46.2 Ice & Water Shield Membranes

Key Takeaways

  • Michigan’s amended Table R301.2(1) shows Yes for ice barriers. Footnote (h) directs local entries by average daily January temperature of 25°F or less or a history of ice-dam damage. Confirm the applicable designation and covered material under R905.1.2.

  • The ice barrier is either not fewer than two layers of underlayment cemented together, or a self-adhering polymer-modified bitumen sheet (ASTM D1970 stock) applied in place of normal underlayment, extending from the lowest edges of all roof surfaces to a point not less than 24 inches inside the exterior wall line.

  • On roofs with slope equal to or greater than 8:12, the ice barrier must ALSO be applied not less than 36 inches measured along the roof slope from the eave edge — the two extent tests run independently and the longer reach governs.

  • Heat loss can melt upper-roof snow. Water refreezes at a colder eave and can back up beneath the roof covering. The membrane limits water entry when backup occurs.

  • The exception: detached accessory structures with no conditioned floor area need no ice barrier (R905.1.2 exception) — an unheated detached garage in Traverse City is exempt; the heated attached one is not.

Last updated: November 2026

Why Ice Dams Destroy Michigan Roofs

Heat reaching the upper roof can melt snow. Water runs down to a colder eave, freezes and forms a ridge. Later meltwater can back up under the roof covering and wet the deck. Air sealing, insulation and properly designed attic assemblies reduce the heat reaching the deck. An ice barrier helps protect against water entry if backup still occurs. Section 47.3 covers roof ventilation.

The Michigan Trigger: Table R301.2(1)

Michigan’s Table R301.2(1), as amended by R 408.30516, shows Yes in the ice-barrier column. Its footnote (h) directs the enforcing jurisdiction to enter Yes when the January average daily temperature is at or below 25°F or there is a history of local ice-dam damage, and No otherwise. Confirm the applicable local designation. Where designated, R905.1.2 covers asphalt shingles, metal roof shingles, mineral-surfaced roll roofing, slate and slate-type shingles, wood shingles and wood shakes.

What the Code Requires (R905.1.2, cross-referenced by R905.2.7)

For asphalt shingles the operative sections are R905.1.2 (the general ice-barrier rule) and R905.2.7 (which simply says asphalt-shingle ice barriers comply with R905.1.2). The requirement has four parts:

  1. Material. Either at least two layers of underlayment cemented together or a self-adhering polymer-modified bitumen sheet used in place of normal underlayment in the barrier zone. The self-adhering stock is the granulated or smooth modified-bitumen membrane the trade calls ice and water shield, manufactured to ASTM D1970 — the standard named throughout R905.1.1 for self-adhering products.
  2. Lower boundary. From the lowest edges of all roof surfaces — every eave, not just the front door elevation.
  3. Upper boundary. To a point not less than 24 inches inside the exterior wall line of the building. Use the exterior wall line as the reference and measure 24 inches horizontally inward in plan.
  4. The steep-roof addition. On roofs with slope equal to or greater than 8:12, the ice barrier shall also be applied not less than 36 inches measured along the roof slope from the eave edge. Read that "also" carefully: the wall-line test never disappears. On a steep roof both tests apply, and the barrier must satisfy whichever reaches farther up the deck.

Exception: detached accessory structures that contain no conditioned floor area need no ice barrier.

Worked Geometry: How Far Up the Slope Is "24 Inches Inside the Wall Line"?

Take a typical 6:12 roof with a 12-inch eave overhang. The horizontal run from the eave edge to the required barrier terminus is 12 (overhang) + 24 (inside the wall) = 36 inches of horizontal run. Convert to distance along the slope by multiplying by the pitch factor — the square root of 1 + (rise/12)²: 4:12 multiplies by about 1.054, 6:12 by about 1.118, 8:12 by about 1.202, 12:12 by about 1.414.

Overhang4:12 (×1.054)6:12 (×1.118)8:12 (×1.202)12:12 (×1.414)
none (24 in. run)25.3 in.26.8 in.28.8 in. → 36 in. test governs33.9 in. → 36 in. test governs
12 in. (36 in. run)37.9 in.40.2 in.43.3 in.50.9 in.
24 in. (48 in. run)50.6 in.53.7 in.57.7 in.67.9 in.

For the 6:12 roof with a 12-inch overhang, the required reach is about 40.2 inches along the slope. A 36-inch course alone falls short. On an 8:12 roof with no overhang, the wall-line calculation reaches about 28.8 inches, so the independent 36-inch minimum governs. Allow for required laps when selecting the number or width of membrane courses.

Application Practice

R904.1 requires the applicable manufacturer’s instructions. Verify the substrate and conditions before opening the roll.

  • Deck condition: prepare a clean, dry, sound surface. Follow the specified application-temperature limits and primer instructions for the substrate. For example, GRACE ICE & WATER SHIELD’s U.S. instructions specify at least 40°F for the air, deck and membrane during installation. They call for primer on identified substrates, with additional guidance where adhesion is marginal.
  • Sequence: integrate eave and rake edges under R905.2.8.5. Lap the field underlayment over the upper edge of the eave membrane and follow the product’s instructions at transitions. During reroofing, R908.6 requires primer where bituminous materials are to adhere to metal flashing.
  • Laps and penetrations: follow the product’s side and end lap dimensions and patch damaged membrane. Fastener sealing depends on the selected product and correct installation.
  • Beyond the eaves: follow the approved assembly at valleys, skylights and roof-to-wall connections. R905.2.8.2 lists separate valley lining methods and includes the ASTM D1970 substitution in the closed-valley provision.

Common Failures and Exam Traps

Check for insufficient width after laps, poor adhesion to wet or frosted decking, damage at fasteners, and gaps where roof planes meet. If the detached accessory exception is claimed, verify that the structure has no conditioned floor area.

Exam traps to mark:

  • Measuring 24 inches from the eave edge or fascia instead of 24 inches inside the exterior wall line — the barrier must first cross the overhang.
  • Treating the 36-inch along-slope requirement as a replacement for the wall-line rule on steep roofs. It is additional; the longer reach governs.
  • Offering a single layer of No. 15 felt as a compliant barrier. It is not: the choice is two cemented layers or self-adhering polymer-modified bitumen.
  • Forgetting the detached, unconditioned accessory-structure exception — and its limit: a heated workshop or finished pool house loses the exemption.
  • Assuming the ice barrier substitutes for valley lining requirements. Separate provisions govern (R905.1.2 for eaves; R905.2.8.2 for valleys).

The diagram traces the causes of backup and shows where a properly installed membrane limits water entry.

Loading diagram...
Ice dam formation and the eave ice barrier
Test Your Knowledge

In a Michigan jurisdiction where the ice barrier is required, a house has a 6:12 asphalt-shingle roof. How far must the barrier extend?

A

36 inches measured along the slope from the eave edge — the only distance the code states

B

Across the entire first course of shingles, whatever its exposure

C

Not at all — the Upper Peninsula's heavy snow pack insulates the eaves

D

From the lowest edge of the roof to a point at least 24 inches inside the exterior wall line, which reaches farther up the slope than 24 inches of membrane laid from the fascia

Test Your Knowledge

In the ice-barrier zone on a covered roof sloped 10:12, which statement correctly applies the two R905.1.2 extent tests?

A

Both apply: the barrier must reach at least 24 inches inside the exterior wall line AND at least 36 inches measured along the slope from the eave edge — the longer reach governs

B

Only the 36-inch along-slope measurement applies on steep roofs, replacing the wall-line test

C

The barrier may stop at the outside face of the wall because ice sheds off steep slopes

D

Slopes steeper than 8:12 are exempt from ice barriers

Test Your Knowledge

Which material satisfies the R905.1.2 ice-barrier specification?

A

One layer of No. 15 asphalt-saturated felt lapped 2 inches

B

A self-adhering polymer-modified bitumen sheet applied in place of normal underlayment — or two layers of underlayment cemented together

C

One ply of mineral-surfaced roll roofing over the eave zone

D

Any synthetic underlayment, provided it is installed full-width at the eaves