52.4 Preventing Water & Air Intrusion

Key Takeaways

  • Trace water from the cladding to the flashing or WRB and out through an unobstructed outlet. Connect the frame to the continuous air barrier with a compatible seal.

  • Michigan Table N1102.4.1.1 calls for sealing the gaps between window or door jambs and framing and between skylights and framing.

  • Under Michigan’s prescriptive N1102.4.1.2 test, envelope leakage may be at most 4 air changes per hour at 50 Pa. Prepare the building and submit results as the rule directs.

  • Michigan enforces amended R601.3 for vapor retarders. The ordinary frame-wall requirement in Zones 5–8 and Marine 4 uses a Class I or II material on the interior side, subject to the listed exceptions.

  • Keep the sill-pan outlet, frame weeps and roof drainage paths clear. Use product-specific sealant and flashing details.

Last updated: November 2026

Water drainage and air sealing

Exterior drainage. The cladding sheds much of the rain. The WRB and flashings redirect water that gets behind it. For the ordinary wall assembly, R703.1.1 requires a WRB and drainage to the exterior. Under R703.4, exterior opening flashing drains to the exterior finish or to the WRB for subsequent drainage. Trace that route from the upper lap to a free outlet.

Continuous air barrier. Michigan Table N1102.4.1.1 calls for sealing the gaps between window or door jambs and framing and between skylights and framing. Connect the unit to the intended air-control layer. In the drained flanged-window example, the interior perimeter seal controls airflow while the exterior sill outlet remains open.

Air sealing that survives

  • Backer rod and compatible sealant can bridge a frame-to-framing gap. Follow the specified joint geometry and allow for dissimilar materials to move.
  • Low-expansion window-and-door foam can fill irregular gaps around shims. Follow the product’s depth and application requirements to avoid distorting the frame.
  • Sill transition: connect the air seal to the unit and wall assembly while maintaining the separate outdoor drainage path.
  • Air barrier continuity: seal the transitions and penetrations in the chosen air-control layer before covering it. In a design using taped structural sheathing as the air barrier, connect the frame seal to the sealed sheathing.

Vapor and condensation in a Michigan winter

Michigan enforces R601.3 as amended by Rule 522a. It generally calls for a Class I or II retarder on the interior side of frame walls in Zones 5 through 8 and Marine 4. Exceptions include Table R702.7.1 and materials that moisture or freezing will not damage. On the interior side of below-grade wall assemblies, Class III or no vapor retarder is allowed. Class I or II is permitted there when the assembly contains no air-permeable insulation.

The air seal limits airflow through the joint. The retarder controls vapor diffusion through the wall materials. Select a wall assembly with the required vapor control and capacity to dry.

Room-side condensation can form when the glass or frame surface falls below the indoor air’s dew point. Check indoor humidity and the temperature of the surface, including cold frame edges. Persistent fog between panes of a sealed IGU points to a glazing-unit seal problem. Confirm its location before opening the flashing.

Thermal bridging at the opening

An opening changes the insulation and heat paths. Michigan’s Table N1102.1.1 gives 0.32 for fenestration other than skylights and 0.55 for skylights on the prescriptive component path. The N1102.5 tradeoff limits are separate area-weighted maximums: 0.48 for vertical fenestration in Zone 5, 0.40 in Zones 6 and 7, and 0.75 for skylights in those zones. These caps still apply when using the relevant tradeoff path. The prescriptive exemptions cover up to 15 ft² of glazed fenestration per dwelling unit (N1102.3.3) and one side-hinged opaque door assembly up to 24 ft² (N1102.3.4). Include these components when using the U-factor or total-UA alternative. The exemptions apply to the prescriptive component path.

Test Your Knowledge

In the drained flanged-window example, which combination controls both rainwater and air leakage?

A

Two layers of housewrap under the cladding

B

Flashing plus a bead of caulk at the exterior

C

Caulking both perimeters with the sill drainage outlet closed

D

An exterior drainage path that sheds water and a sealed interior connection to the air barrier

Drainage details that actually drain

  • Keep frame weeps and other outlets clear where the unit is designed to drain.
  • For a sill pan, use the specified outlet, jamb turns and back dam or slope. For the compatible example, the sill flashing drains over the lower WRB, jamb flashing laps onto it, the head laps the jambs and the upper WRB laps the head.
  • At a wall with anchored masonry veneer, preserve the specified flashing and weeps above it. At other claddings, use the appropriate drainage detail between the covering and WRB.
  • At a skylight, check curb height where applicable, the matching flashing kit and its laps with the roofing and underlayment.

Diagnostics

A blower door measures whole-envelope leakage. Under Michigan’s amended N1102.4.1.2, the prescriptive limit is 4 air changes per hour at 50 Pa, after the envelope penetrations are in place. Close exterior windows, exterior doors and fireplace or stove doors using their intended seals. Close dampers without extra sealing. Close and seal the exterior doors for continuous ventilation systems and heat-recovery ventilators as the rule directs. Open interior doors and supply and return registers if installed, and turn off heating and cooling systems. Submit a signed report. A certified independent third party is required when the code official calls for one. Use inspection or diagnostic tools to locate individual leaks while the building is under test pressure.

For suspected roof or wall leakage, trace the path from above the opening and check moisture at the head and sill. A moisture meter helps locate wet material, and smoke tracing under a pressure difference can help locate air leaks. ASTM E1105 is a controlled field water-penetration test for installed windows, skylights, doors and curtain walls. ASTM E331, referenced in the R703.1.1 assembly exception, is a different test with specific code conditions. ASTM E2112 is an installation practice for the fenestration products within its scope.

Defect to symptom

ObservationCheck first
Damp drywall or peeling paint at the headHead flashing, the upper WRB lap and conditions above the opening
Moisture at a lower jamb cornerPan, end returns, jamb lap and sill outlet
Water retained in a drainage trackBlocked weeps or a misaligned unit
Water inside a thresholdSeal behind the intended outlet, threshold drainage or conditions above
Water staining at a skylightPitch, curb where applicable, upper flashing and roof membrane laps
Persistent fog inside a sealed glazing cavityIGU seals
Frost on the room side of the frameSurface temperature and indoor humidity
Draft around trimContinuity of the perimeter air seal
Latch binds or strike missesAlignment, support and evidence of frame movement

Installation quality checklist

  1. Confirm the WRB’s approved laps, repairs and condition before closing the wall.
  2. Compare the framed opening and the unit alignment to the manufacturer’s tolerances and check the specified shims, supports and fasteners.
  3. In the drained example, trace the sill outlet, jamb and head laps and upper WRB. For other systems use their details.
  4. Verify the continuous air seal and the separate exterior outlet. Operate and latch the unit before finish work.
  5. At the roof, check the skylight mount, flashing and underlayment. Preserve ice-barrier coverage where required.
  6. Record the prescriptive blower-door result and inspect or test remaining suspected leakage paths.
Test Your Knowledge

What air leakage limit does Michigan enforce for the prescriptive blower-door test?

A

3 air changes per hour at 50 pascals, the base 2015 IECC limit for these climate zones

B

4 air changes per hour at 50 pascals

C

5 air changes per hour at 50 pascals

D

7 air changes per hour at 50 pascals

Test Your Knowledge

Under Michigan’s amended R601.3, where does the ordinary frame-wall provision call for a Class I or II vapor retarder?

A

Only in climate zone 5

B

Nowhere; vapor retarders are optional in Michigan

C

On the interior side in Zones 5 through 8 and Marine 4, subject to listed exceptions

D

Only on below-grade walls