43.3 Anchors, Ties & Connections
Key Takeaways
R403.1.6 ordinarily sets at least 1/2-inch sill bolts, at least 7 inches of embedment, at most 6 feet between bolts, at least two per plate section and an end bolt from seven bolt diameters to 12 inches from each end.
Connect the floor and roof using the specified R606 connection detail or approved design. Read the figure for the applicable ledger, span and bolt diameter.
R606.3.3 calls for 5/8 inch of mortar cover and appropriate embedment or face-shell engagement. Select corrosion protection by accessory and exposure under Table R606.3.4.1.
Veneer ties ordinarily allow at most 2.67 square feet per tie, 32 inches horizontally and 24 inches vertically. Check the 2-square-foot seismic and wind exception, supplemental opening ties and the chosen veneer system.
For drained anchored veneer, coordinate the applicable airspace detail with the flashing and weeps. The 2015 code places the anchored veneer requirements in R703.8.
Anchorage transfers forces between assemblies. A foundation bolt connects the wood sill to the foundation. A floor or roof anchor delivers lateral load to the supporting system. A masonry cavity tie connects the wythes. A veneer tie transfers lateral load to the backing and is installed separately from the support carrying the veneer weight. Check which connection a drawing calls for before selecting hardware, embedment or spacing.
Wood Sill Plates on Masonry
For the ordinary bolt method in 2015 MRC R403.1.6, use at least 1/2-inch-diameter bolts at no more than 6 feet on center. Embed them at least 7 inches in concrete or grouted CMU cells, position them within the middle third of the plate width, and tighten a nut and washer at each bolt. Provide at least two per plate section and a bolt within 12 inches of each end, at least seven bolt diameters from the end. Seven diameters is 3-1/2 inches for a 1/2-inch bolt. Check the specified short plate exceptions and approved alternatives, which can include an anchor or strap giving equivalent anchorage. For seismic braced wall lines check R403.1.6.1 and the approved design with Michigan's exclusion of R602.11 in the state adoption rule. Do not import the model R602.11 plate-washer requirement as a Michigan blanket rule.
Worked Layout for a Single 40-Foot Plate Section
The example assumes one idealized 480-inch plate section with no additional corner, bracing or hardware constraints. With both end bolts within 12 inches, the distance between them is at least 456 inches. Seven bolts make six intervals and can bridge only 432 inches at 72-inch maximum spacing, so at least eight bolts are needed. If both end bolts are 8 inches in, the distance between them is 464 inches. Eight bolts give seven intervals of about 66.29 inches. Check the drawn layout against the maximum after rounding, and restart the end and bolt-count checks for every actual plate section. Locate the bolts to clear other hardware while keeping them in the specified grouted cells and within the plate limits.
Masonry at the Floor and Roof
For the floor and roof restraint methods in R606.6.4.2, first confirm it is an applicable A, B or C seismic detail. R606.6.4.2.1 identifies manufacturer-spaced metal straps, 1/2-inch bolts at a maximum 6 feet on center or other approved anchors for a roof. The section specifies 16 inches of masonry embedment, or hooking or welding to bond-beam reinforcement at least 6 inches below the top of the wall. Under R606.6.4.2.2, floor diaphragms can use manufacturer-spaced straps, 1/2-inch bolts at a maximum 6 feet installed according to Figure R606.11(1), or other approved methods. Match the ledger and anchor installation to the referenced figure and other applicable limits. Its floor and roof wall details identify A, B and C and wind loads below 30 psf.
For a 12-foot span in the figure's 10-to-15-foot row, the 1/2-inch bolt entries are 16 inches on center for a floor ledger and 21 inches for a roof ledger. Identify the supported assembly, bolt diameter and row before reading spacing. The foundation sill detail uses its own load path and rules.
Intersecting bearing walls that provide horizontal support can be masonry bonded under R606.6.4.1.1, with at least half the units at the intersection interlocking and alternate units bearing at least 3 inches on the unit below. R606.6.4.1.2 gives steel-connector alternatives. At interior nonbearing intersections, it calls for No. 9-gage or heavier joint reinforcement or 1/4-inch galvanized mesh hardware cloth at intervals no greater than 16 inches. At other intersecting masonry walls, the joint reinforcement detail uses at least No. 9 gage, no more than 8 inches between levels and at least 30 inches of extension in each direction from the intersection. Install the specified connection to both elements before covering the work.
Wall Ties Between Masonry Wythes
R606.3.3 requires the tie ends in mortar joints with at least 5/8 inch mortar cover from the exposed face. Do not bend ties after embedment in mortar or grout. Embed ties at least 1-1/2 inches into the bed of solid units, solid-grouted hollow units or hollow units in anchored veneer. In other hollow masonry, ties must engage the outer face shell at least 1/2 inch.
R606.13 distinguishes the ways to bond adjacent masonry wythes. In its fixed 3/16-inch tie option, use one tie per 4-1/2 square feet or less, with staggered alternate courses and maximum spacing of 36 inches horizontally and 24 vertically. Use the specified rectangular ties for hollow units with vertical cells, or prescribed hooked ends in other walls. Add ties at all openings in this option, within 12 inches of the opening and spaced at most 3 feet around the perimeter. Adjustable ties joining masonry wythes are limited to 2.67 square feet each, 24 inches in either direction and 1-1/4 inches of bed-joint offset. With qualifying prefabricated joint reinforcement, each cross wire serving as a tie serves at most 2.67 square feet, with vertical spacing at most 16 inches and cross wires No. 9 gage or larger.
Corrosion Protection in R606
| Masonry accessory or exposure | Minimum corrosion protection under Table R606.3.4.1 |
|---|---|
| Ordinary interior joint reinforcement | ASTM A641 Class 1 |
| Exterior wire tie or anchor fully embedded in mortar or grout | ASTM A641 Class 3 |
| Exterior wire tie or anchor partly embedded, or joint reinforcement in exterior or moist interior walls | ASTM A153 Class B-2 |
| Sheet tie or anchor exposed to weather | ASTM A153 Class B-2 |
| Sheet tie or anchor fully embedded in mortar or grout | ASTM A653 G60 |
| Stainless hardware listed for any exposure | ASTM A167 Type 304, as identified in the 2015 table |
Match the specified accessory and exposure. Fasteners and the attachment to framing also must suit the approved system. Tie diameter, corrosion protection, effective embedment and spacing all matter.
Anchored Veneer Over Framing
R703.8.4 requires corrosion-resistant ties with at least 1-1/2 inches of embedment into mortar or grout and 5/8 inch of cover to the exposed face. For wood framing, Table R703.8.4 lists 22-gage corrugated sheet ties (0.0299 by 7/8 inch minimum) or No. 9-gage strand wire with a hook, with the applicable approved fastener. The 8d common nail is the basic entry for both wood details, with the table's rust-inhibitive fastener requirement. Use the listed 8d ring-shank fastener for the wood detail in D0, D1 and D2. Fasten to the backing framing. The ordinary wood corrugated tie detail has a nominal 1-inch space from sheathing to veneer. The table's wood strand-wire detail also specifies a nominal 1-inch minimum and has a maximum 4-1/2 inches from backing to veneer. Cold-formed steel details use an adjustable wire tie and a No. 10 screw with at least three exposed threads. Confirm the exact measured surfaces and tie type. R703.8.4.2 allows a grouted alternative with the specified water-resistive protection.
R703.8.4.1 simultaneously limits ordinary tie layout to 2.67 square feet per tie, 32 inches horizontally and 24 inches vertically. At 16 by 24 inches a field tie serves 384 square inches, or 2-2/3 square feet. At 32 by 24 it would serve 768 square inches, or 5-1/3 square feet, so that layout fails the area limit. In D0, D1 or D2, in townhouses in C, or where wind pressure exceeds 30 psf, use at most 2 square feet per tie. For openings greater than 16 inches in either dimension, provide supplemental ties within 12 inches of the opening and no more than 3 feet apart along its perimeter.
For a solid 200-square-foot area in an ordinary exposure, 200/2.67 requires at least 75 ties by area alone. Draw the field grid against the stud and mortar-joint layout and check edges, spacing, any openings and the applicable unit-support details before ordering. Coordinate flashing below the first course above grade and at other supports (R703.8.5) and weep holes directly above the flashing, at least 3/16 inch in diameter and at most 33 inches on center (R703.8.6). Before the next lifts of brick obscure the work, check framing attachment, embedded length, cover, opening ties and the drainage path against the approved assembly.
For the ordinary 2015 MRC R403.1.6 bolted sill over grouted CMU, what are the specified minimum bolt diameter and embedment and maximum center-to-center spacing?
5/8-inch bolts, 12-inch embedment, maximum 4 feet on center
1/2-inch bolts, 4-inch embedment, maximum 8 feet on center
3/8-inch bolts, 7-inch embedment, maximum 6 feet on center
At least 1/2-inch bolts and 7 inches of embedment into grouted cells, at most 6 feet on center and at most 12 inches from each plate end
What field spacing and area limits apply to ordinary anchored veneer ties under 2015 MRC R703.8.4.1 where the tighter wind and seismic area exception does not apply?
Maximum 16 inches horizontally and 24 inches vertically, one tie per 1.5 square feet
Maximum 32 inches horizontally and 24 inches vertically, not more than 2.67 square feet per tie
Maximum 24 inches horizontally and 32 inches vertically, one tie per 4.5 square feet
Maximum 48 inches in both directions, one tie per 4.5 square feet
Sections you finish are checked off in the contents.