57.3 Hazardous Materials on the Jobsite

Key Takeaways

  • On a Michigan construction site, Part 18 Rule 1877 prohibits storing portable LPG containers indoors and requires protection from tampering and the outdoor setback in Table 4. Rules 1875 and 1884 govern specified containers connected for use.

  • Part 18 Rule 1863 allows at most 25 gallons of flammable liquid stored in a room outside an approved cabinet. Rule 1862 recognizes approved safety cans, DOT-approved containers and specified original-container allowances.

  • For welding and cutting, Part 7 requires stored oxygen cylinders to be separated from fuel-gas cylinders, highly combustible material or ignition by at least 20 feet or by a noncombustible wall at least 5 feet high with a 30-minute fire-resistance rating.

  • Michigan Part 690 uses the task, tool, setting and shift duration in the adopted silica Table 1. Integrated water delivery is an outdoor-only Table 1 option for handheld grinding other than mortar removal.

  • Part 24 requires a qualified, experienced operator to attend a fired tar kettle and specifies temperature indication, extinguisher capacity and clearances.

Last updated: November 2026

Handling Propane, Gasoline, Solvents and Paint

Use the jobsite rules for the actual operation. A portable cylinder waiting to be used is a storage question. A cylinder feeding a temporary heater is an equipment and clearance question. A container of gasoline is a flammable-liquid question.

Propane cylinders

Michigan Construction Safety Standard Part 18, R 408.41877, prohibits indoor storage of portable LPG containers, including empty containers that have been in service. Store the containers outdoors, using Table 4 for distance from buildings and protecting them against tampering with a suitable ventilated enclosure or equivalent means. Keep valves closed in storage and protect them in accordance with the container design. Protect the setup against vehicle strikes where that hazard exists. Propane vapor can collect in low spaces and reach an ignition source. Keep ignition sources away, post the required warning and prohibit smoking within 25 feet of flammable material under Rule 1861.

For example, three 100-pound cylinders awaiting use represent 300 pounds of LPG at full nominal capacity. Table 4 allows zero feet of building separation for up to 500 pounds. The cylinders still belong outdoors, protected from tampering and subject to other applicable clearances. Use an upright secured arrangement for these upright-design cylinders. The Table 4 setback does not authorize indoor overnight storage.

Part 18 treats containers connected to temporary heat separately in Rules 1875 and 1884. Use approved equipment with adequate fresh air, and follow the heater, hose, regulator, placement and container provisions. A nonintegral LPG heater, for example, generally needs at least 6 feet between the heater and any LPG container. The rule separately allows qualifying integral designs. Check the manufacturer's prescribed inspection and leak-check procedure. If gas is escaping and cannot be controlled safely, clear the area and use the emergency plan.

Gasoline and flammable liquids

Part 18 Rules 1862–1869 cover approved containers and portable tanks, inside and outside storage, dispensing, point-of-use handling and refueling.

  • For handling and use of 5 gallons or less, use an approved safety can or DOT-approved container. Rule 1862 allows original shipping containers for extremely viscous products and original containers for quantities of 1 gallon or less under its terms. An open pail or a milk jug is not an approved fuel container.
  • Inside a room, limit flammable liquids stored outside an approved cabinet to 25 gallons. A cabinet may hold up to 60 gallons of categories 1–3 or 120 gallons of category 4, under Rule 1863. Check the limits for the storage area, the requirements for a dedicated storage room and the outside storage provisions. Keep egress clear.
  • When transferring categories 1–3 between containers, electrically bond the containers under Rule 1867. Use the authorized dispensing arrangement. Rule 1868 requires ventilation capable of keeping vapor below 10% of its lower explosive limit when handling or using a flammable liquid. That fire limit does not establish a safe inhalation exposure.
  • Shut off the motor during refueling. Keep ignition sources at least 25 feet from refueling or flammable-liquid dispensing under Rule 1869, and post the required warning. Match fire protection and spill supplies to the location and material. Keep gasoline out of cleaning operations.

Solvents, adhesives and paints

Read each formulation's label and SDS. Start with a compatible lower-hazard product if the specification permits, minimize open containers and use suitable ventilation. Assess ignition sources and airborne exposure separately. Select gloves and eye protection for the product and contact conditions. A solvent-resistant glove for one coating may offer inadequate protection for another. If respirators are required, apply Part 451 to the assessed exposure and conditions.

For existing painted surfaces, identify the building, age, planned disturbance and lead information before starting. Federal RRP applies to covered renovation in pre-1978 housing or child-occupied facilities. Michigan Part 603 independently addresses the employer's construction lead exposure duties. The product SDS for fresh paint does not characterize dust from old paint.

Match the Control to the Hazard

Material or operationWhat to checkExample controls
Portable LPG storageLeaks, ignition, tampering and impactsStore outdoors per Part 18 Table 4. Use protected storage and keep ignition sources away
Gasoline transfer and refuelingFlash fire, static ignition and vapor accumulationApproved containers, proper dispensing equipment, bonding where required and motor off during fueling
Solvents, adhesives and coatingsProduct-specific flammability, inhalation and skin or eye effectsClosed containers, suitable ventilation, ignition control and SDS-informed protective measures
Silica-containing concrete and masonryExposure from the specific tool, task and settingFollow the exact Table 1 control row and housekeeping requirements or follow the alternative exposure-control provisions
Tar kettleBurns and ignition from heated material and fuelAttend while fired, use a working temperature gauge and set out Part 24 fire protection
Pressure-treated lumberDust and treatment chemicals during cutting and handlingFollow the treatment manufacturer's label and SDS, control dust and keep offcuts out of burn piles
Wet portland cementAlkaline burns and dermatitisChemical-resistant gloves and boots, splash protection and prompt removal of contaminated clothing and cement

Silica controls depend on the row

MIOSHA Construction Health Standard Part 690 adopts 29 CFR 1926.1153 for construction. Table 1 item (xii) covers handheld grinders for uses other than mortar removal. Use integrated water delivery for that row only outdoors. For indoor slab-edge grinding with a handheld grinder, use a commercially available shroud and dust collection system. The collector needs at least 25 cfm per inch of wheel diameter, a filter with at least 99% efficiency, and a cyclonic pre-separator or filter-cleaning mechanism. Use the tool per the manufacturer's instructions. Provide exhaust as needed indoors to minimize visible airborne dust. For this indoor task, Table 1 requires an assigned protection factor of at least 10 when the total time on Table 1 tasks exceeds 4 hours in the shift. Mortar removal uses a different row and different respirator requirements.

If the employer does not fully and properly implement Table 1 or the task is absent from it, apply the alternative exposure-control requirements, including assessing exposure and meeting the permissible exposure limit of 50 micrograms per cubic meter as an eight-hour time-weighted average. Dry sweeping or brushing that could contribute to silica exposure is allowed only when lower-exposure methods are infeasible. Compressed air for cleaning that could contribute to exposure has its own narrow exceptions, including capture by a ventilation system. Plan wet or HEPA-filtered cleanup when feasible.

Welding, cylinders and tar kettles

Under Part 7 Rule 722, a stored oxygen cylinder for welding or cutting needs separation of 20 feet from fuel-gas cylinders, highly combustible material or ignition sources, or a noncombustible wall at least 5 feet high rated for at least 30 minutes. Protect cylinders against damage and follow the applicable positioning and valve protection rules.

Use any hot work permit required by the facility or project to document controls. For welding, Rule 761 requires removal or fire-resistant cover for combustibles and flammables within 35 feet and protection of openings through which sparks can travel within that distance. It also calls for an immediately available 2A-10BC or greater extinguisher and a designated fire-safety person when the rule's conditions apply. If there is a possibility of smoldering fire, that person remains at least 30 minutes after welding. Evaluate further hazards or stricter permit conditions before work. A permit or fire watch cannot make welding safe in the presence of an explosive atmosphere.

For fired tar kettles, Part 24 Rules 2403, 2404 and 2406 require a qualified, experienced operator in attendance and close enough to respond immediately, a working temperature gauge and dry-powder extinguishers totaling at least 40 pounds, 10–25 feet from the kettle, with each unit at least 10 pounds. Verify placement and separation before firing. The rule calls for 20 feet from combustibles unless separated by a fire-resistant blanket and 10 feet from a structure that extends above the kettle, excluding piping.

Match the extinguisher class to the potential fire. Class A covers ordinary combustibles such as wood and paper, Class B flammable liquids, Class C energized electrical equipment, Class D combustible metals and Class K cooking oils and fats. A multipurpose rating can cover several classes. Check the operation-specific minimum.

Spill response

Train workers to recognize spills they may handle under the site procedure and protect drains or soil when they can do so safely. For an uncontrolled or unknown release, isolate the area and get the designated responders. Use emergency services for imminent danger and follow the applicable release-notification criteria, including EGLE's Pollution Emergency Alerting System when required. Characterize the collected material and contaminated absorbent before selecting the disposal route.

Test Your Knowledge

A Michigan construction crew will store three portable, upright-design 100-pound propane cylinders overnight. Which practice complies with Part 18 storage rules?

A

Store them in the basement, where temperature is stable, with the valves open to prevent pressure buildup

B

Lay them horizontally under a tarp to keep them out of the weather

C

Store them upright and secured outdoors, protected from tampering and away from ignition, with the valves closed

D

Store them inside the attached garage beside the water heater, provided a fire extinguisher is nearby

Test Your Knowledge

Under Michigan Part 18 Rule 1863, what is the maximum volume of flammable liquid that may be stored in a room outside an approved cabinet?

A

25 gallons

B

60 gallons

C

5 gallons

D

120 gallons

Test Your Knowledge

A worker grinds a concrete slab edge indoors with a handheld grinder for five hours, with no other Table 1 tasks that shift. Which method meets the applicable silica Table 1 requirements?

A

Use integrated water delivery alone because the Table 1 grinder row permits it in every setting

B

Use the commercial shroud with a collector rated below the minimum airflow and add APF 10 respiratory protection

C

Use the Table 1 shroud and collection system without respiratory protection, relying on the indoor exhaust

D

Use a commercially available shroud and dust collector meeting the Table 1 flow, filtration and cleaning provisions, use exhaust as needed and wear respiratory protection with APF 10 or higher