45.4 Fireplaces & Chimneys

Key Takeaways

  • R1001.6 sets a 20-inch ordinary firebox depth, with the throat at least 8 inches above the opening and at least 4 inches deep. Confirm the conditions for the separate Rumford exception.

  • The hearth extension reaches 16 inches in front and 8 inches beyond the sides for an opening smaller than 6 square feet, and 20 and 12 inches at or above that threshold. Check the separate thickness rule and its raised-opening exception.

  • Check fireplace clearances under R1001.11 and masonry chimney clearances under R1003.18. Use the proper noncombustible chimney fireblocking at floor and ceiling penetrations.

  • R1003.9 requires the greater of 3 feet above the highest roof contact and 2 feet above any part of the building within 10 feet. Rule 547b gives Michigan-specific cap and chase-cover details.

  • R1003.15.1 sizes a masonry fireplace flue by net area and opening area. Use 1/12 for round, 1/10 for square or rectangular under 2:1, and 1/8 for rectangular at or above 2:1.

Last updated: November 2026

Masonry Fireplace Components

A masonry fireplace under 2015 MRC R1001 has a footing, firebox, hearth, throat and damper, smoke chamber, and chimney with a compatible lining. R1001.2 requires a concrete or solid masonry footing at least 12 inches thick and extending at least 6 inches past the fireplace or foundation wall on all sides. Bear on undisturbed natural soil or engineered fill below frost depth. For Michigan exterior footings, Rule 522 requires 42 inches below actual grade unless the building official approves a modification based on the specified conditions. Check any applicable frost requirement separately. Consult the Michigan-amended Figure R1001.1 and the provisions for seismic reinforcement and anchorage in the applicable categories.

The firebox may be solid masonry, grouted-solid hollow masonry, stone or concrete. With at least 2 inches of firebrick or another approved lining, provide at least 8 inches of solid masonry in the back and side walls including the lining. Without a lining, those walls are at least 10 inches thick. For the firebrick option, use ASTM C27 or C1261 firebrick, joints no wider than 1/4 inch, and ASTM C199 medium-duty refractory mortar (R1001.5). R1001.5.1 addresses steel units used with solid masonry.

Under R1001.6 the ordinary firebox is at least 20 inches deep. The throat is at least 8 inches above the opening and at least 4 inches deep. The passage above the firebox, including the throat, damper and smoke chamber, needs at least the flue's cross-sectional area. The Rumford exception requires a depth of at least 12 inches and at least one-third of the opening width, with a throat at least 12 inches above the lintel and at least 1/20 of the opening area. Over the opening, support masonry on a noncombustible lintel with at least 4 inches of bearing at each end. R1001.7 locates the throat or damper at least 8 inches above the lintel. Under R1001.7.1 the ferrous damper is operable from the room and at least 8 inches above the top of the opening.

The smoke chamber is normally 8 inches thick. It can be 6 inches including a qualifying lining of at least 2 inches of C1261 firebrick with C199 mortar or at least 5/8 inch of C315 vitrified clay. Parging needs a smooth interior using C199 refractory mortar. The chamber's inside height from throat to flue cannot exceed the opening's inside width. Under R1001.8.1, the limit from vertical is 45 degrees for rolled or sloped walls or prefabricated linings, and 30 degrees for corbeled masonry.

ElementWhat to verify
HearthConcrete or masonry with noncombustible support. At least 4 inches thick, reinforced for its own weight and imposed loads (R1001.9 and .9.1)
Hearth extensionNoncombustible support and reinforcement per R1001.9. Ordinarily at least 2 inches thick. The 3/8-inch minimum option uses approved noncombustible materials where the bottom of the firebox opening is at least 8 inches above the extension (R1001.9.2)
Opening under 6 square feetExtend at least 16 inches in front and 8 inches beyond each side (R1001.10)
Opening 6 square feet or largerExtend at least 20 inches in front and 12 inches beyond each side (R1001.10)
UndersideRemove combustible material against the underside of the hearth and extension after construction

Clearance to Combustibles

The default minimum from masonry fireplace front faces and sides is 2 inches and from back faces is 4 inches. Preserve these airspaces except for code-required fireblocking (R1001.11, R1001.12 and R302.11 through R602.8). R1001.11 allows contact for fireplaces specifically listed and labeled for that use under UL 127 and installed as instructed. Other exceptions cover masonry or concrete wall contacts and specified abutting trim or sheathing, with 12 inches measured from the inside surface of the nearest firebox lining for the stated cases. For exposed combustible mantels or trim on the fireplace front, keep at least 6 inches from the opening. Within 12 inches, the allowed projection is at most 1/8 inch for each inch of distance from the opening.

Masonry Chimneys and Flue Selection

R1003.2 gives the masonry chimney footing requirements. The chimney walls under R1003.10 use solid masonry or grouted-solid hollow masonry, at least 4 inches nominal. R1003.11 requires a lining suited to the appliance and its listing. Examples include ASTM C315 clay lining and listed UL 1777 lining systems, subject to appliance-specific provisions. For clay liners, R1003.12 uses ASTM C1283. Run the liner from at least 8 inches below the lowest inlet, or from the top of the smoke chamber for a fireplace, to above the enclosing masonry. Keep any slope within 30 degrees of vertical. Use C199 medium-duty water-insoluble refractory mortar with tight, smooth internal joints, and maintain the specified separation from the surrounding masonry so the assembly can move as designed.

With multiple flues, the R1003.13 default is bonded separating wythes at least 4 inches thick. The one-appliance exception permits adjacent liners with joints staggered at least 4 inches. Preserve the space around a liner under R1003.12.2. Another appliance cannot simply vent into that space. Section R1003.14 applies to appliance connectors and refers to the separate rule for multiple appliance venting. Use R1003.15 for a masonry fireplace.

Worked Flue Sizing

The R1003.15.1 area option uses at least 1/12 of the opening area for a round flue, 1/10 for a square or rectangular flue with aspect ratio under 2:1, and 1/8 for a rectangular flue at 2:1 or more. Compare against the net liner area. Table R1003.14(1) uses the inside diameter of a round liner, while Table R1003.14(2) lists square and rectangular units by nominal outside dimensions. The alternate R1003.15.2 chart uses chimney height from the firebox floor to the top of the flue.

For a 36-by-30-inch masonry fireplace opening, the area is 1,080 square inches. A round flue needs 90 square inches under Option 1. The 10-inch liner is listed at 78, so select the 10-3/4-inch liner listed at 90 in this example. A square flue needs 108. The nominal 12-by-12 liner provides only 102, while the nominal 13-by-13 provides 127. A rectangular flue with exactly a 2:1 aspect ratio would need 135 square inches.

R1003.17 generally requires a covered cleanout within 6 inches of the base of each flue. The opening is at least 6 inches high, with its upper edge at least 6 inches below the lowest inlet. Provide a noncombustible cover. A separate cleanout is unnecessary where a masonry fireplace flue can be cleaned through the fireplace opening. An ash dump provided below the firebox has a distinct R1001.2.1 cleanout provision.

Worked Chimney Termination Heights

R1003.9 requires at least 3 feet above the highest point of the roof penetration and 2 feet above any portion of the building within 10 feet. Calculate both, using the taller result. In both examples the roof rises 6 inches per foot of horizontal run and the highest roof contact at the chimney is the reference elevation.

  • The ridge is 4 horizontal feet uphill and is the highest feature within 10 feet. It rises 2 feet above the reference. The minimum top is the greater of 3 feet and 2 + 2 feet, so use 4 feet above the roof contact.
  • If the ridge is 12 feet uphill with the same uninterrupted pitch and no higher nearby features, the roof 10 feet uphill is still within the zone and rises 5 feet. The 2-foot clearance above that point gives 7 feet above the roof contact, which exceeds the 3-foot minimum.

Chimney Cap, Clearance and Roof Intersections

Michigan Rule 547b amends R1003.9.1 and its cap detail. Provide a concrete, metal or stone cap with at least a 10-degree slope, an edge or slot that drips clear and the flashing detail in Figure R1003.9.1(1). Check the 2-inch minimum at the outer edge, 2-inch overhang and the slot's 1-1/2-inch setback from the outer masonry face. Provide a bond break below a concrete cap and a compressible filler with sealant at the liner. Seal vertical cap joints. A metal cap laps at least 4 inches down the wall and is sealed. Use an ASTM C920 Type S or M, Grade NS, Class 25 joint sealant as specified by the rule.

If a spark arrestor is installed, R1003.9.2 requires net free area at least four times the flue outlet's net free area, heat and corrosion resistance equivalent to 19-gage galvanized or 24-gage stainless steel, and access for cleaning with a removable screen or cap. The allowed opening sizes pass spheres smaller than 3/8 inch and exclude spheres larger than 1/2 inch. For a masonry or metal rain cap, R1003.9.3 requires net free area underneath of at least four times the outlet area.

R1003.18 generally requires 2 inches of airspace to combustibles for a chimney within the building or its exterior wall, and 1 inch for a chimney wholly outside, including passage through a soffit or cornice. The clearance exceptions for qualifying listed liners, masonry-wall contacts and specified trim or sheathing have separate conditions. At floor and ceiling penetrations, R1003.19 requires securely fastened noncombustible fireblocking. At wood framing use a self-supporting detail or support it on metal strips or lath. Preserve the airspace elsewhere.

Where the chimney dimension parallel to the ridge exceeds 30 inches and the chimney does not intersect the ridge, provide the cricket required by R1003.20. Table R1003.20 gives height as a fraction of width: 1/2 at 12:12, 1/3 at 8:12, 1/4 at 6:12, 1/6 at 4:12 and 1/8 at 3:12. Flash and counterflash the cricket intersection as for the normal roof-chimney intersection. Where masonry veneers a framed chimney, R1003.10.1 separately calls for the wall-cladding through-flashing and weeps.

Factory-Built Fireplaces and Chimneys

R1004.1 requires a listed and labeled factory-built fireplace tested to UL 127 and installed under its listing. Its hearth extension is installed under the listing, distinguishable from the floor, and a listed and labeled extension complies with UL 1618. Under R1004.3–.5, decorative shrouds, unvented gas logs and gasketed doors are subject to specified compatible listings, testing and installation conditions.

R1005.1 requires listed and labeled factory-built chimneys installed and terminated under the manufacturer's instructions. In dwellings, R1005.3 generally uses UL 103 Type HT for chimneys with solid-fuel-burning appliances. Its open combustion chamber fireplace exception uses the specified UL 103 listing and marking without the Type HT rule. Michigan's amended R1005.4 requires UL 127 compliance for chimneys used with factory-built fireplaces. It also requires a metal chase cover with at least a 10-degree slope, a sealed 4-inch minimum lap down the chimney wall, and flashing and cladding per R703 and installation instructions. Use the state chase detail to coordinate the storm collar, cover and cladding with the listed equipment.

R1006 addresses exterior combustion air for the covered fireplaces. The exception applies when mechanical ventilation maintains neutral or positive indoor pressure. A factory-built fireplace's exterior air duct must be a listed component installed under its instructions. Masonry heaters use R1002, including Michigan Rule 545a's separate clearance criteria.

Inspection Points

  1. Confirm fireplace, chimney and appliance type, applicable listing, exterior combustion air and state details.
  2. Check footing bearing, thickness and projection, and the approved frost and seismic details.
  3. Check firebox, throat, damper, lintel, smoke chamber, hearth dimensions and nearby trim.
  4. Check liner material and joints, clearances and floor and ceiling fireblocking before concealment.
  5. Verify both termination heights, cap and sealant, cricket and roof flashing, and any required chase-cover detail.
Test Your Knowledge

Under 2015 MRC R1001.6, what is the minimum firebox depth for a masonry fireplace using the ordinary provision, outside the Rumford exception?

A

12 inches

B

16 inches

C

20 inches

D

24 inches

Test Your Knowledge

A masonry fireplace has an opening 40 inches wide by 30 inches high, about 8.3 square feet. What hearth extension does MRC R1001.10 require?

A

16 inches in front and 8 inches beyond each side

B

20 inches in front and 8 inches beyond each side

C

16 inches in front and 12 inches beyond each side

D

20 inches in front and 12 inches beyond each side

Test Your Knowledge

How high must a masonry chimney extend relative to the roof under MRC R1003.9?

A

At least 3 feet above the highest point where it passes through the roof and at least 2 feet above any portion of the building within 10 feet

B

At least 2 feet above the highest point where it passes through the roof and at least 3 feet above any portion within 10 feet

C

At least 3 feet above the ridge in all cases, regardless of distance

D

At least 10 feet above the roof surface in all cases