44.3 Stone Masonry
Key Takeaways
Granite is igneous, limestone is sedimentary and marble is metamorphic. R606.2.4 identifies product standards for these and other natural dimension stones. Use material tests and the approved design for the actual exposure.
ASTM C1670/C1670M covers adhered manufactured stone units, while C1780 addresses installation of the products in its scope. R703.12 identifies the applicable 2015 MRC installation paths.
Over wood-based sheathing check the R703.7.3 two-layer barrier or its qualified drainage exception. Integrate the WRB and screed and verify the specified lath, fasteners and bond.
R703.12.1 sets exterior stud-wall clearances at 4 inches above earth and 2 inches above ordinary paving, or 1/2 inch at an exterior walking surface supported by the same foundation.
Use the R703.8 support path for anchored stone. The R703.8.2 framing-supported exterior route uses at most 40 psf installed and L/600 and excludes D0, D1 and D2.
Natural Dimension Stone
Natural dimension stone is quarried and then cut or split to size. Its geologic family helps explain the material, but select the actual source and finish using project requirements and test data.
| Geology and example | Specification identified in 2015 MRC R606.2.4 | What to check |
|---|---|---|
| Igneous granite, crystallized from melt | ASTM C615 | Absorption, strength, finish and suitability for the exposure |
| Sedimentary limestone | ASTM C568 | Specified density class, durability, exposure and water shedding |
| Sandstone, a sedimentary example of quartz-based stone | ASTM C616 | Properties of the selected stone. The specification covers several quartz-based stone classes |
| Metamorphic marble | ASTM C503 for exterior marble | Exterior suitability and sensitivity to acids |
| Metamorphic slate | ASTM C629 for dimension slate | Intended use, direction of cleavage, finish and relevant flexural properties |
ASTM C97 measures absorption and bulk specific gravity of dimension stone. C170 measures compressive strength, C99 modulus of rupture and C880 flexural strength. Select tests appropriate to the stone and design. For example, a thin panel supported at discrete points needs a bending and attachment check. A compressive-strength number alone cannot validate it. Check the stone and finish for exterior use, and detail the support, flashing and drainage to limit saturation in freeze-thaw exposure.
Manufactured Stone Veneer
Adhered manufactured stone masonry veneer is made from cementitious material, aggregates and commonly pigments. A wet-cast product can get its texture from a mold that replicates stone. ASTM C1670/C1670M specifies the manufactured units. ASTM C1780 is an installation practice for covered cement-based adhered veneer products, including the manufactured veneer units covered by C1670. Use the editions and options that apply to the approved project. The 2015 MRC sets the installation routes in R703.12 using its own provisions, TMS 402/602 and the applicable manufacturer instructions.
| Decision | Natural stone | Adhered manufactured stone |
|---|---|---|
| Unit selection | Identify the stone, quarry and product specification. Check finished size, tolerances and performance | Verify the product's evaluation documentation and unit specification |
| Attachment | An approved thin-stone system can be adhered. A ledge-supported system can be anchored | Use the bond, lath when required, and backing specified for the assembly |
| Weight | Use actual unit thickness, density or supplied weight data | Check installed weight with the layers and materials defined by the design and applicable provision |
| Weather | Detail for the selected stone and exposure | Use an approved exterior product and detail its backing, drainage and clearances |
Support follows the approved system, rather than a choice based on the face material alone. Allow for the units and their mortar in the load path. Anchored veneer transfers gravity loads to a support and lateral loads to the backing. Adhered veneer transfers loads into the prepared backing through its bond and attachment.
Anchored and Adhered Stone
Follow the R703.8 path for anchored stone veneer, including the support, attachment, flashing and drainage details in the approved system. Use Rule 545's figures in Michigan. When using the framed exterior gravity support route in R703.8.2, the installation is limited to 40 psf and the supporting construction is designed for the imposed loads with supporting-member deflection limited to L/600. This route excludes D0, D1 and D2. The foundation-supported table allowances are separate.
On approved concrete or concrete masonry, some manufactured stone can be adhered directly to a clean, adequately textured surface free of release oil, coatings and contaminants. An ICRI concrete surface profile of 2 or higher is commonly adequate for that CMHA detail. If the substrate cannot develop the required bond, use an approved lath and scratch-coat assembly. The CMHA direct-bond method is for concrete or concrete masonry and excludes clay masonry. Over wood or steel framing, follow the evaluated backing, WRB, lath and fastener details.
Installation and Inspection Sequence
- Substrate. Check that the frame and backing can carry the veneer system. For a typical wood structural panel detail, the panel manufacturer or APA guidance provides for about 1/8 inch across panel joints. Follow the instructions for that sheathing and keep the assembly dry enough for installation.
- Water-resistive barrier. R703.12 and R703.7.3 call for the specified barrier over wood-based sheathing, generally two separately installed continuous layers with performance at least equivalent to two layers of Grade D paper. The section allows the stated single-barrier exception with at least 60-minute Grade D water resistance and an intervening substantially nonabsorbing layer or a designed drainage space. In a conventional two-layer detail, the inner layer is integrated with flashing and the outer layer separates the scratch coat. For the applicable lapped-sheet detail, follow the R703.2 2-inch horizontal lap and 6-inch felt joint lap, plus the product and corner details. Use an independently approved drainage alternative only when its conditions are satisfied.
- Flashing and screed. Coordinate openings, penetrations and transitions with R703.4. For a stud wall under R703.12.2, install the corrosion-resistant base screed or flashing with a vertical attachment flange at least 3-1/2 inches tall and its outlet at least 1 inch below the foundation plate line. Lap the WRB over the attachment flange and preserve the outlet.
- Lath and scratch coat. Pick the approved corrosion-resistant lath by backing and span. Self-furring ASTM C847 diamond metal lath is one option. Follow the specified laps, fasteners and framing penetrations. In the CMHA metal-lath example, the fasteners go into framing at no more than 7 inches on center, with at least 3/4 inch of nail penetration into wood. Apply and score a nominal 1/2-inch scratch coat that surrounds the lath. CMHA's example includes ASTM C270 Type N or S site-mixed mortar. If the selected detail calls for curing over open studs, non-solid sheathing or metal panels, CMHA describes 48 hours before dampening and applying the setting bed.
- Set and finish. Prepare the bonding surfaces per the specified mortar and unit instructions. Apply full setting-bed coverage. If a unit moves after the mortar starts to set, remove it, clean the bonding surfaces and set it again. Where joints are filled, allow the units to set, then tool the pointing mortar at thumbprint hardness. A dry soft brush removes loose residue without spreading fresh mortar.
For exterior stud walls under R703.12.1, the minimum clearance is 4 inches above earth and 2 inches above ordinary paving. It is 1/2 inch at an exterior walking surface that shares the wall's foundation. When veneer continues down a masonry foundation with WRB and lath, CMHA recommends the same stud-wall clearances. Its separate concrete or masonry wall detail uses 2 inches above grade and 1/2 inch above paving. Confirm the approved detail for the actual substrate and installation. Keep the bottom clear of snowmelt and soil, direct drainage away from the veneer and avoid damaging deicing chemicals. Inspect the flashing and lath before they are covered.
Which ASTM standard specifies adhered manufactured stone masonry veneer units?
ASTM C216
ASTM C1670
ASTM C902
ASTM C1261
Under 2015 MRC R703.12.1, what clearances apply to adhered masonry veneer on an exterior stud wall above earth and ordinary paving, away from a walking surface supported by the same foundation?
1 inch above earth and 1/2 inch above paving
2 inches above earth and 1 inch above paving
6 inches above earth and 4 inches above paving
4 inches above earth and 2 inches above paving
Granite, limestone and marble are classified differently because of how they formed. Which pairing is correct?
Granite is metamorphic and marble is sedimentary
Granite is igneous and marble is metamorphic
Limestone is igneous and granite is sedimentary
Marble is igneous and limestone is metamorphic