34.2 Concrete Curing
Key Takeaways
Curing maintains the moisture and temperature the concrete needs for hydration and development of the specified properties.
Start protecting against evaporation early. Select the final cure and confirm its timing, duration and any test-based release criteria from the applicable specification.
Apply an approved membrane at the specified rate for the actual finish. Check later coatings or flooring for compatibility and for any required residue removal.
ACI 306R-16 recommends at least 55°F for placement and protection of normalweight concrete in sections less than 12 inches thick. About 500 psi addresses one early freezing event, while repeated cycling in critical saturation has a higher threshold.
Curing compounds primarily retain moisture. Use a cure-and-seal product or a separate later sealer only where it is compatible with the specified system.
Quick Answer: Curing maintains moisture and temperature so hydration can continue. Start protecting the concrete during placement and finishing, then apply the specified final cure as soon as the surface can accept it. Use the specified method and duration or verified release criterion. A high early strength label, dry appearance or an early freezing threshold does not establish that curing can stop.
Why Moisture and Temperature Matter
Portland cement reacts with water. Calcium silicate hydrate is a principal product of this reaction and binds the hardened paste together. Bleeding occurs when water moves upward in fresh concrete. Evaporation at the surface and later drying are different processes. There is no need to let moisture escape for concrete to harden. If evaporation outruns bleeding, the exposed surface can dry and crack before the body has gained strength. Drying also slows or interrupts hydration after setting, particularly near the surface.
Curing develops the surface that must resist abrasion, weather and deicing exposure. NRMCA reports that concrete in a dry curing environment can lose as much as half its potential strength in comparison with moist-cured concrete. That comparison illustrates the risk, not a prediction for every mix. Curing also affects permeability and early cracking. In freezing exposure, curing complements mixture durability and a proper air-void system. It cannot supply the missing air entrainment.
Choose a Method Before Placement
| Method | Use | Controls |
|---|---|---|
| Ponding or continuous sprinkling | Keep compatible surfaces supplied with water | Use suitable water and prevent drying cycles. Use ponding where water can be contained. |
| Wet absorbent covers | Keep slabs or other accessible surfaces continuously moist | Prewet covers, overlap them, and replenish water. Uniform contact matters. |
| Fogging during initial protection | Limit rapid evaporation while a fresh surface would be marred by final curing | Fog above the surface. Do not work water into the paste. |
| Moisture-retention sheets | Cover slabs or compatible formed work | Use the specified sheet material, such as ASTM C171. Overlap, seal and secure the edges. Contact marks can be a concern on appearance-sensitive work. |
| Liquid membrane | Limit water loss where this system is allowed | Apply a uniform film at the specified rate and check compatibility with subsequent work. |
| Form retention or insulated covers | Keep formed faces from drying or protect concrete against heat loss | Protect exposed faces separately. Check whether the particular cover retains moisture as well as heat. |
Maintaining existing moisture may be adequate for some mixtures. For low water-to-cementitious-material ratios, ACI advises checking whether water curing is needed to sustain hydration. A surface that requires additional curing water is a different case from a compatible slab whose moisture can be retained with a membrane. Specify methods before work starts. For example, plan a water supply for wet covers or use an approved membrane for a site without one.
Curing Compounds and Later Finishes
ASTM C309 covers liquid membrane-forming curing compounds. Type 1 is clear or translucent without dye. Type 1-D has fugitive dye for seeing where the material has been sprayed. Type 2 is white-pigmented and can help reduce solar heating. Class A puts no restriction on the type of vehicle solids, while Class B uses resin solids. Water-retention testing uses the applicable ASTM C156 method with the specified laboratory conditions. Use the coverage rate and coat instructions approved for the field surface. For example, one resin product specifies 200 ft²/gal for exterior broomed work and 400 ft²/gal for a tight steel-troweled finish.
After final finishing, apply the specified membrane once bleeding has ended, free surface water has cleared and the surface will not be marred. Under rapid evaporation a surface can lose its sheen while bleeding is still active. Protect it during that interval and confirm surface readiness before applying the membrane. Follow the written directions on dry, porous or formed surfaces and on transitions from other methods. Check film continuity, including edges.
ASTM C1315 covers products with special properties for curing and sealing. A cure-and-seal system can serve both purposes if approved for the installation. For a later coating, adhesive, topping or floor covering, check that product's moisture, age and surface-preparation limits. Keep incompatible membranes out of the system or remove their residues as directed. A product described as dissipating still requires verification that the surface is ready.
How Long to Cure
ACI PRC-308-26 is a curing guide. ACI SPEC-308.1-23 is a specification with initial, final and termination requirements when incorporated into the project. NRMCA CIP 11 describes typical external curing periods of 3 to 7 days. A historical specification such as ACI 301-96 used a seven-day period with a three-day provision for high-early-strength concrete and separate test-based release routes. These figures are tied to that specification. There is no stand-alone three-day rule whenever a bag says Type III, nor a universal extension based on the name of a blended cement.
For a given job, read the cure method, the required moisture and temperature, and the duration or termination criteria together. If the governing documents allow a strength-based release, use the authorized in-place strength evidence and obtain any required approval. Suppose the specification allows release only after the in-place strength reaches 70% of a specified 4,000 psi, and the other cure criteria are met. The threshold is 2,800 psi. An authorized test result of 2,600 psi is below it. A laboratory-cured cylinder prepared for acceptance alone does not establish the required in-place strength. Nor does getting above 2,800 psi authorize loading or stripping if those operations have different criteria.
Weather and Protection
ACI 306R-16 considers conditions cold when air temperature has fallen or is expected to fall below 40°F during the protection period. For normalweight concrete in sections less than 12 inches thick, its recommendation for the minimum as placed and maintained is 55°F. The corresponding value for sections 12 to 36 inches thick is 50°F. Use the applicable protection plan and monitor concrete temperatures, including vulnerable edges. Cooler concrete gains strength more slowly. Use the actual mix, temperatures and specified tests or times to establish adequate curing and protection.
About 500 psi protects against one early freezing event. Repeated freeze-thaw while critically saturated calls for protection until about 3,500 psi. Neither number overrides the specified cure, formwork, loading or other release criteria. Remove ice and snow and thaw frozen bearing surfaces before placement. Limit abrupt cooling when the protection comes off. Moisture retention remains important in heated enclosures. Select external water and insulation methods appropriate to the conditions.
For hot or windy placements, estimate surface evaporation from concrete temperature, air temperature, humidity and wind. About 0.20 lb/ft²/h is a common ACI hot-weather specification action level. Low-bleeding mixes can require precautions at lower rates. Use the plan's limit and control drying with windbreaks, shade, fogging as appropriate and prompt final curing. Maintain the cure for the specified duration.
Worked Example: Cover and Compound for a 24 × 24 ft Slab
The job specifies a 4-inch-thick, broom-finished exterior slab, 576 ft². The two plans below are alternative permitted methods for the example. Prepare the selected supplies before placement.
Moisture planning. At a nominal evaporation rate of 0.20 lb/ft²/h, 576 × 0.20 is 115.2 lb/h, equivalent to about 13.8 gal/h at 8.34 lb/gal. This is an estimate of the indicated evaporation potential from an exposed surface. It does not size a water supply for covered work. Account for actual conditions, runoff and equipment, and monitor that the coverings stay wet.
Wet covers with sheet protection. With 3-ft-wide burlap and stipulated 6-inch side laps, ten 25-ft strips cover 25.5 ft across and 25 ft along the slab. This uses 250 linear feet, or three 100-ft rolls. For separate 10-ft-wide sheeting and a stipulated 6-inch lap, three 26-ft strips cover 29 by 26 ft before securing the edges. The sheet extends more than 8 inches beyond every slab edge if centered. One 100-ft roll supplies the 78 linear feet. Check site geometry and the approved overlaps and securement before cutting.
Approved membrane option. If the specified field rate is 200 ft²/gal for one full coat on this surface, the net requirement is 576 ÷ 200 = 2.88 gallons. With the stipulated 10% estimating allowance, plan for about 3.17 gallons and purchase a 5-gallon pail if that is the package offered. The allowance is for estimating supply. Apply the specified actual coverage to the work. If a product allows two perpendicular passes at a stated combined rate, do not treat that total rate as the rate for each pass.
Field Checks
- Confirm the approved method, supply quantities, weather protection, duration or release condition, and compatibility with the final surface treatment.
- Use early evaporation controls until the planned final cure can be placed without damaging the surface.
- After application, check the edges and seams or membrane continuity. Fix covering damage and interrupted wetting using the approved procedure.
- Record dates, temperatures, cure interruptions and applicable test results. Obtain approval before changing the method or ending the protection where the specification requires it.
A project permits a specified strength-based curing release after in-place concrete reaches 70% of 4,000 psi and other curing conditions are met. The authorized in-place result is 2,600 psi. What should the contractor do?
End curing because an in-place result of 2,600 psi is above 70% of 4,000 psi.
End curing as soon as one normal laboratory-cured acceptance cylinder tests above 2,800 psi.
Continue curing because the authorized in-place result is below the 2,800 psi threshold.
End curing immediately if the concrete contains Type III cement.
An approved membrane will cure a slab scheduled for a bonded coating. Which procedure addresses both curing and the later coating?
After finishing and bleeding are complete and the surface is ready, apply the approved membrane at the specified rate. Verify coating compatibility and remove incompatible residue as directed.
Apply the compound while free bleed water remains so the film mixes with the paste.
Apply any C309 compound and use its film as a permanent primer for the bonded coating.
Wait until the surface dries for a day, then apply the compound at twice the specified rate.
Under ACI 306R-16, what is the recommended minimum concrete temperature as placed and maintained for normalweight concrete in a section less than 12 inches thick, and at about what strength can the concrete resist a single early freeze?
40°F and 2,000 psi
45°F and 1,000 psi
50°F and 250 psi
55°F and 500 psi