed density, area and the number of bags used. Compare the records with depth markers and inspect coverage, concealed areas and clearances. Adequate installed depth and material loading both matter.
Where the ceiling table lists R-49, the separate prescriptive N1102.2.1 allowance permits R-38 over all ceiling area requiring insulation if its full uncompressed thickness extends over the wall top plates at the eaves. Protect the vents while maintaining that coverage. Michigan's 4 ACH50 prescriptive test is a separate measurement of enclosure leakage.
A 1,200 ft² attic has a loose-fill chart row showing 39.9 ft² maximum coverage per bag and 25 bags per 1,000 ft². What is the minimum whole-bag quantity that satisfies those two printed R-49 figures?
25 bags
30 bags
31 bags
40 bags
A cellulose coverage chart gives 14.3 inches initial installed depth and 13.3 inches minimum settled depth for R-49. What should the installer check?
Install at least 14.3 inches initially and meet the required bag loading. Use 13.3 inches as the minimum settled reference.
Install 13.3 inches and disregard the initial figure.
Treat the one-inch difference as fixture clearance.
Meet only the bag count without checking depth.
Why does the crew install baffles next to soffit and eave vents before blowing insulation into a vented attic?
To move attic intake to the ridge.
To keep loose fill out of the vents and maintain an airflow passage.
To hold the insulation depth markers.
To serve as the thermal barrier for sprayed foam.