26.1 Soil Testing, Types & Compaction
Key Takeaways
The 2015 Michigan Residential Code Table R401.4.1 presumptive bearing values run from 12,000 psf for crystalline bedrock to 1,500 psf for clay, silty clay, clayey silt and silt, with gravel at 3,000 psf and sand at 2,000 psf.
USCS distinguishes coarse and fine mineral soils at the No. 200 sieve. More than 50% retained is coarse-grained. At least 50% passing is fine-grained. Highly organic peat (Pt) is identified separately.
ASTM D698 Standard Proctor uses nominal effort of 12,400 ft-lbf/ft³. ASTM D1557 Modified Proctor uses 56,000 ft-lbf/ft³. Percent compaction is meaningful only against the designated method and material.
The project specifies required density, moisture range, lift thickness and test method. Use engineering direction for fill supporting foundations and verify each tested lift against its specified target.
Compacting a lift changes that lift. Verify that the underlying soil can carry the resulting loads and remove unsuitable material under the applicable design.
Why the Soil Under the Footing Decides the Job
A concrete footing does not hold a house up — it spreads the load over enough soil that the soil can carry it. Common soil-related risks include inadequate bearing capacity, settlement, frost heave, poor drainage, or volume change in expansive clay.
Bearing capacity in plain terms
Bearing capacity is the pressure a soil can support before it shears. Ultimate bearing capacity is the pressure at which the soil actually fails; allowable bearing pressure accounts for safety against shear failure and may be limited further by settlement. For one- and two-family dwellings the 2015 Michigan Residential Code (MRC) lets a designer skip a full geotechnical report and assume presumptive values from Table R401.4.1.
| Material — MRC Table R401.4.1 | Presumptive allowable bearing |
|---|---|
| Crystalline bedrock | 12,000 psf |
| Sedimentary and foliated rock | 4,000 psf |
| Sandy gravel, gravel (GW, GP) | 3,000 psf |
| Sand, silty sand, clayey sand, silty gravel, clayey gravel (SW, SP, SM, SC, GM, GC) | 2,000 psf |
| Clay, sandy clay, silty clay, clayey silt, silt, sandy silt (CL, ML, MH, CH) | 1,500 psf |
For a uniformly loaded continuous footing in this simplified example, bearing-area width per linear foot = total service line load on soil (plf) ÷ allowable bearing pressure (psf). The result addresses soil pressure. Check code minimums, geometry and other design requirements separately. A wall carrying 3,000 plf on 1,500 psf clay needs 3,000 / 1,500 = 2.0 ft, or 24 in. The same wall on gravel has a soil-pressure result of 1.0 ft, before checking any governing minimum or other design requirement. Footnote 2 to the table tells you what to do when the ground is worse than the table assumes: if the building official has reason to believe in-place soil is below 1,500 psf, the value must come from a soils investigation, not from the table. Section R401.4 separately lets the official order a soil test wherever accepted soil science indicates expansive, compressible or shifting soil.
Settlement is a separate problem from strength
A soil can be strong and still ruin a house. Immediate (elastic) settlement develops as load is applied, often during construction. Consolidation settlement in saturated clay continues for months or years as water is squeezed out of the voids. Check the design's acceptable total and differential settlement. Unequal movement can rack doors and crack finishes or foundations. Organic material, undocumented fill and stump holes require evaluation for settlement and strength.
Frost heave and Michigan's 42-inch rule
Frost heave needs three things at once: a frost-susceptible soil, a supply of water, and freezing that reaches the soil. Silt and fine sand pull water upward by capillary action and grow ice lenses that lift footings. For the exterior footings and foundation systems it covers, Michigan generally requires that they extend at least 42 inches below grade (MRC R403.1.4, as amended by R 408.30522), subject to modification by the building official based on site evidence. Where applicable, also comply with the frost-protection provisions in R403.1.4.1. In Table R405.1, GW, GP, SW and SP have low frost-heave potential, CL has medium potential, and ML and MH have high potential.
Expansive clay
Expansive soils change volume as moisture changes. A high plasticity index (PI = liquid limit minus plastic limit) marks a fat clay that swells when wet and shrinks when dry, lifting a slab's perimeter and leaving the middle low. Under the R401.4.2 alternative to a full geotechnical evaluation, remove compressible or shifting soil far enough to keep moisture stable in each active zone. That alternative also restricts reuse or in-place stabilization of that material within an active zone. Where engineering is required, select the foundation and drainage measures for the actual soil and site.
Sorting Soil: USCS Groups and the Tests That Name Them
The Unified Soil Classification System (ASTM D2487) is the vocabulary behind every soils report, and the MRC table uses its symbols. The first cut is at the No. 200 sieve (0.075 mm): if more than 50% of the dry sample is retained on that sieve the soil is coarse-grained (G gravel, S sand); if 50% or more passes, it falls on the fine-grained side. Plasticity and organic content then help distinguish fine-grained groups. Highly organic peat (Pt) is identified separately.
| Symbol | Name | Behavior that matters on site |
|---|---|---|
| GW, GP | Well-graded / poorly graded gravel | typically free draining; confirm density and stability |
| GM, GC | Silty / clayey gravel | drainage and strength depend on the fines |
| SW, SP | Well-graded / poorly graded sand | typically free draining; seepage and loose deposits can be unstable |
| SM, SC | Silty / clayey sand | fines influence drainage and frost susceptibility |
| ML | Inorganic silt | can pump when wet, with high potential for frost heave |
| CL | Lean clay | lower plasticity than fat clay, generally slow drainage |
| CH | Fat clay | high plasticity, high shrink-swell, very slow drainage |
| OL, OH, Pt | Organic silt and clay, peat | potentially highly compressible; evaluate or remove unsuitable material |
Field identification you can do with your hands
- Ribbon test: press a moist bolus between thumb and forefinger. A longer, more durable ribbon suggests a greater clay contribution. Use it with other observations.
- Dilatancy (shake) test: pat a wet sample in the palm. Silt sheens with water as you shake and goes dull when you squeeze it; clay stays dull and responds slowly.
- Dry strength: a dry clay crumb is hard to break, silt crumbles, sand falls apart.
- Roll test: thread formation at roughly 1/8 inch and the behavior as it is rerolled help assess the plasticity of the fines.
Field descriptions help screen for changed conditions. Formal classification and design use appropriate sampling and tests. A geotechnical report rests on sieve and hydrometer analysis for gradation, Atterberg limits (ASTM D4318) for liquid limit, plastic limit and PI, and oven moisture content. The Atterberg tests run only on the fraction passing the No. 40 sieve, so the reported limits describe the tested fraction. In a predominantly gravel sample, the fines help determine the gravel's subgroup.
Moisture, Density and Compaction
Compaction primarily reduces air voids as particles rearrange. For a given soil and a given compactive effort, dry density climbs as water is added (thin films lubricate the particles), peaks at the optimum moisture content (OMC), then falls on the wet side of the curve, where additional water limits the attainable dry density for that effort. The peak is the maximum dry density (MDD). Plotted against moisture, that relationship is the Proctor curve, and every field density test is judged against it.
| Standard Proctor | Modified Proctor | |
|---|---|---|
| ASTM standard | D698 | D1557 |
| Rammer | 5.5 lb | 10 lb |
| Drop | 12 in | 18 in |
| Layers × blows for Method A | 3 × 25 | 5 × 25 |
| Compactive energy | 12,400 ft-lbf per cu ft | 56,000 ft-lbf per cu ft |
| Reference selection | Use when specified for the material | Use when specified for the material |
Modified energy is roughly 4.5 times standard energy, and often yields a higher MDD and lower OMC for the same soil. Check the actual test curves. The practical consequence: The acceptance target uses the specified reference curve. Method C uses a different mold and blow count from Method A.
Applying a project specification
R401.2 requires fill supporting foundations to be designed, installed and tested according to accepted engineering practice. Follow the project's requirements for material, loose lift thickness, moisture, and density. A specification might require 95% of Standard Proctor MDD in an approved lift thickness. Match the compactor to the soil and verify density through the lift before placing the next one.
- Sheepsfoot roller: cohesive clay and silt; kneading action; larger fills.
- Smooth vibratory drum: granular base and gravel.
- Plate compactor: footing trenches, slab subgrade, small areas.
- Jumping jack (rammer): trench backfill, utility bedding, tight corners.
Field tests
| Test | Standard | How it works | Limits |
|---|---|---|---|
| Sand cone | ASTM D1556 | calibrated sand fills a dug hole to measure its volume; sample mass gives density | not for soft, saturated or very coarse soil |
| Nuclear gauge | ASTM D6938 | gamma attenuation for wet density, neutron thermalization for water | uses direct transmission or backscatter as applicable; follow licensing and operator training requirements |
| Drive cylinder | ASTM D2937 | fixed-volume cylinder driven into the soil | requires an intact sample and suitable soil; appreciable gravel can invalidate the result |
| Oven moisture | ASTM D2216 | gravimetric water content | the reference for comparing to OMC |
A validated one-point comparison uses a reference curve family for similar soils where the project permits it. Verify the reference again if the material changes.
Worked example
The lab reports MDD = 120.0 pcf at OMC = 11.5% for the borrow. The gauge reads 114.0 pcf dry density at 12.1% moisture. Percent compaction = 114.0 / 120.0 = 95.0%, which meets the density criterion if the project requires 95% of Standard Proctor. The sample is 0.6 percentage points above OMC. Compare that result separately with the specified moisture range. Compare the identical gauge reading to a Modified Proctor MDD of 126 pcf and the same fill is only 90.5% — a failure. Same soil, same roller, different verdict.
Exam traps
- Check the soil below the fill. Densifying a lift changes that lift. Evaluate the native clay below it separately. Weak native soil calls for over-excavation and replacement, a wider footing, or an engineered design.
- Strip organic topsoil; never bury it. Organic material under a slab or footing decays and leaves voids.
- Do not place fill on frozen ground or use frozen fill. Ice lenses melt and leave the lift loose.
- Percent compaction is density, not moisture. A sample can sit exactly at OMC and still fail density.
- Check which Proctor governs. The same percentage can imply different target dry densities when the test methods have different maxima.
Which ASTM designation is the Standard Proctor laboratory compaction test?
ASTM D1557
ASTM D698
ASTM D1556
ASTM D4318
In 2015 MRC Table R405.1, which USCS group is rated high for frost-heave potential?
GW — well-graded gravel
SP — poorly graded sand
CL — lean clay
ML — inorganic silt
A nuclear gauge reads 114.0 pcf dry density on a lift, and the lab report for that borrow gives a maximum dry density of 120.0 pcf with the Standard Proctor method. What is the percent compaction?
95%
90%
105%
89%