32.2 Reinforcement Methods & Installation
Key Takeaways
Steel can carry tension after concrete cracks. For common US sizes No. 3 through No. 8, the bar number gives the nominal diameter in eighths of an inch.
Grade 60 identifies a minimum yield strength of 60,000 psi. Match grade and bar specification to the plans and to the assumptions of the selected prescriptive table.
The prescriptive 2015 MRC footing and cast-in-place wall provisions use 3 inches of cover when cast against earth, 2 inches for No. 6 and larger and 1-1/2 inches for No. 5 and smaller in removable forms exposed to earth or weather, and 3/4 inch for unexposed removable or stay-in-place forms.
Table R608.5.4(1) gives Grade 60 tension laps of 30, 38 and 45 inches for No. 4, No. 5 and No. 6 respectively. Under the applicable noncontact rule, spacing between lapped bars is limited by the smaller of one-fifth the required lap and 6 inches.
Support welded wire reinforcement at the specified elevation. WWR and specified fiber systems can have structural uses when designed for them. Keep all required reinforcement in place unless a substitution is approved.
Concrete resists compression well but cracks at relatively low tensile stress. A wall loaded by backfill or a slab bridging a support bends, producing a tension zone. The design places steel where it can carry tensile force. Bond transfers force between steel and concrete, and the surrounding concrete provides protection.
Rebar grades and sizes
The 2015 MRC prescriptive cast-in-place foundation wall rules recognize ASTM A615, A706 or A996, with rail-steel A996 bars limited to Type R. A615/A615M-12, listed in Chapter 44, specifies Grades 40, 60, 75 and 80. The grade denotes minimum yield strength in thousands of psi. The foundation-wall provision sets a 40,000 psi minimum for Seismic Design Categories A through C, while individual wall tables can assume Grade 60. A change in grade, size or bar arrangement needs approval based on the applicable design, detailing and development requirements.
The ribs of a deformed bar bear against concrete and help develop bond. Prevent contamination by mud, oil, ice and other bond-reducing material. Use plain or smooth bars only where specified, such as a designed dowel that allows joint movement.
For these common US sizes, the bar number gives the equivalent nominal diameter in eighths of an inch. A No. 5 bar has a nominal diameter of 5/8 inch.
| Bar | Nominal diameter | Nominal area (in²) | Nominal weight (lb/ft) |
|---|---|---|---|
| No. 3 | 3/8 in | 0.11 | 0.376 |
| No. 4 | 1/2 in | 0.20 | 0.668 |
| No. 5 | 5/8 in | 0.31 | 1.043 |
| No. 6 | 3/4 in | 0.44 | 1.502 |
| No. 8 | 1 in | 0.79 | 2.670 |
Cover: the number inspectors check first
Measure clear cover from the outside of the reinforcement to the concrete face. Cover helps protect steel and is needed for the detailed assembly. The table summarizes the prescriptive cast-in-place provisions in R403.1.3.5.3, R404.1.3.3.7.4 and R608.5.4.1.
| Condition | Minimum clear cover |
|---|---|
| Cast against and permanently exposed to earth (footings) | 3 in |
| Removable forms, exposed to earth or weather, #6 and larger | 2 in |
| Removable forms, exposed to earth or weather, #5 and smaller | 1-1/2 in |
| Removable forms not exposed, and stay-in-place forms | 3/4 in |
R404.1.3.3.7.4 and R608.5.4.1 limit the minus tolerance to the smaller of one-third of the required cover and 3/8 inch. For a specified 3-inch cover under that wall rule, the tolerance limit is 3/8 inch. Set the steel at its required design location using supports. An engineered member or precast foundation uses the cover provisions for that system.
Chairs, spacers and placement rules
- Support the cage. Select approved chairs, spacers or concrete supports to maintain position under the construction loads. Set support spacing for the reinforcement stiffness and anticipated traffic.
- Secure it. Tie or otherwise secure bars against movement from discharge and vibration.
- Check wall location. R404.1.3.3.7.2 centers vertical reinforcement for Tables R404.1.2(2) through (7), while Table (8) uses a maximum cover of 1-1/4 inches from the inside face. Follow the selected detail.
- Protect the bond. Keep bars and the area around supports free of mud, oil, ice and debris.
Lap splices and development
A lap splice transfers force between overlapping bars through the surrounding concrete. Development length is the embedment needed to develop the bar force at a critical section. The required overlap and the required embedment are separate dimensions.
For the applicable MRC prescriptive concrete details, Table R608.5.4(1) lists these tension laps. Confirm the bar grade, loading and governing detail before using the table.
| Bar | Lap splice, Grade 40 | Lap splice, Grade 60 |
|---|---|---|
| #4 | 20 in | 30 in |
| #5 | 25 in | 38 in |
| #6 | 30 in | 45 in |
The same table gives straight tension development of 15 and 23 inches for No. 4, 19 and 28 inches for No. 5, and 23 and 34 inches for No. 6, in Grade 40 and Grade 60 respectively. Engineered development and splice lengths depend on the reinforcement and the design conditions. Use their specified details.
For a No. 4 Grade 60 tension lap in this table, 24 inches is 6 inches short of the required 30. If those bars lap without contact, the limit under the prescriptive rule is the smaller of 30 ÷ 5 = 6 inches and 6 inches, so set them no more than 6 inches apart.
Use the splice locations and staggering shown in the approved details. Review positions near corners and congested connections before the cage is tied.
Dowels, keyways and continuity
Check how each connection transfers the required forces. The footing-to-wall connection and a construction interruption in the wall can use different details.
- Dowels transfer specified forces between placements. Check size, spacing, hook or embedment and projection for the required development or overlap.
- Keyways can transfer shear across a joint where detailed. Use the approved shape, location and steel.
- Construction joints in foundation walls follow R404.1.3.3.7.8. For the plain-wall detail, including the specified nominally reinforced cases, locate the joint at a point of lateral support and use at least No. 4 crossing bars at no more than 24 inches on center with at least 12 inches of embedment each side. A reinforced wall can use the middle third of the span between lateral supports or use the plain-wall joint provisions. The stated exception allows required vertical steel, alone or combined with the crossing bars, where the spacing limit is met.
For standard sill anchorage under R403.1.6, verify the 1/2-inch minimum diameter, 7-inch minimum embedment and 6-foot maximum spacing. Check the plate middle third, nuts and washers, and the general two-bolt and end-distance rules. Where the end rule applies, the bolt is between seven bolt diameters and 12 inches from each end. Follow any applicable exception or stricter connection design.
Welded wire reinforcement and fibers
Welded wire reinforcement (WWR) under ASTM A1064 is a factory-welded grid. 6 × 6–W1.4 × W1.4 means 6-inch spacing each way with plain wires of 0.014 in² each. A lightly reinforced slab may use it to limit crack widths. Where engineered for the application, WWR can also carry structural forces. In a prescriptive slab on ground, R506.2.4 requires support so reinforcement stays from the slab center to its upper one-third during placement. Secure it before the pour instead of lifting it out of the concrete after placement.
Fiber-reinforced concrete under ASTM C1116 distinguishes Type I steel, Type II alkali-resistant glass, Type III synthetic and Type IV natural cellulose fibers. Synthetic microfibers chiefly address plastic shrinkage cracks. Selected macrofibers or steel fibers can provide specified post-crack resistance in an engineered mix, with performance verified by tests such as ASTM C1609. A fiber addition alone does not authorize omitting specified bars or mesh.
Pre-pour inspection checklist
Complete the reinforcement check with enough time to correct defects and obtain the required pre-pour approval.
- Size and grade. Match the bars and wires to the plan and selected table assumptions.
- Position and spacing. Follow the design or prescriptive schedule. The R404.1.3.3.7.6 wall-bar spacing bounds are one-half the wall thickness and 48 inches on center. The design or table can require tighter maximum spacing.
- Cover and supports. Check exposed faces, bar supports and tie security.
- Laps and embedment. Confirm the required lengths, orientations and locations.
- Cleanliness and embeds. Remove contamination and secure anchor bolts, dowels, sleeves and any specified joint details.
- Inspection. Obtain approval and resolve any proposed cuts or substitutions before covering the reinforcement.
A correctly positioned cage must also stay in position during discharge and vibration. Recheck it after workers, pumps or equipment cross the placement area.
How reinforcement is installed, step by step
On a typical residential foundation the sequence runs like this:
- Footing steel. Place the detailed bars on the required supports. Check the specified cover against earth.
- Dowels. Secure the specified bars to the cage or templates, with the required embedment in the footing and projection into the wall.
- Footing placement. Consolidate around the cage without shifting it.
- Wall steel. Tie the vertical and horizontal bars and verify the correct face or centerline placement and cover.
- Openings and corners. Install the scheduled trim and corner steel before closure.
- Inspection and placement. Recheck the completed cage, obtain approval and monitor placement. If a cage shifts, stop as needed and restore its position using the approved procedure.
Exam traps
- Read bar size and grade separately. No. 5 gives a 5/8-inch diameter, while Grade 60 describes yield strength.
- Use separate cover values for earth-cast, exposed formed and protected formed concrete.
- Use the applicable lap or development column. For No. 4 Grade 60 in the table, those are 30 inches and 23 inches.
- Support WWR at the required elevation and use fibers and mesh for the roles they were specified to perform.
In the prescriptive MRC footing and concrete-wall provisions, what minimum cover is specified for reinforcing steel where concrete is cast directly against earth?
1 inch
1-1/2 inches
3 inches
2 inches
A #5 reinforcing bar has a nominal diameter of:
1/2 inch
3/4 inch
1 inch
5/8 inch
Under MRC Table R608.5.4(1), what is the minimum tension lap splice for a #4 Grade 60 vertical bar?
30 inches
20 inches
38 inches
24 inches