40.2 Exterior Deck Construction
Key Takeaways
Trace the loads from the deck through its supports to adequate footings. A deck supported by the dwelling also needs a positive connection to the primary structure for vertical and lateral loads.
Michigan generally requires deck footings 42 inches below actual grade under R 408.30522, subject to approved modification. A freestanding deck’s R403.1.4.1 frost exception is separate from the state minimum-depth rule.
A prescriptive deck ledger is at least nominal 2x8 in a species and grade permitted by R507.2.1, supports no concentrated beam load and does not bear on veneer. Use the approved flashing and ledger placement details under Michigan R 408.30523 and R 408.30523a.
Ledger fastener spacing comes from Table R507.2: for example, 1/2 inch lag screws at 30 inches on center where the joist span is 6 feet or less behind 1/2 inch maximum sheathing, and 36 inches on center for 1/2 inch through-bolts in the same condition.
R507.5 limits deck joist overhang to one-quarter of the actual adjacent span. Use Table R507.5’s cantilever column for a projection beyond the short-overhang allowance in note f, then check the connection and loading conditions.
Quick Answer: Trace deck loads to the soil and verify how the deck resists lateral movement. Use the applicable 2015 MRC span, ledger and footing provisions, including Michigan’s amendments. A ledger attachment also needs a verified lateral load path into the structure.
R507 covers wood-framed decks and directs nonprescribed materials and conditions to R301. Gravity loads travel through decking, joists, beams, posts and footings. At an attached deck part of the vertical load usually travels through the ledger into the building. Follow the approved structural and lateral details for the actual assembly.
The parts of a deck
| Component | What it does | Key rule |
|---|---|---|
| Footing | Spreads post load into soil | Under the Michigan rule, generally 42 inches below actual grade. Check applicable frost protection and approved modifications. |
| Post | Carries beam load to footing | For the single-level Table R507.8 path, 4x4 and 4x6 up to 8 feet and 6x6 up to 14 feet, measured to the underside of the beam |
| Beam (girder) | Collects joists and delivers load to posts | Span from Table R507.6, based on species, size and joist span |
| Joist | Carries decking to beam or ledger | Span from Table R507.5; cantilever limited |
| Ledger | Ties the deck to the house band joist | Minimum nominal 2x8 in qualifying material. No bearing on veneer and no concentrated beam loads. |
| Band joist | House-side support for the ledger | Prescriptive band requirements at R507.2.2, including full bearing on the main structure |
| Decking | Walking surface | Maximum joist spacing from Table R507.4 |
| Guard | Fall protection at the edge | On a level deck, check a drop greater than 30 inches within 36 inches of the edge, 36-inch guard height and 4-inch sphere |
| Stair stringer | Carries deck stairs | Stair geometry per R311.7, including the Michigan 8-1/4 inch riser |
Footings in Michigan
Michigan R 408.30522 generally requires exterior footings and foundation systems to extend 42 inches below actual grade. The official may modify depth based on the conditions in that rule. R507.8.1 refers to R403 for deck footings. Its 12 inches is a post embedment option for lateral restraint, not a general footing-depth dimension. Footings may bear on frozen soil only where it is permanently frozen.
Under R403.1.4.1, a deck not supported by a dwelling is exempt from the requirement that its footing extend below the frost line. Check the separate state minimum-depth rule and its approval process before choosing a shallow foundation. Confirm suitable bearing under R403.1.
Posts, beams and joists
Table R507.8 gives the post heights above for single-level wood decks using beams sized under Table R507.6. Under R507.8.1, restrain the bottom of each post using a manufactured connector installed per its instructions or the allowed 12-inch embedment in soil or a concrete pier. At the beam, Figure R507.7.1 illustrates connections that resist lateral displacement. Other equivalent means are permitted. Use washers under bolt heads and nuts. A beam bearing directly on a footing has a separate allowance.
At the ends of beams and joists, R507.7 generally requires at least 1½ inches of bearing on wood or metal, or 3 inches on concrete or masonry, across the full member width. Joists framing into the side of a ledger or beam need approved hangers. Joists bearing on a beam need a connection to resist lateral displacement. Provide rotational restraint at joist ends and bearing under R507.5.1 with the applicable hanger, blocking or rim detail.
Select the main span from Table R507.5 by species, size, spacing and whether there is a cantilever. A No. 2 southern pine 2x8 at 16 inches on center has an 11 ft 10 in. main-span entry without a cantilever and 10 ft 1 in. in the cantilever column under the table assumptions. Under R507.5 the overhang may be no longer than one-quarter of the actual adjacent span. Table note f allows an overhang up to nominal joist depth when using the no-cantilever span values. For a longer overhang, use the cantilever column and check the one-quarter limit and the rest of the detail.
For example, with a 10-ft actual adjacent span for that 2x8, one-quarter is 30 inches. A 20-inch overhang exceeds the short-overhang allowance but fits both the 10-ft-1-inch main-span entry and the 30-inch maximum. A 32-inch overhang exceeds the one-quarter rule. Check the uplift connection required by R507.1 for cantilevered framing. Beam overhangs follow the separate R507.6 beam rule.
In Table R507.4, nominal 2-inch wood decking permits 24-inch joist spacing perpendicular to the joists or 16 inches diagonally. Nominal 1¼-inch wood decking permits 16 and 12 inches respectively. The diagonal entries apply at up to 45 degrees from perpendicular. Use at least two 8d threaded nails or two No. 8 wood screws at each support for wood decking. Follow R507.3 and the product's approved instructions for composite decking.
The ledger is where decks come off the house
R507.2.1 requires a deck ledger to be at least a 2x8 nominal pressure-preservative-treated southern pine, incised pressure-treated hem-fir, or approved naturally durable No. 2 grade or better lumber. The ledger cannot carry concentrated beam or girder loads or be supported on stone or masonry veneer. Under R507.2.2, the supporting band joist must be at least 2-inch nominal solid-sawn spruce-pine-fir or 1-inch by 9-1/2-inch Douglas fir laminated veneer lumber. The band joist must be fully supported by a wall or sill plate below.
Under the Table R507.2 assumptions of 40 psf deck live load, 10 psf dead load and snow load up to 40 psf, select spacing by connection type, sheathing and span. The table treats snow and live load as separate loading cases. Use these two rows with no more than ½ inch of wood structural panel or solid-sawn lumber sheathing. The separate bolt row for sheathing up to 1 inch has its own conditions.
| Connection | 6 ft or less | 6 ft 1 in to 8 ft | 8 ft 1 in to 10 ft | 10 ft 1 in to 12 ft |
|---|---|---|---|---|
| 1/2 inch lag screw, 1/2 inch maximum sheathing | 30 inches o.c. | 23 inches o.c. | 18 inches o.c. | 15 inches o.c. |
| 1/2 inch bolt, 1/2 inch maximum sheathing | 36 inches o.c. | 36 inches o.c. | 34 inches o.c. | 29 inches o.c. |
The lag screw tip must extend beyond the inner face of the band joist. Stagger rows along the ledger. Use Table R507.2.1 and Michigan’s amended Figure R507.2.1(1) to check end distances, edge distances and spacing between rows. The ends generally use 2 inches minimum and 5 inches maximum. Check the ledger-depth-dependent bottom-row placement separately and follow the manufacturer for engineered rim joists. Table connections use hot-dipped galvanized or stainless steel fasteners. Use an approved design for connections outside the table’s conditions.
R 408.30523a requires approved corrosion-resistant flashing above the ledger. Use the state-corrected Figure R507.2.1(2) or an approved alternate, and integrate the flashing with the water-resistive barrier to protect the band joist.
Lateral load is a separate connection
For a dwelling-supported deck, R507.1 requires anchorage into the primary structure for vertical and lateral loads. Michigan excluded the model lateral-load Figures R507.2.3(1) and (2), and the Michigan text of R507.2.4 addresses flashing. Use the approved connection design to carry lateral loads. Toenails or nails relying on withdrawal are prohibited for the required anchorage. Where attachment to the primary structure cannot be verified, the deck must be self-supporting.
Guards, Stairs and Materials
A level deck needs a guard at open sides where the drop is greater than 30 inches at any point within 36 inches horizontally of the edge. The guard must be at least 36 inches high and reject a 4-inch sphere in the required guard area. Check attachments and load transfer under Table R301.5. Deck stairs have the applicable R311.7 geometry and rail requirements, with separate stair-side guard openings and heights. Check R311.5.1 attachment, exterior landings and R303.8 lighting. Verify the stringer span, remaining depth, fastening and bearings against the design.
Select wood for the exposure under R317.1. Where pressure-treated wood is required, check its treatment label for the end use, including ground contact where applicable. Follow the applicable AWPA M4 field treatment instructions for cuts, notches and holes in pressure-treated members. Under R317.3.1, usual fastener materials for treated wood include hot-dipped zinc-coated galvanized steel, stainless steel, silicon bronze and copper, subject to the applicable exceptions and more specific connection requirements. For connectors use the manufacturer’s compatible coating and fasteners. When there is no manufacturer recommendation for the coating on a connector in contact with treated wood, the code specifies at least ASTM A653 G185 or equivalent. Follow the composite decking installation instructions for joist spacing, fasteners and end gaps.
Worked layout: a 16 by 12 foot attached deck
Assume a single-level deck 16 feet wide and 12 feet deep with a ledger, no joist overhang, and a flush beam at the 12-foot line. The beam has two 8-ft simple spans spliced above the center post. Use the table conditions for No. 2 lumber in wet service and assume a uniform governing 40 psf live load plus 10 psf dead load. Snow and other loads are checked separately and assumed noncontrolling here.
- Joists: No. 2 spruce-pine-fir 2x10 at 16 inches on center spans 12 ft. The applicable Table R507.5 entry is 13 ft 7 in.
- Beam: At a 12-ft joist span, Table R507.6 gives 9 ft 2 in. for three No. 2 southern pine 2x10 plies. The actual 8-ft spans fit. Assemble the plies to the specified fastening schedule and locate the splice at the post.
- Posts and footings: Table R507.8 gives an 8-ft height limit to the beam underside for 4x4 posts in this layout. Each end post receives 4 ft of beam tributary length times 6 ft of tributary deck width, or 24 ft². The center receives twice that at 48 ft². At 50 psf the gravity reactions are 1,200 lb at each end and 2,400 lb at the center, before footing weight. The approved footing detail must account for bearing, load and frost requirements.
The span table and reaction calculations cover the stated framing assumptions. Check the approved ledger, lateral bracing, posts, connectors and footings as independent parts of the load path.
Inspection traps
- Ledger bolted through siding or veneer instead of to the band joist, or bearing on masonry veneer.
- Missing flashing, flashing lapped against drainage, or a sealant-only detail where approved corrosion-resistant flashing is required.
- Positive vertical or lateral attachment missing or unverifiable.
- A cantilever beyond one-quarter of the actual adjacent span or a longer overhang paired with values permitted only for the short-overhang or no-overhang condition.
- A guard post detail without a verified load path through the rim and supporting framing.
- Joist hangers with fasteners outside the connector manufacturer’s approved schedule.
- Footings on topsoil or unapproved fill, or installed without verifying the applicable bearing depth and frost provisions.
- Deck boards fastened with smooth common nails, which back out under seasonal movement.
- Stair stringers notched so deeply that the remaining section cannot carry the load, or a bottom riser laid out without the finished landing elevation.
What general minimum depth does Michigan require for the footings of this dwelling-supported deck if the building official has approved no depth modification?
12 inches below grade, the same as any other footing
24 inches below grade, or to the local frost line if shallower
36 inches below grade unless the deck is under 200 square feet
42 inches below actual grade
Assume the conditions of 2015 MRC Table R507.2. A deck ledger uses 1/2-inch lag screws through no more than 1/2 inch of wood structural panel sheathing, and joists span 6 feet. What maximum fastener spacing applies?
30 inches on center
16 inches on center
24 inches on center
36 inches on center
A No. 2 southern pine 2x8 deck joist at 16 inches on center has a 10-ft actual adjacent span. Assume the 2015 MRC table loading and service conditions. How does a proposed 20-inch overhang compare with the R507.5 span and overhang limits?
It is approved by the span table without checking any connection or load path.
It exceeds the short-overhang allowance, but the 10-ft-1-in. cantilever-case main-span entry and the 30-inch overhang limit both accommodate the stated geometry.
It fails because every deck joist overhang is capped at 8 inches for that joist size.
It fails because the one-quarter rule limits any 10-ft adjacent span to 20 inches or less.