29.1 Footing Loads & Soil Bearing

Key Takeaways

  • For a centered load and a uniform bearing-pressure check, divide total service load per foot by allowable bearing pressure. At 4,000 plf and 1,500 psf the resulting width is 32 inches before checking other limits.

  • Table R401.4.1 presumptive bearing values are 12,000 psf for crystalline bedrock, 4,000 psf for sedimentary or foliated rock, 3,000 psf for gravel, 2,000 psf for sand and silty sand, and 1,500 psf for clay, silt and sandy clay.

  • Michigan generally requires exterior footings and foundation systems 42 inches below actual grade under R 408.30522. The building official may modify depth on evidence of conditions specified in the rule, and applicable frost protection must be checked separately.

  • Footings must bear on undisturbed natural soil or engineered fill (R403.1); fill that supports footings must be designed, installed and tested per accepted engineering practice (R401.2).

  • Uneven support can produce differential settlement, causing diagonal cracks, out-of-square openings and floor slopes. Check allowable bearing and expected settlement before footing design.

Last updated: November 2026

Load Paths: From Roof to Bearing Soil

A footing spreads wall or column loads over enough bearing area to meet the allowable soil pressure. Soil conditions also govern settlement. The goal is a continuous path from roof and floor framing through walls, beams or posts into the foundation and supporting ground.

Dead load includes permanent construction and fixed components. Occupancy live loads, snow and wind have distinct rules in R301. Use the applicable load combinations and account for the foundation and footing weight consistently with the bearing value used. For this simplified gravity example, assume a 32-ft clear-span roof bearing on the exterior walls and 16-ft floor spans bearing between the exterior walls and a center support. An exterior wall then takes 16 ft of roof tributary width and 8 ft of floor tributary width. A roof with a different bearing layout has a different tributary width.

Building a wall load in pounds per linear foot

ComponentUnit loadTributaryplf
Roof: 15 psf dead + 30 psf snow45 psf16 ft720
Second floor: 12 psf dead + 30 psf live42 psf8 ft336
First floor: 12 psf dead + 40 psf live52 psf8 ft416
Exterior wall, two stories at 15 psf15 psf18 ft270
8-in concrete foundation wall, 8 ft high (150 pcf × 8/12 ft)100 psf8 ft800
Wall reaction above footing2,542 plf

From load to width

For a centered load, the uniform pressure check gives a preliminary width:

Footing width (ft)=total wall load (plf)allowable soil pressure (psf)\text{Footing width (ft)} = \frac{\text{total wall load (plf)}}{\text{allowable soil pressure (psf)}}

Using only the 2,542-plf wall reaction above on soil with a nominal 1,500-psf allowance gives about 1.69 ft, or 20.34 in. That is a preliminary result before footing weight and the remaining design checks. A separate prescriptive lookup for a qualifying light-frame house with two stories and a basement at 1,500 psf and a 30-psf snow or roof live load gives 23 × 6 in as the table entry. Check the chosen approach and footing geometry before specifying dimensions.

For a second bearing check, assume a centered 4,000-plf total service load including the footing weight. On the same 1,500 psf clay, 4,000÷1,500=2.67 ft=32 inches4{,}000 \div 1{,}500 = 2.67\ \text{ft} = 32\ \text{inches} minimum. A 36-inch trial width gives about 1,333 psf. It still needs geometry, strength and settlement checks. Note what the arithmetic does not say: a wider footing does not make bad soil good. It only lowers the contact pressure. If the soil cannot support the load without excessive settlement, the fix is a geotechnical evaluation, over-excavation and engineered fill, or a deep foundation — not a bigger pad.

Presumptive soil bearing values (Table R401.4.1)

Where a full geotechnical evaluation is not provided, the code permits the following assumed values. They are a fallback, not a soil test.

Class of materialPresumptive bearing pressure
Crystalline bedrock12,000 psf
Sedimentary and foliated rock4,000 psf
Sandy gravel and/or gravel (GW, GP)3,000 psf
Sand, silty sand, clayey sand, silty gravel, clayey gravel (SW, SP, SM, SC, GM, GC)2,000 psf
Clay, sandy clay, silty clay, clayey silt, silt and sandy silt (CL, ML, MH, CH)1,500 psf

Several exam points hide in the footnotes. The 1,500 psf clay value is the floor of the table; where the building official determines that in-place soil with less than 1,500 psf capacity is likely, the allowable capacity must come from a soils investigation. A soil test is called for where accepted soil science indicates expansive, compressible or shifting soil — the building official determines whether a test is required (R401.4). And where topsoil or subsoil is compressible or shifting, R401.4.2 provides removal or active-zone stabilization as alternatives to full geotechnical evaluation. Removed compressible or shifting material must not be used as fill.

Settlement, Frost and the Failures Exams Test

Uniform vs. differential settlement

Settlement within the design limit may be acceptable. Unequal movement across a building produces differential settlement, where one part of the foundation moves more than another. A corner that drops 1-1/2 inches while the adjacent wall drops 1/4 inch produces angular distortion — the structure is being bent. The visible results are predictable: stair-step cracks in masonry, diagonal cracks radiating from door and window corners, drywall cracking at ceiling-wall joints, doors that rack and no longer latch, and floor slopes that show up under a level.

Both large total settlement and excessive differential settlement can damage a building. Check utility connections and transitions to adjoining work as well as the foundation. Differential movement is created by bearing part of the footing on hard material and part on soft material, by a footing that spans a buried stump or trash pit, by a downspout that dumps water at one corner, or by frost lifting one side of an unheated garage.

Frost heave and Michigan's 42-inch depth

In freezing soil, water does not simply expand in place. Thermal gradients pull capillary water upward toward the freezing front, where it grows into horizontal ice lenses that lift everything above them. When the lenses thaw, the soil turns to mush and the structure drops. Heave and thaw are rarely even around a building, so the result is again differential movement.

Michigan’s general minimum is all exterior footings and foundation systems shall extend 42 inches below actual grade (R403.1.4 as amended by R 408.30522). Michigan's Table R301.2(1) also lists the frost line depth as 42 inches. The building official may modify the depth only on evidence of specific conditions — freezing degree days, soil type, groundwater, snow depth experience, exposure, or other conditions that affect the foundation system. Footings are never permitted to bear on frozen soil unless the frozen condition is permanent.

Two traps follow from that sentence. First, 42 inches is measured from actual grade, not from the basement floor, not from the top of the footing, and not from the top of the wall. A basement footing 8 feet below the first floor still has to be 42 inches below the exterior grade line. Second, freestanding accessory structures get limited relief: no frost protection is required for light-frame accessory buildings of 600 square feet or less with an eave height of 10 feet or less, or for non-light-frame accessory buildings of 400 square feet or less with the same eave height. Decks not supported by the dwelling do not need frost-depth footings either. Those are frost-protection exceptions under R403.1.4.1. Check the separate Michigan minimum-depth rule and its approval process for any shallower footing.

Bearing on undisturbed soil or engineered fill

R403.1 requires footings to be supported on undisturbed natural soils or engineered fill, and R401.2 requires fill soils that support footings to be designed, installed and tested in accordance with accepted engineering practice. In the field that means: strip all topsoil, roots and debris; excavate to firm mineral soil; where over-excavation occurs, fill with compacted structural fill placed in lifts and tested — never with loose spoil, cinders, or construction debris. A footing poured on loose backfill is a footing waiting to settle.

The practical inspection sequence matters too. Before concrete is placed, the footing trench bottom should be clean, free of standing water and frost, at the correct elevation, and bearing on the material the design assumed. Confirm the required inspection point with the enforcing agency before the pour and have the excavation, forms and required reinforcement available to inspect. Michigan does not adopt the model inspection list at R109.1, so the exact schedule comes from the enforcing agency — but R109.3 puts the request with the permit holder or agent, and amended R109.4 governs approval before proceeding.

Quick code reference

QuestionAnswer
How wide must the footing be?Load ÷ allowable soil pressure, then round up; or use Tables R403.1(1) through R403.1(3)
What soil values may I assume?Table R401.4.1: 12,000 / 4,000 / 3,000 / 2,000 / 1,500 psf
How deep?Generally 42 in below actual grade under R 408.30522. Check the exception and applicable frost protection.
What may it bear on?Undisturbed natural soil or engineered fill (R403.1); tested fill per R401.2
What if the soil is soft or organic?Check bearing and settlement and use the approved soil treatment or foundation design

A last trap: presumptive values apply only where a geotechnical evaluation is not provided, and only where the building official accepts them. If a test pit shows 6 inches of topsoil over soft clay, the answer is not 1,500 psf — the answer is to remove the unsuitable material first.

Test Your Knowledge

For a uniform bearing check, a continuous exterior footing carries a centered total service load of 4,000 pounds per linear foot on soil with a presumptive bearing capacity of 1,500 psf. What is the calculated minimum footing width before rounding to a buildable dimension?

A

1.5 ft (18 in)

B

2.67 ft (32 in)

C

3.0 ft (36 in)

D

4.0 ft (48 in)

Test Your Knowledge

A footing bears on undisturbed clay at one corner and on 4 ft of loose, uncompacted fill at the opposite corner. Which condition is most likely to result?

A

Uniform settlement of the whole structure, which is structurally harmless

B

Higher bearing capacity under the fill because loose soil compacts easily

C

Differential settlement, producing diagonal cracking and racked openings

D

Frost heave only, because fill soils do not consolidate