36.2 Sole Plates, Top Plates & Rim Joists

Key Takeaways

  • MRC R602.3.2 requires a double top plate lapped at corners and at intersections with bearing partitions, with end joints in the plates offset at least 24 inches; joints in top plates need not occur over studs.

  • For a single top plate in SDC A–C, Table R602.3.2 uses six 8d box nails each side at corners and intersecting walls and twelve each side at straight butt joints. Match the splice hardware to the applicable row or equivalent, and center rafters or joists over studs within 1 inch.

  • R602.3.4 requires full bearing on a nominal 2-by or larger plate at least as wide as the stud. For plates covered by R403.1.6, the ordinary bolt path uses a minimum 1/2-inch diameter, maximum 6-foot spacing and minimum 7-inch embedment, with approved equivalent anchorage also permitted.

  • Rim joists, also called band joists, provide the required lateral restraint at joist ends under R502.7 and are toe-nailed to the sill or top plate with 8d box nails at 4 inches on center, or 8d common or 10d box nails at 6 inches on center, per Table R602.3(1).

  • Both R502.3.3 cantilever tables require a full-depth rim at the unsupported end and solid blocking at the support. The support blocking may be omitted at a cantilever of 24 inches or less in Seismic Design Categories A, B or C.

Last updated: November 2026

The Plate Stack and the Load Path

Four different horizontal members get called a plate on a residential job, and mixing them up is the fastest way to lose easy exam points.

  • The sill plate (mud sill) is bolted flat to the top of the foundation wall. It provides a wood bearing and connection surface where that foundation detail is used.
  • The sole plate, also called the bottom plate, is the bottom member of a stud wall. On a first floor over a foundation it may sit on the sill plate; on an upper floor it sits on the subfloor.
  • The top plate caps the studs. In conventional light framing it is doubled: one plate tied into the studs, a second plate lapped across it to splice the wall line.
  • The rim joist, also called the band joist, is the full-depth member that closes the end of a floor frame and caps the ends of the floor joists.

The load path is the reason each one exists. Roof and floor loads travel down studs into the sole plate, across the floor system into joists and the rim, and down the foundation. Lateral loads also pass through connections along the load path: sheathing to studs, studs to plates, plates to floor and rim, rim to foundation anchorage. A plate that is undersized, unanchored, or spliced in the wrong place breaks that chain.

Bottom (Sole) Plates — R602.3.4

R602.3.4 requires studs to have full bearing on a nominal 2-by or larger plate or sill, with a plate width not less than the width of the studs. Two failures follow from that sentence, and both show up in the field:

  1. A 2x4 plate installed under 2x6 studs leaves part of the stud unsupported and is a framing correction, not a judgment call.
  2. A plate that is twisted, bowed or shimmed so the studs bear on one corner fails the full-bearing requirement even though the plate is the right size.

Anchorage to slabs and floors

MRC R403.1.6 anchors wood sill plates and also wood sole plates at exterior walls on monolithic slabs, plus the sole plates of interior braced wall panels on monolithic slabs. The verified numbers, which Chapter 29 covers from the foundation side, are:

Anchor bolt requirementValue (R403.1.6)
Bolt diameterMinimum 1/2 inch
Maximum spacing6 feet on center
EmbedmentMinimum 7 inches into concrete or grouted cells of concrete masonry
Position across plate widthMiddle third of the plate width
Bolts per plate sectionGenerally at least two, with one bolt not more than 12 inches and not less than seven bolt diameters from each end
HardwareA nut and washer tightened on each bolt

Approved equivalent anchorage and the specific short offset-braced-wall exception are available under R403.1.6. Seven bolt diameters for a 1/2-inch bolt is 3-1/2 inches. R403.1.6 requires a nut and washer. R403.1.6.1 covers specialized seismic braced-line washers. Because Michigan excludes model R602.11 from direct adoption, check the approved hardware where a seismic detail applies.

Decay, termites and fasteners

R403.1.6 sends sill and sole plate protection to R317 and R318. For sills and sleepers on a slab in direct contact with ground, R317.1 allows an impervious moisture barrier as an alternative to naturally durable or preservative-treated wood. Field-treat eligible cuts, notches or holes in pressure-treated members under R317.1.1. R317.3.1 allows hot-dipped galvanized steel, stainless steel, silicon bronze or copper for fasteners in preservative-treated wood, subject to its exceptions, including steel bolts at least 1/2 inch in diameter. Follow connector coating instructions or the stated G185 default or equivalent.

Check the sill seal and air barrier at the plate-to-foundation transition. A gasket used there must serve the specified sealing or moisture function. Decay protection follows the separate exposure and barrier rules.

Bottom plate to floor fastening

Table R602.3(1) governs the connection to the floor below. Away from braced wall panels, the bottom plate is face-nailed to joists, rim joist, band joist or blocking with 16d common nails at 16 inches on center, or 16d box or 3-inch by 0.131-inch nails at 12 inches on center. At a braced wall panel the connection intensifies to three 16d box nails at each 16-inch spacing, or two 16d common nails, or four 3-inch by 0.131-inch nails, because that is where lateral load enters the floor diaphragm.

Double Top Plates — R602.3.2

R602.3.2 is short, specific, and heavily tested. Wood stud walls must be capped with a double top plate installed to provide overlapping at corners and intersections with bearing partitions. End joints in top plates must be offset not less than 24 inches. Joints in plates need not occur over studs. Plates must be at least 2 inches nominal thickness and at least as wide as the studs.

That collection of rules produces the standard detail: the first plate is nailed down through the studs, the second plate is nailed over it, and the second plate runs past the corner so it ties the two wall lines together. The 24-inch offset ensures that a splice in the upper plate does not sit on top of a splice in the lower plate, which would create a hinge in the wall line.

Upper plate   ================|================
Lower plate   ========|========================
                      <------->
                      24 in. minimum between joints

Fastening the plate assembly

Table R602.3(1) supplies the numbers inspectors check:

ConnectionFastener schedule (Table R602.3(1))
Top or bottom plate to studItem 16 has separate rows. For example, four 8d box toe nails or two 16d common end nails.
Top plate to top plate16d common at 16 inches on center, face nailed (or 10d box or 3-inch by 0.131-inch nails at 12 inches on center)
Double top plate spliceFor the item 13 row that includes SDC A, each side of the end joint takes eight 16d common nails or twelve 16d box, 10d box or 3-inch by 0.131-inch nails. Face nail with at least 24 inches of lap each side. Check the separate row for wide seismic braced lines.
Top plate laps at corners and intersections3-10d box, or 2-16d common, or 3-3-inch by 0.131-inch nails, face nailed

Bearing studs under widely spaced members — R602.3.3

A plate is only as good as what sits under it. Where joists, trusses or rafters are spaced more than 16 inches on center and the bearing studs below are 24 inches on center, R602.3.3 requires those members to bear within 5 inches of the studs beneath. The exceptions are a double top plate of two 2x6 or two 3x4 members, a third top plate, or solid blocking equal in size to the studs installed to reinforce the double plate. This is the classic second-floor plan where 24-inch stud spacing meets 19.2-inch or 24-inch joist spacing, and it is a favorite inspection correction.

Single Top Plate Alternative — Table R602.3.2

The code permits a single top plate instead of the double plate, using the applicable splice detail or equivalent. The exception has three conditions: the single plate is tied at corners, intersecting walls and in-line splices per Table R602.3.2; rafters or joists are centered over the studs with a tolerance of not more than 1 inch; and omission of the top plate over headers is permitted only where the headers are adequately tied to adjacent wall sections per the same table.

For structures in Seismic Design Categories A through C, and D0 through D2 with braced wall line spacing under 25 feet, the plate and nail schedule distinguishes the location of the joint:

ConditionSplice plateNails each side of joint
Corners and intersecting walls3 inch x 6 inch x 0.036 inch galvanized steel plate or equivalent6-8d box (2-1/2 inch x 0.113 inch)
Butt joints in straight walls (in-line splices)Galvanized steel splice plate sized per the butt-joint row, or equivalent12-8d box (2-1/2 inch x 0.113 inch)

For D0–D2 with braced lines at least 25 feet apart, the table uses the heavier detail with nine 8d box nails per side at corners and intersections and eighteen per side at butt joints. For the lower seismic case shown above, APA’s advanced framing guide M400 Figure 6 illustrates a 3-inch by 12-inch by 0.036-inch straight splice plate. Use the applicable adopted table or approved equivalent to select the plate for the job.

The single plate is not a cheaper way to skip hardware. It trades lumber for steel, and the 1-inch centering tolerance is unforgiving: joists set 2 inches off the studs leave the plate carrying load it was never detailed for.

Rim and Band Joists

The rim joist closes the floor frame, caps the ends of the floor joists, and carries the edge of the subfloor and the wall above. It has three code jobs that exam questions test separately.

Lateral restraint. R502.7 requires joists to be supported laterally at the ends by full-depth solid blocking not less than 2 inches nominal, or by attachment to a full-depth header, band or rim joist, or to an adjoining stud, or by other lateral support that prevents rotation. Engineered joist and truss restraint follows manufacturer requirements. In SDC D0–D2, provide lateral restraint at intermediate supports as well. For a hanger detail without a rim, verify how the connection or adjacent framing prevents rotation.

A defined connection. Table R602.3(1) item 22 covers the rim joist, band joist or blocking to the sill plate or top plate at 8d box nails at 4 inches on center, toe nailed, or 8d common, 10d box, or 3-inch by 0.131-inch nails at 6 inches on center. Item 26 covers the band or rim joist to each joist: end fastening with three 16d common nails, four 10d box nails, four 3-inch by 0.131-inch nails, or the listed staples. Engineered rim board is its own product category under R502.1.7, conforming to ANSI/APA PRR 410 or evaluated to ASTM D7672 and marked accordingly; a piece of OSB ripped to depth is not an engineered rim board.

Cantilever termination. The notes to Tables R502.3.3(1) and R502.3.3(2) require a full-depth rim joist at the unsupported end of cantilevered joists and solid blocking at the supported end, with the blocking waived only for cantilevers of 24 inches or less in Seismic Design Categories A, B or C. A cantilever without a full-depth rim at its tip has nothing tying the joist ends together.

Blocking and the rim

R502.2.2 specifies utility grade or better for lumber blocking used to fasten panel edges or fixtures. If full-depth sawn blocking is the method chosen for joist end restraint, R502.7 requires at least nominal 2-inch thickness. R502.4 requires full-depth, nominal 2-inch or thicker blocks at no more than 4 feet on center between double joists separated for pipes or vents under bearing partitions. Check braced wall force transfer separately under R502.2.1 and R602.10.8. The rim assembly at the thermal envelope also needs the applicable air-sealing and insulation details.

Inspection Points on the Plate Assembly

  • Top plate splice locations. End joints offset at least 24 inches, laps at corners and at bearing partition intersections, no splice stacked directly over another.
  • Single top plate hardware. Correct plate size, correct nail count per side, the right connection at each corner, intersection and straight-wall splice, joists centered within 1 inch of the studs.
  • Anchor bolt placement. In the middle third of the plate width, the applicable number of bolts per plate section, one within 12 inches and no closer than seven bolt diameters to each end.
  • Treated plates and gaskets. Verify R317/R318 exposure protection, the specified sill seal, and compatible fasteners and connectors.
  • Rim joist nailing. 4-inch or 6-inch toe-nail pattern to the plate, item 26 end fastening, full-depth rim at tabulated cantilever tips, the applicable support blocking and verified joist end restraint.
  • Plate penetrations. For plumbing and duct cuts removing more than half an exterior or interior bearing top plate width, check R602.6.1’s tie or full-side sheathing exception.

Exam Traps

TrapCorrect rule
Thinking top plate joints must land on a studJoints need not occur over studs; they must be offset 24 inches (R602.3.2)
Using 12 inches as the top plate offsetThe offset is 24 inches minimum
Treating a single top plate as hardware-freeApply the Table R602.3.2 splice detail or equivalent, plus 1-inch joist or rafter centering
Confusing sole plate with sill plateSill plate sits on the foundation; sole plate is the bottom plate of the wall
Quoting 15-inch anchor bolt embedmentA 1/2-inch bolt needs 7 inches into concrete or grouted masonry cells
Assuming every sill bolt needs a 3 × 3 plate washerApply R403.1.6 and the approved hardware detail. Check specialized braced-line anchorage under R403.1.6.1 and the Michigan exclusions.
Ignoring the 5-inch bearing stud ruleJoists over 16 inches on center above studs at 24 inches on center must bear within 5 inches of the studs, unless plated or blocked per R602.3.3
Installing a 2x4 plate under 2x6 studsPlate width must be at least the stud width (R602.3.4)
Leaving a cantilever tip openFull-depth rim at the unsupported end under either cantilever table. Check the 24-inch and SDC A–C support-blocking exception.
Standard nails in treated platesUse eligible fastener materials and connector coatings under R317.3.1, applying the listed exceptions
Test Your Knowledge

Under MRC R602.3.2, what is the minimum offset required between end joints in a double top plate?

A

12 inches

B

16 inches

C

24 inches

D

48 inches

Test Your Knowledge

In a Seismic Design Category A house using a single top plate, the galvanized splice plate for a straight-wall butt joint has been selected under Table R602.3.2. Which nail count and centering tolerance apply?

A

Six 8d box nails per side, with a 1-inch centering tolerance

B

Twelve 8d box nails per side, with a 1-inch centering tolerance

C

Six 16d common nails per side, with a 2-inch centering tolerance

D

Twelve 8d box nails total, with no centering tolerance

Test Your Knowledge

Which listed toe-nail option matches Table R602.3(1) item 22 for fastening a rim joist to the sill plate?

A

8d box nails at 4 inches on center, toe nailed, or 8d common or 10d box nails at 6 inches on center

B

16d common nails at 16 inches on center, face nailed

C

Three 16d common nails per joist, end nailed

D

4-8d box nails per stud, toe nailed