53.2 Siding Types & Selection

Key Takeaways

  • R703.11 requires vinyl siding certified and labeled to ASTM D3679. Check R703.3.1 wind limits and use the applicable R703.11.2 attachment and wind-rating route when siding over foam.

  • R703.10.2 covers fiber-cement lap siding up to 12 inches wide with a minimum 1-1/4-inch lap. MIOSHA Part 690 incorporates Table 1 silica controls, including the outdoor dust-collection option for small fiber-cement saws.

  • Table R703.6.1 gives No. 1 grade sidewall exposures. A 24-inch shingle allows 10-1/2 inches single-course or 16 inches double-course. The No. 2 grade double-course limit for that length is 14 inches.

  • Follow the product’s wood lap detail and the adopted fastening schedule. Without a manufacturer’s lap recommendation, R703.5.3 uses at least 1 inch of lap, or 1/2 inch for a rabbeted profile.

  • At 8-inch exposure, 100 square feet of lap siding needs 150 linear feet. At that exposure, 1,200 net square feet with 10 percent waste requires 1,980 linear feet.

Last updated: November 2026

Compare products by the backing and fasteners they require, how each handles moisture and movement, and what it takes to maintain the finish. In Michigan, check the wind exposure and site criteria before selecting an attachment schedule. Leave drainage outlets open and use the right clearances where snow or runoff can persist.

Vinyl (MRC R703.11)

An approved quality-control agency certifies and labels conventional vinyl siding to ASTM D3679 (R703.11). Follow the specific manufacturer’s instructions. Many horizontal vinyl products use slotted hems and loose fastener heads so the panel can move, as in the VSI example in the preceding lesson. Insulated vinyl has a separate ASTM D7793 certification under R703.13, with installation under R703.13.1 and the applicable wind and backing provisions.

Wind. Under R703.3.1, design the attachment for components and cladding if design wind pressure exceeds 30 psf or the limits of Table R703.3.1 are exceeded. Use the applicable pressure from Table R301.2(2), adjusted for height and exposure under Table R301.2(3), with 10 square feet effective wind area for this attachment check. Michigan Table R301.2(1) prints 90 mph. Its footnote (d) directs the jurisdiction to the wind map and requires site-specific exposure. Confirm the applicable ultimate wind speed and exposure before using the foam attachment provisions.

Foam backing. R703.11.2 allows ordinary R703.11.1 installation where the foam lies directly on approved backing that can independently resist the design wind pressure. For the R703.11.2.1 route, the site must be Exposure B with an ultimate speed of 115 mph or less. The inside face needs gypsum board, a gypsum panel product or equivalent. Minimum nominal foam thickness is 1/2 inch XPS or polyiso, or 1 inch EPS, meeting the specified standards. Nails at 16 inches on center have at least a 0.120-inch shank and 0.313-inch head, penetrating wood framing by at least 1-1/4 inches.

If those conditions are unmet, under R703.11.2.2 multiply the manufacturer’s solid-sheathing design pressure rating by 0.39 with interior gypsum or equivalent, or 0.27 without it. The adjusted rating must meet the required pressure. An approved rating specifically for installation over foam is another route under R703.11.2.3, with its manufacturer’s installation details.

Plan access for panel replacement, and check exposed locations for impact. Check that replacement panels use a compatible lock and profile.

Wood lap and board-and-batten (R703.5)

Table R703.3(1) puts wood rustic and drop siding at a 3/8-inch minimum and gives substrate-specific fastening. Where the manufacturer gives no recommendation, R703.5.3 calls for at least a 1-inch lap, or 1/2 inch with a rabbeted profile, and an allowed end treatment using caulking, a batten, or a seal over flashing. The Western Red Cedar Lumber Association bevel profile guide recommends laps of 1 inch for nominal 4- and 6-inch boards, 1 to 1-1/8 inches for 8-inch, 1 to 1-1/2 inches for 10-inch, and 1 to 2 inches for 12-inch boards.

For that Western red cedar bevel example, use one face nail per piece at each stud, at no more than 24 inches on center under the profile guidance. Place it just above the overlap so the two courses can move separately. Stagger butt joints and place them on studs. The guide’s 1/8-inch clearance applies to its rabbeted profile detail. Use the applicable Michigan schedule for the installed wall. The cedar guide shows 1-1/4 inches into solid wood. The Michigan prescriptive requirement under R703.3.3 is 1-1/2 inches into studs, studs plus wood sheathing, or blocking. For vertical board-and-batten wood siding, R703.5.1 places horizontal nailing strips or blocking at no more than 24 inches on center.

Protect end grain and maintain the finish specified for the siding. A finish reduces moisture uptake, and the wall still needs a path to drain and dry. For unfinished cedar, evaluate weathering and replacement access with the owner.

Shingles and shakes (R703.6)

R703.6 uses CSSB grading rules. R703.6.1 covers single and double courses over nominal 1/2-inch wood-based sheathing or over furring on nominal 1/2-inch nonwood sheathing. Its WRB detail calls for 2-inch horizontal and 6-inch vertical laps. Where specified, nominal 1-by-3 or 1-by-4 horizontal strips are spaced to match the actual exposure and fastened into studs with the specified 7d or 8d box nails. For a nonpermeable WRB the code calls for vertical furring first, then horizontal strips. The section specifies 1/8 to 1/4 inch between shingles, 3/8 to 1/2 inch between shakes and at least 1-1/2 inches of offset at joints in neighboring courses. Check the selected shingle grade, species and manufacturer’s detail in addition to the code.

Test Your Knowledge

Under MRC R703.10.2, what is the minimum lap for fiber-cement lap siding, and what width does that section cover?

A

1 inch lap; 8-inch maximum width

B

1-1/4 inch lap; 12-inch maximum width

C

2 inch lap; 16-inch maximum width

D

1/2 inch lap; 10-inch maximum width

The Table R703.6.1 limits below apply to No. 1 grade wall shakes and shingles. Read across for the actual piece length and number of courses.

ProductLengthSingle courseDouble course
Shingles16 in.7 in.12 in.
Shingles18 in.8 in.14 in.
Shingles24 in.10-1/2 in.16 in.
Shakes18 in.8 in.14 in.
Shakes24 in.10-1/2 in.18 in.

For No. 2 grade shingles, the double-course limits are 9, 10 and 14 inches for 16-, 18- and 24-inch shingles, respectively. Under R703.6.3 use two corrosion-resistant fasteners per piece. The section specifies Type 304 or 316 stainless or hot-dipped galvanized box nails meeting ASTM A153D at 1 ounce per square foot, and allows specified 16-gage stainless staples. For single-course work, conceal the fasteners about 1 inch above the next course’s butt line and 3/4 inch from each edge. In double-course work, face-fasten the exposed piece about 2 inches above its butt and 3/4 inch in from each edge. Penetrate the sheathing or furring by at least 1/2 inch and avoid overdriving. Use Type 316 for the covered treated shakes and shingles and within the specified saltwater coastal zone. R703.6.4 requires doubled bottom courses.

Metal, fiber cement, engineered wood, and veneer

Aluminum siding is light and can dent. Use aluminum nails for the horizontal aluminum rows in Table R703.3(1). For example, the table limits unbacked 0.019-inch horizontal aluminum to panels up to 10 inches wide with up to 8 inches of flat area. Steel siding uses a protected finish and comes in factory profiles or can be formed on site from coil for certain systems. Its openings, laps and cut ends need the selected detail. For the EDCO steel panel example, center fasteners in the slots at 16 inches on center, leave at least 1/32 inch under heads, and select nails that reach at least 3/4 inch into the stud. Compare the selected product schedule with the code’s basis, including the R703.3.3 requirements for the substrate and wind conditions.

Fiber cement. R703.10 accepts ASTM C1186 Type A, Grade II or better, or ISO 8336 Category A, Class 2 or better. Lap siding up to 12 inches wide needs at least 1-1/4 inches of lap. Non-tongue-and-groove ends need a permitted treatment or a design meeting R703.1. The prescriptive table shows 5/16-inch nominal lap siding and substrate-specific fasteners. Use that table or the approved product schedule under R703.10.2. R703.10.1 gives separate panel joint and fastening rules.

For the HardiePlank HZ5 example, the manufacturer’s installation guide shows a 1-1/4-inch-wide starter strip and recommends blind nailing about 1 inch below the top edge. On the cited wood-framed detail the plank ends land on studs and joint flashing protects the butt joints. Use the finish-specific cut-edge treatment. The illustrated HZ5 clearances are 6 inches above ground, 2 inches at the roof, deck or paved slab, and 1/4 inch above horizontal flashing, with the flashing gap open. HardieZone designations are product regions. Confirm the current product and instructions for the job location.

Silica. MIOSHA Part 690 adopts the relevant sections of 29 CFR 1926.1153. Table 1 item (iii) covers outdoor cutting with a handheld saw having a blade up to 8 inches in diameter. Use commercial dust collection at or above the tool maker’s airflow with a filter at least 99 percent efficient, and follow the tool instructions. No respirator is specified for either duration column when that row’s controls are fully implemented. For other setups, apply the appropriate Table 1 row or the standard’s alternative exposure-control method, and follow the siding maker’s cutting instructions.

Concrete and masonry veneer. For anchored brick, stone or concrete units, R703.8 covers structural support, corrosion-resistant ties, WRB, drainage space and flashing. Consult Michigan Rule 545 for the state’s support and wall-detail figures. In the drained assembly keep the R703.8.6 weeps no more than 33 inches on center, at least 3/16 inch in diameter and immediately above the flashing. Adhered concrete or masonry veneer has its own R703.12 attachment, clearances, WRB and foundation drainage details. Chapters 44 and 45 develop the support and flashing checks.

Engineered wood lap siding uses a bonded wood substrate with a specified finish and edge treatment. For example, LP SmartSide lap siding is recognized in ICC-ES ESR-1301. The product instructions give a 3/16-inch gap at window or door trim to be sealed and a separate set of butt-joint options. Check the selected profile, backing, fastener schedule and finish details before ordering.

Comparison

TypeMain installation checkService or repair check
VinylSecure locks and free movement in slots and receiversMatch the profile for panel replacement
Wood lapProfile-specific lap, siding nails and protected endsInspect the finish and end grain
Shakes and shinglesGrade-specific exposures and spaced, offset jointsKeep course terminations and drainage clear
AluminumUse the specified nail material and profile supportAllow for dents in exposed areas
SteelProtect cut ends and select the correct attachmentRepair finish damage as the maker directs
Fiber cementSupport joints, provide clearance and control cutting dustMaintain finish and keep flashing outlets open
Engineered woodDetail trim gaps and protect field-cut edgesKeep moisture-sensitive edges above wet surfaces
Anchored or adhered veneerChoose the correct support and drainage systemKeep weeps or the specified drainage outlet open

Worked example: coverage for a 1,200 ft² wall

A rectangular wall area 40 feet wide and 30 feet high, with no openings in the example, has 1,200 net square feet. The selected lap siding has 8-inch exposure and the estimate allows 10 percent waste.

  1. Order area: 1,200 x 1.10 = 1,320 ft² = 13.2 squares (a square is 100 ft²).
  2. Coverage per course: one course on a 40-foot wall covers 40 x (8 ÷ 12) = 26.67 ft².
  3. Courses: 360 inches ÷ 8 inches per course = 45 courses. Use unrounded exposure for this calculation.
  4. Linear feet: 45 x 40 = 1,800 LF net; 1,800 x 1.10 = 1,980 LF.
  5. Shortcut: linear feet per square = 100 ÷ (exposure in feet) = 100 ÷ (8/12) = 150 LF per square; 13.2 x 150 = 1,980 LF.
Exposureft² per 40-ft courseLF per square
6 in.20.0200
8 in.26.7150
10 in.33.3120

If the selected product is packaged 2 squares per carton, order 7 cartons for 13.2 squares. For a wall with gables and openings, estimate net area by shape first, then check the cut layout and product packaging before applying a waste allowance.

Test Your Knowledge

Using Table R703.6.1, what is the maximum weather exposure for 24-inch No. 1 grade wood shingles installed double-course on a sidewall?

A

10-1/2 inches

B

12 inches

C

14 inches

D

16 inches

Test Your Knowledge

A wall has 1,200 net square feet to cover with lap siding at 8-inch exposure. Add 10 percent of the net quantity for waste. How many linear feet does the estimate require?

A

1,800 LF

B

1,980 LF

C

2,178 LF

D

1,620 LF