48.1 Blanket Insulation
Key Takeaways
Blankets include precut batts and continuous rolls. Compare the product labels for width, thickness, package coverage and rated R-value.
Uniformly compressing fiberglass reduces its total R-value. Check the installed thickness using product data and repair voids separately.
Use approved materials to seal the air barrier. Fit the blanket around wiring and boxes and keep required ventilation and equipment clearances.
Michigan lists ceiling R-38 in Zone 5A and R-49 in Zones 6A and 7. The attic substitution requires 100 percent of the required ceiling area and full uncompressed depth over the eave top plates.
Count the lower joist bays by length. Use labeled package coverage for the continuous top layer and keep assembly performance separate from insulation-path R-value.
What Blanket Insulation Is
Blanket insulation is flexible fibrous material sold in continuous rolls or lengths cut at the factory, called batts. Both forms can be fiberglass. Mineral wool is also available in batts. Fiberglass comes unfaced or with facings such as kraft and foil-scrim-kraft. Check the package for the specific length, width, thickness, R-value and coverage. The wrap on the package is separate from the permanent facing on the insulation.
Batts are often sized for framing on 16- or 24-inch centers. With 1-1/2-inch framing, the usual clear widths are 14-1/2 inches and 22-1/2 inches. A manufacturer's batt may be slightly wider for a friction fit. Check actual widths at edges, corners and doubled members. The same labeled thickness can have different R-values. Owens Corning's fiberglass submittal lists both R-13 and R-15 at 3-1/2 inches, for example.
| Product examples | Labeled thickness | Insulation R-value |
|---|---|---|
| Owens Corning EcoTouch fiberglass wall batts | 3-1/2 in. | R-13 or R-15, depending on the product |
| Owens Corning EcoTouch high-density fiberglass wall batt | 5-1/2 in. | R-21 |
| Owens Corning EcoTouch standard R-38 and cathedral R-38C fiberglass batts | 12 in. and 10-1/4 in., respectively | R-38 |
| ROCKWOOL Comfortbatt stone-wool wood-stud products | 5-1/2 in. | R-21 or R-23, depending on the product |
Where Blankets Go
- On an attic floor, fit the cavity layer and run a continuous unfaced layer across the joists when the design calls for it. Keep insulation away from required clearances and keep the attic hatch accessible.
- In exterior wood-frame walls, the amended Michigan table uses R-20 or R-13 cavity plus R-5 continuous insulation or qualifying insulated siding for the conventional prescriptive options. A well-fitted R-13 batt alone does not meet that component value.
- For floors over unconditioned space, Michigan lists R-30 in Zones 5A and 6A and R-38 in Zone 7, with a table footnote allowing the full-cavity option at a minimum of R-19. Check subfloor contact and air-barrier continuity under the floor installation provisions.
- In a vented cathedral ceiling, choose insulation and rafter depth that leave the required space beneath the roof sheathing at eave or cornice vents. An Owens Corning R-38C batt rated at 10-1/4 inches fits beneath a 1-inch vent space in an 11-1/4-inch rafter bay if the detail provides that full clearance.
Michigan Ceiling Values
Michigan Rule 547d's Table N1102.1.1 lists R-38 for Zone 5A and R-49 for Zones 6A and 7. For ceilings with attic space on the prescriptive R-value route, N1102.2.1 lets R-30 substitute for R-38 or R-38 for R-49. The reduced R-value must cover the entire ceiling area requiring insulation and extend at full, uncompressed height over the wall top plates at the eaves. The U-factor and total-UA alternatives use their own criteria. Check the county's zone when the plans do not state it.
Fit Batts Without Gaps or Unplanned Compression
Choose the label thickness that fits the designed space. For uniformly compressed fiberglass, the total R-value decreases while resistance per inch can increase. A thickness ratio alone cannot determine the installed R-value. Use manufacturer data at the actual thickness. Where those data are absent, use an applicable accepted inspection reference at a listed depth. NAIMA's installation example estimates about R-10 when a labeled R-13, 3-1/2-inch fiberglass batt is uniformly compressed to 2 inches while filling the space behind blocking. That is an estimate for the example, rather than a product rating or a design recommendation. Michigan's table footnote requires the installed resistance to meet the component minimum when the insulation is fitted into a shallower cavity.
Air-seal the enclosure at the designated air-barrier plane before insulation. The state's installation table prohibits using air-permeable insulation as a sealing material. Use approved, compatible sealants and respect fire and equipment clearances. Fit batts neatly around boxes. Split or cut insulation to fill the space on both sides of wires or pipes as appropriate to the assembly. Install facing and flanges per the specified product and vapor-control design. Store packages dry and let material recover to its rated thickness.
Worked Example — Two Layers in a 1,200 ft² Attic
A 40-by-30-foot attic with 30 full-length, 30-foot joist bays on 16-inch centers is designed to meet the Zone 6A prescriptive R-49 ceiling value. For the takeoff, assume an unobstructed rectangular area and approved framing with a cavity deep enough for a full 12-inch lower layer that reaches the joist tops.
- Between joists. Select the standard R-38 batt rated at 12 inches for that cavity. Verify actual bay widths. The takeoff is 30 bays × 30 feet = 900 linear feet of batt. A 4-foot batt yields a theoretical minimum of 225 batts before waste, assuming usable cutoffs. Count the bays and fit cuts in the field. The 1,200 ft² includes the framing and cannot be divided by the batt width to count those bays.
- Across the framing. Lay unfaced R-13 insulation over the whole 1,200 ft², keeping the layers in contact at the insulated field without compressing either layer. Divide 1,200 ft² by the upper product's labeled package coverage and round up. Keep both layers at their rated thickness and account for the access opening, cutting, ventilation and clearances.
- Check the proposed design. Full R-38 and R-13 layers give an R-51 insulation path where both layers are present. The insulation sum is not the whole-assembly U-factor across framing. Check actual coverage, structure, air seal and eave details. If field measurements show a shallower or deeper bay, revisit both product thickness and layer fit before using this assembly.
To use the separate prescriptive R-38 allowance instead, verify full-area coverage and full uncompressed R-38 over the top plate at the eaves.
A labeled R-13 fiberglass batt, 3-1/2 inches thick, is uniformly compressed into a 2-inch-deep space behind solid blocking. Which statement is correct?
The installed total R-value is lower. Check the product data at 2 inches instead of scaling by the thickness ratio.
It maintains R-13 because no fibers were removed.
Higher density gives a total R-value above R-13.
Only facing permeance changes.
What distinguishes an insulation roll from a precut batt?
Only rolls are available with facings.
Rolls always have a higher R-value per inch.
A roll is a continuous length cut on site. A batt comes in precut lengths.
A roll is loose fill, and a batt is rigid fiberboard.
What minimum ceiling insulation R-value does Michigan Table N1102.1.1 list in Climate Zone 6A before applying the separate attic allowance?
R-30
R-38
R-60
R-49