35.4 Structural Loads & Load Paths

Key Takeaways

  • Table R301.5 sets 40 psf for rooms other than sleeping rooms, 30 psf for sleeping rooms, 50 psf for passenger vehicle garages, and 40 psf for decks and stairs.

  • Michigan prints 90 mph in R301.2(1). Use footnote (d), the applicable wind map and site exposure to establish the design input on the basis needed by the selected table.

  • Table R301.2(5) gives ground snow by jurisdiction, from 20 psf in most of Wayne County to 100 psf in three Keweenaw townships. Use the ground value where a table calls for it and determine roof snow load on its own design basis.

  • Table R301.7 limits floor live-load deflection to L/360, flexible-finish ceilings to L/240, and rafters steeper than 3:12 with no finished ceiling attached to L/180. In this deflection table, L is twice the cantilever length.

  • A typical interior joist at 16 inches on center has a tributary width of 1.333 feet. An even 40 psf live plus 10 psf dead produces 66.7 pounds per linear foot.

Last updated: November 2026

The Loads the Code Expects You to Know

Dead load is the weight of permanent construction, including framing, sheathing, roofing, insulation and finishes. R301.4 uses actual material and assembly weights, including fixed service equipment. Table R502.3.1 gives 10- and 20-psf dead-load cases for the listed floor joists. A heavy floor finish can change which case applies or put the floor outside the table.

Live load comes from use and occupancy, such as occupants, furniture and movable goods. Table R301.5 gives minimum uniform floor loads as well as separate component loads:

Use or componentMinimum load
Rooms other than sleeping rooms40 psf
Sleeping rooms30 psf
Habitable attics and attics served by fixed stairs30 psf
Uninhabitable attics with limited storage20 psf
Uninhabitable attics without storage10 psf
Exterior balconies and decks40 psf
Fire escapes40 psf
Passenger vehicle garages50 psf
Stairs40 psf
Guards and handrails200 lb concentrated
Guard in-fill components50 lb on 1 square foot

For limited-storage attics, apply the table footnotes to decide which portions receive 20 psf. Check access, joist or bottom-chord slope and insulation depth. Remaining portions are designed for the concurrent 10-psf load stated in note (g). An elevated garage floor must also support a 2,000-pound load on 20 square inches. Check an individual stair tread for the uniform load or a 300-pound load on 4 square inches, whichever produces higher stress. The top of a guard or handrail takes a single 200-pound load in any direction at any point. Infill takes 50 pounds applied horizontally normal to one square foot, independently of other live load under note (f). Check the separate glazing note where applicable.

Roof live load allows for activities such as roof maintenance. Use the tributary loaded area for the member on the roof’s horizontal projection. Table R301.6, using its 0–200, 201–600 and over-600 square-foot columns, gives 20/16/12 psf for flat roofs or slopes below 4:12, 16/14/12 psf from 4:12 up to but excluding 12:12, and 12 psf in each column at 12:12 or steeper. Use the greater of the applicable roof live load and the design roof snow load for the downward roof load check under R301.6.

Snow. Michigan Rule 515 supplies ground snow load by jurisdiction in Table R301.2(5). Examples are 20 psf in Monroe, Lenawee and most of Wayne County, with Northville listed at 25. Oakland and Macomb are 25 psf. Kent is generally 35 psf with 40-psf exceptions. Ingham generally uses 25 psf with 30 in Lansing and other listed jurisdictions. Washtenaw generally uses 25 psf with 20 in Ann Arbor and other listed jurisdictions. Houghton County generally uses 80 psf. Check its local exceptions. Keweenaw generally uses 90 psf, with 100 in the Townships of Eagle Harbor, Grant and Houghton. Use the value for the actual jurisdiction. R301.2.3 requires accepted engineering practice above 70 psf ground snow. At lower values, verify the limits and load basis of the specific prescriptive provision. Tables that ask for ground snow take the county input, while a roof-snow calculation uses its own design method.

Wind. Table R301.2(1) as amended by Michigan Rule 516 prints 90 mph. Footnote (d) directs the jurisdiction to the wind map and requires site-specific exposure under R301.2.1.4. For structural design under R301.2.1, establish the applicable ultimate design speed using Figure R301.2(4)A and the enforcing jurisdiction’s design criteria. Apply the wind-speed basis stated by the selected provision. For covered components and cladding, use Table R301.2(2) with the height and exposure adjustment in Table R301.2(3) unless otherwise specified. Where Figure R301.2(4)B triggers wind design, use an applicable R301.2.1.1 method such as WFCM, ICC 600, ASCE 7, AISI S230 or the IBC, subject to the specific exceptions.

Seismic. R301.2.2.1 assigns a seismic design category from Figure R301.2(2). The map basis is Site Class D. R301.2.2.1.1 provides an alternate determination using site spectral response under the IBC where soil conditions differ.

Michigan design criteria. The state table lists severe weathering, a 42-inch frost line subject to the R403.1.4 modification route, and the termite map in Figure R301.2(6), with local history under note (c). For ice barrier underlayment, check note (h) and Michigan’s local designation. Flood hazard criteria use the adopted effective maps, with the state fallback specified in note (g).

Load Path Continuity

R301.1 requires a continuous path that carries gravity, lateral and uplift forces from where they act into the foundation. The soil must then support the foundation reactions.

In a conventional platform-framed house, trace gravity from the roof covering and sheathing to the rafters or trusses. A truss carries load to its designated bearings. In a rafter roof with a structural ridge beam, follow that beam’s reactions down through its supports as well as the load at the exterior plates.

  1. Bearing walls carry roof or upper-floor reactions through their plates and studs. Under R602.3, studs run between their sole- and top-plate supports for out-of-plane resistance, with the listed opening-framing exception.
  2. Floor platforms transfer the loads into the floor joists, rim or blocking, then to bearings such as walls, girders and posts. Under R502.4, size joists for bearing partitions parallel to them. For a perpendicular bearing partition offset more than the joist depth, verify that the joists can carry the added load.
  3. Foundation walls and footings carry the collected reactions to the supporting soil. Verify bearing, continuity and the connection at each change of material or framing direction.

Follow separate paths for lateral loads and uplift. R502.2.1 directs the connection between the floor and braced wall panels above or below to R602.10.8. Roof-member attachment is checked under R802.11. The downstream exterior braced-wall connections that carry roof uplift are checked under R602.3.5, including applicable stories below the roof.

For the braced-wall check, Table R602.3(1) fastening is allowed in the stated wind and geometry case of 115 mph ultimate or less, Exposure B, pitch 5:12 or greater and roof span 32 feet or less. A separate fastening route allows a net uplift at the top of the wall of 100 plf or less, determined under R802.11 with a permitted reduction of 60 plf per full wall above. Where net uplift exceeds 100 plf and the first route is unavailable, use approved uplift connectors down to the foundation or the point where the force is 100 plf or less. The section also allows an engineered wall-sheathing and fastening design for combined uplift and shear. The roof-to-wall attachment check under R802.11.1 uses a separate force per connection.

Tributary Width and Worked Load Math

Tributary width is the width of loaded area assigned to one member. For equally spaced joists with the same tributary loading on both sides, the usual interior joist takes half of each adjacent bay. Check member spacing, edge conditions and any point load separately.

Example 1 — joist load. A simply supported interior joist at 16 inches on center carries a uniform 40 psf live and 10 psf dead. Its tributary width is 16 / 12 ft. Use the unrounded value to find a line load of 50 × 16 / 12 = 66.7 plf rounded. Across the 15-foot-5-inch distance between the idealized supports, the total is 50 × (16 / 12) × (185 / 12) = 1,028 pounds rounded. Each equal reaction is about 514 pounds. Check the selected bearing or hanger for this demand and the applicable R502.6 and product conditions.

Example 2 — girder and post. A center girder takes half the load from simply supported 14-foot joists on each side, giving it 7 + 7 = 14 feet of tributary width. At 50 psf, the floor contribution is 700 plf. A simply supported 12-foot girder with the stated uniform load has 8,400 pounds of floor load and 4,200 pounds at each end post. Add the girder and other supported loads as applicable, then check girder capacity, post and connection capacity, and footing bearing separately.

Example 3 — concentrated loads. A 300-pound tread load has a contact pressure of 300 ÷ (4 / 144) = 10,800 psf over those four square inches. It remains a 300-pound localized force when checking the supported tread. A filled 3,000-pound hot tub on a 6-by-7-foot platform averages about 71 psf across that footprint. Actual bearing points and occupants can change the member demands. Check the supports and framing for that specific loading under R301.1.3.

Load combinations. Apply prescriptive tables only within their stated loads and construction limits. When an element falls outside those limits, R301.1.3 directs its design to accepted engineering practice. Under the ASCE 7-10 allowable-stress method, D + L and D + (Lᵣ or S or R) are distinct checks for dead, floor live, roof live, snow and rain loads. The wind stability or uplift check includes the 0.6D + 0.6W case where dead load resists wind, alongside the other applicable combinations. Compare all applicable effects using one consistent design basis. The 2015 R507.2 ledger table’s note about nonconcurrent deck snow and live loads applies to that table.

Deflection Limits and Why Floors Feel Wrong When They Are Strong Enough

Table R301.7 caps deflection under live load and wind:

Structural memberAllowable deflection
FloorsL/360
Ceilings with brittle finishes (plaster, stucco)L/360
Ceilings with flexible finishes (gypsum board)L/240
Rafters steeper than 3:12 with no finished ceiling attachedL/180
All other structural membersL/240
Interior walls and partitionsH/180
Exterior walls, wind load, plaster or stuccoH/360
Exterior walls, wind load, other brittle finishesH/240
Exterior walls, wind load, flexible finishesH/120
Lintels supporting masonry veneerL/600

L is member span and H is wall span height. Use twice the projection for L in the cantilever deflection limit, so a 2-foot cantilever uses 4 feet in that calculation. For the exterior-wall wind check, note (a) permits 0.7 times the specified component and cladding ASD pressure. Note (d) sets H/180 for an exterior wall with interior gypsum board. Check the special sunroom and patio-cover cases in note (c) and the masonry veneer lintel reference in note (e).

A 15-foot-5-inch floor span is 185 inches, so L/360 permits 0.51 inch of live-load deflection. Check the deflection limit separately from bending, shear and bearing. A deeper member of the same width and stiffness has a larger section moment of inertia, which can reduce deflection. Use the actual grade and species row, member size and loading conditions when selecting a span.

Test Your Knowledge

What is the allowable live-load deflection for a residential floor member under Table R301.7?

A

L/240

B

L/360

C

L/180

D

L/600

Test Your Knowledge

A member supports a low-slope roof below 4:12 and carries 150 square feet of tributary area on the horizontal projection. What minimum roof live load applies under Table R301.6?

A

12 psf

B

16 psf

C

20 psf

D

30 psf

Test Your Knowledge

Typical interior floor joists are equally spaced at 16 inches on center. They carry an even 40 psf live plus 10 psf dead. What uniform load does one interior joist carry per linear foot?

A

40 plf

B

50 plf

C

60 plf

D

66.7 plf