49.4 Sound Insulation

Key Takeaways

  • STC measures airborne isolation, and IIC measures the impact isolation of a floor-ceiling assembly. Use the complete tested construction.

  • Michigan’s 2015 Residential Code adopts Appendix K. Covered dwelling separations use the STC 45 and IIC 45 laboratory criteria as applicable.

  • The 2021 Michigan Building Code has its own Section 1206 scope and named field ratings. Apply the code governing the building.

  • Maintain cavity fill, mass, decoupling and penetration protection as detailed. Inspect the adjoining structure for flanking paths.

  • A floor-finish change can affect IIC and STC by different amounts. Compare each result to the required criterion.

Last updated: November 2026

Airborne Sound and Impact Sound

Airborne sound includes voices and television. Impact sound starts when a footstep or other blow excites the floor. Sound can pass through the wall or floor-ceiling assembly or bypass it through connected framing, ducts, gaps and other flanking paths.

RatingWhat it describesLaboratory route
STC (Sound Transmission Class)Resistance of an assembly to airborne sound transmissionASTM E90 measurements, classified under ASTM E413
IIC (Impact Insulation Class)Resistance of a floor-ceiling assembly to impact soundASTM E492 tapping-machine measurements, classified under ASTM E989

A higher rating indicates better isolation for the relevant test. It describes the tested assembly and frequency range. Look up the complete construction, including board layers, studs or joists, cavity fill, channels, floor finish and the attachment pattern. Lab ratings do not predict a specific level of speech privacy or a fixed result in the field. Continuous framing or openings can carry sound around even a well-built partition.

Which Michigan Requirement Applies?

Under Rule 500, Michigan adopts Appendix K with the 2015 Michigan Residential Code. AK101 and AK102 apply airborne separation to walls and floor-ceiling assemblies dividing dwelling units, including adjacent townhouses. AK102 specifies STC 45 tested under ASTM E90, with the permitted TMS 0302 calculation route for concrete or clay masonry. Protect the rating at penetrations, and fit dwelling-unit entrance doors from common spaces tightly to the frame and sill. AK103 specifies IIC 45 under ASTM E492 for floor-ceiling assemblies between units or between a dwelling unit and public or service space. An ordinary bedroom partition within the same dwelling is outside this separation requirement.

Check the building's actual code before you choose an assembly. For projects governed by the 2021 Michigan Building Code, Section 1206.2 covers assemblies separating dwelling and sleeping units from one another or from public or service areas. Its airborne minimum is lab STC 50 or field Normalized Noise Isolation Class (NNIC) 45 under ASTM E336. Section 1206.3 sets a lab IIC 50 or field Normalized Impact Sound Rating (NISR) 45 under ASTM E1007 for the covered floor-ceiling separations. Use the named field metric if you use that route. Fire separation or a project acoustic specification may impose separate criteria. Follow the approved fire assembly and penetration protection as well as the acoustic details.

Controlling the Sound Path

  • Mass. An approved assembly may use additional gypsum layers to increase airborne isolation. Follow the tested thicknesses, fastening and joint details.
  • Decoupling. Staggered or double-stud walls and resilient channels or clips can reduce direct vibration transfer. Use the system's attachment details. A fastener that runs through a resilient channel into the framing can bypass the intended separation.
  • Cavity absorption. Fiberglass or mineral-wool batts specified for an assembly absorb sound in the cavity. Match the tested thickness and installation. The batt's thermal R-value does not rate the wall's isolation.
  • Openings and bypasses. Treat perimeter joints, outlets, ducts and other penetrations as detailed for the assembly. Use approved acoustical materials and preserve required fire protection. Inspect adjoining floors, ceilings and framing for flanking paths before closing the work.
  • Impact. A specified resilient underlayment or floor finish can help control footfall at its source. Match the tested floor build-up, and avoid rigid bridges through the resilient layer.

Worked Test Comparison

USG reports two laboratory results for a wood floor-ceiling assembly in Plaster Systems SA920. Use the paired cases with the same nominal 1¼-inch wood floor. The second includes the specified carpet and pad over that floor.

USG testFloor finishSTCIIC
CK-6412-7Wood floor3832
CK-6412-8Wood floor with tested carpet and pad3956

The second configuration improves the impact rating by 56 − 32 = 24 points and the airborne rating by 39 − 38 = 1 point. For the stated Michigan residential separation requiring both lab ratings of 45, the second result clears the IIC value, and the STC result still falls 6 points short. Choose an assembly substantiated for both criteria, plus any applicable fire rating. Before approving a floor-finish substitution, compare the submitted test with the joists, resilient ceiling, cavity fill and subfloor on the project. Suppose the supplier offers a pad with a report showing IIC 56 on a concrete slab. That rating describes the concrete assembly in the report. Keep the wood-floor substitution pending until there is evidence for the proposed assembly. AWC Technical Report 15 explains that the finish interacts with the base construction and can raise or lower its impact rating.

Test Your Knowledge

Which change addresses airborne sound transfer through a shared stud wall when the approved assembly includes it?

A

Install the specified resilient channel and gypsum without bridging the channel into the studs.

B

Place radiant-barrier foil directly behind the gypsum.

C

Raise the batt label from R-13 to R-15 while assuming the wall STC rises by two points.

D

Change the carpet in a neighboring room and assume the wall rating rises.

Test Your Knowledge

In the USG example, the carpeted floor-ceiling assembly tests at STC 39 and IIC 56. How does it compare with a residential floor requiring STC 45 and IIC 45?

A

It reaches both criteria.

B

It reaches only the airborne criterion.

C

It misses both criteria.

D

It reaches the impact criterion and falls short on airborne isolation.

Test Your Knowledge

A new townhouse project falls under the 2015 Michigan Residential Code. Which lab sound criterion applies to the wall separating adjacent dwelling units under Appendix K?

A

IIC 45.

B

STC 45.

C

STC 50 under the residential appendix.

D

No requirement until a local ordinance separately adopts the appendix.

Sections you finish are checked off in the contents.