37.2 Subflooring & Decking

Key Takeaways

  • In MRC Table R503.2.1.1(1), select structural sheathing from the maximum subfloor span column. For example, the 24/16 row allows 16 in. and the 48/24 row allows 24 in. subject to the applicable support and installation requirements. The load columns under the roof heading describe roof use.

  • For lumber floor sheathing, Table R503.1 specifies 11/16 in. net thickness at 24 in. joist spacing if laid perpendicular or 3/4 in. if laid diagonally. Both orientations use 5/8 in. at 16 in. spacing.

  • For the Table R602.3(1) item 31 schedule, fasten 19/32 to 1 in. subfloor sheathing to wood framing with 8d common nails at 6 in. at supported edges and 12 in. at intermediate supports. Combination subfloor-underlayment has separate rows.

  • Lay the panel strength axis across the supports. Support panel ends and the perimeter as detailed, and use T&G, blocking or a qualifying assembly detail along unsupported edges. Follow the panel manufacturer’s joint spacing.

  • A 24 by 36 ft floor is 864 sq ft or 27 nominal 4x8 panels by area. With the example’s 10% allowance, order 30 panels after checking that the cuts and joints work on the actual layout.

Last updated: November 2026

What the Subfloor Is Doing Structurally

Subflooring supports the finish floor and transfers loads to joists. When detailed and fastened as a diaphragm, it also carries lateral loads across the floor. Use the panel grade, support spacing, fastening and assembly requirements together.

Panel Identification and Span Rating

Wood structural panels used as subfloor must conform to DOC PS 1, DOC PS 2, CSA O437 or CSA O325, and must have grade, bond classification and Performance Category identified by an approved agency’s grade mark or inspection certificate (MRC R503.2.1). Use the Performance Category when the code calls for panel thickness.

Read the grade and bond classification together. Exposure 1 allows temporary construction exposure. For long-term exposure, use the applicable protected assembly or a product approved for that service. Follow the plans and product instructions.

For rated sheathing with a two-number span rating, the first refers to roof use and the second to subfloor use. A 48/24 mark identifies a 24 in. subfloor span under the specified conditions. A single-floor product can instead have a single rating such as 24 oc.

Read the Subfloor Column

Rated sheathingNominal minimum thicknessMaximum subfloor span
24/167/16 in.16 in.
32/1615/32 or 1/2 in.16 in.
40/2019/32 or 5/8 in.20 in.
48/2423/32 or 3/4 in.24 in.
60/327/8 in.32 in.

In Table R503.2.1.1(1), the right-hand maximum span column applies to subfloor use. The listed total and live loads at maximum span appear under the roof heading. Check the floor loads separately with the applicable code or APA E30 provisions, the panel information and the assembly design. A 48/24 panel at 24 in. spacing meets the table’s span entry. Also check edge support, floor loads and the selected finish system before specifying the floor.

Table R503.1 is a different table

A frequent citation error: Table R503.1 is the minimum thickness of lumber floor sheathing, not panels. It applies to board sheathing laid perpendicular or diagonally over joists:

Joist spacingMinimum net thickness, perpendicularMinimum net thickness, diagonal
24 in.11/16 in.3/4 in.
16 in.5/8 in.5/8 in.

R503.1.1 locates lumber end joints over supports unless the boards are end-matched and bear on at least two joists. Select the table by the type of structural decking shown on the drawings.

Installation: Orientation, Joints and Gaps

Put the marked strength axis across the joists. It usually runs in the long direction. The table assumes panels continuous over at least two spans. Coordinate both dimensions before cutting. Stagger joints as required by the construction detail and panel instructions, and plan the cuts to keep short panel ends on framing.

For an unsupported long edge, use a T&G panel, provide blocking, or use a qualifying underlayment or finish-floor detail where the applicable row and footnotes allow it. Check the conditions of that specific panel and assembly, including joint offset for some underlayments. Roof edge clips are listed under the roof edge support provision. Keep the floor perimeter supported by framing or solid blocking per the fastening table.

APA recommends about 1/8 in. spacing at structural panel edges and ends unless the manufacturer directs otherwise. Check products with a self-spacing profile. Allow for movement as panels take up moisture, particularly during construction.

Fastening schedule

Fastening is a code table, not a preference. MRC Table R602.3(1) governs:

Panel thicknessFastenerPanel edgesIntermediate supports
3/8 to 1/2 in.6d common (subfloor)6 in.12 in.
19/32 to 1 in.8d common6 in.12 in.
1-1/8 to 1-1/4 in. (subfloor sheathing, item 32)10d common or 8d deformed (2½ × 0.131 in.)6 in.12 in.
3/4 and less (combination subfloor-underlayment)6d deformed or 8d common6 in.12 in.

Footnote (h) identifies where edge spacing applies, including supported edges and required floor-perimeter blocking. Keep the perimeter supported. Drive fasteners flush and use the edge distance in the product and construction details.

Select the code row for the application and specified fastener. A different fastener system, such as a proprietary screw, needs an applicable approval and installation schedule.

Adhesive

Follow the drawings and manufacturer for a glued floor. APA recommends compatible floor adhesive, such as a product meeting ASTM D3498. Clean the joist contact surface and apply only enough adhesive to install one or two panels within the product’s working time. Complete the required mechanical fastening.

Underlayment, Moisture and Squeaks

Separate Underlayment and Finish Floors

Combination subfloor-underlayment is a structural panel suitable for selected finishes. Sanded plywood in that application uses Table R503.2.1.1(2) and its grade, thickness and edge-support conditions. For a separate plywood underlayment, follow the finish and underlayment instructions. APA recommends a dry, flat deck and staggering the underlayment joints relative to the subfloor. Use the fasteners, spacing and panel gap for that assembly.

Type PBU particleboard floor underlayment must meet ANSI A208.1 and be at least 1/4 in. thick under R503.3.1–.2. It is an underlayment, separate from the structural panel. Where a table footnote allows qualifying fiber-cement underlayment, the board must meet ASTM C1288 or ISO 8336 Category C. For tile, check the whole assembly’s stiffness and installation requirements in addition to the structural floor deflection limit.

Moisture and Squeaks

Protect panels in storage, clear standing water from the deck and let the assembly dry before covering it. Verify moisture limits for the selected finish. A miss at a joist, an unsupported joint or movement between panel and framing can cause noise. Check framing alignment, support and attachment before adding the finish. Use dry framing, the specified fasteners and the approved glue detail where applicable.

Worked Example: A 24 by 36 ft Floor

The area is 24 × 36 = 864 sq ft. A nominal 4 by 8 ft sheet is 32 sq ft, so the area count is 27 panels. Check whether that count matches a supported, staggered layout.

Suppose the joists run in the 24 ft direction at 16 in. on center, with boundary support on both sides and the required intermediate bearing. This is a panel takeoff, so the 24 ft direction does not establish a joist span. Place the 8 ft panel dimension across the joists along the 36 ft direction. The floor has six 4 ft courses along the 24 ft direction. Each course can cover its 36 ft run with four 8 ft pieces and one 4 ft piece. Alternate the short piece between the two ends. This staggers the panel end joints on the 16 in. module. If the two halves of each cut panel can be used, the six courses use 24 full sheets and three more split for the short ends.

With 10% allowance for cuts and damage, 27 × 1.10 = 29.7. Order 30 panels in this example. Across the 36 ft dimension, 432 ÷ 16 = 27 spaces, or 28 support lines including both edges. Count joists and perimeter members from the framing detail rather than assuming every line is an interior joist.

Before Covering the Deck

Check the panel marks, spacing and loads. Verify the axis and cut layout, edge support and perimeter blocking, joint spacing, fastener locations and drive depth. Confirm the deck is dry and flat enough for the finish system.

Test Your Knowledge

Which listed rated sheathing meets the 24 in. joist spacing in the maximum subfloor span column of 2015 MRC Table R503.2.1.1(1), assuming the specified support and installation conditions are met?

A

7/16 inch, span rating 24/16

B

19/32 inch, span rating 40/20

C

15/32 inch, span rating 32/16

D

23/32 inch, span rating 48/24

Test Your Knowledge

For 23/32 in. subfloor sheathing attached to wood framing with 8d common nails, what spacing does item 31 of 2015 MRC Table R602.3(1) specify?

A

4 inches on center at supported edges and 8 inches at intermediate supports

B

6 inches on center at supported edges and 12 inches at intermediate supports

C

8 inches on center at supported edges and 16 inches at intermediate supports

D

12 inches on center at supported edges and 12 inches at intermediate supports

Test Your Knowledge

A 24 by 36 ft floor uses nominal 4 by 8 ft panels. Based on net area and a 10% allowance for waste, how many whole panels should the estimator include?

A

24 panels

B

27 panels

C

30 panels

D

36 panels