56.2 Smoke & Carbon Monoxide Detectors
Key Takeaways
Michigan Rule 546 places smoke alarms in each sleeping room or its immediate vicinity and on additional stories, including basements and habitable attics. Check its separate provisions for qualifying pre-November 6, 1974 buildings.
Where commercially powered building wiring serves the dwelling, the ordinary new-construction smoke alarm uses permanent wiring with battery backup. Required smoke alarms interconnect when there is more than one, with an exception for existing areas.
For new dwellings, R315.2.1 is triggered by a fuel-fired appliance or an attached garage with a communicating opening. Michigan Rule 520 addresses permit-level work in existing dwellings with attached garages or fuel-fired appliances.
Coordinate the placement and approved product with the code and the Overbeck law. The law identifies zones near bedrooms and adjacent to an attached garage or fuel-burning appliances.
Since October 2, 2026, Michigan’s smoke alarm sales law requires a qualifying ten-year power source for devices subject to the act. The law has separate exceptions for specified building-powered, system-connected and wireless devices.
Place smoke alarms under Michigan Rule 546
Use R314 as amended by R 408.30546, Rule 546. For ordinary new dwellings, amended R314.3 calls for an alarm in each sleeping room or in its immediate vicinity, and on each additional story, including the basement and habitable attic. Crawl spaces and uninhabitable attics are excluded. An upper split level can cover the adjacent lower level if there is no intervening door and the lower level is less than one full story below it. Check actual coverage for each room. A hallway remote from a second bedroom wing cannot be assumed to cover that wing.
Under amended R314.2.2, work requiring a permit or the creation of one or more sleeping rooms in an existing dwelling triggers new-dwelling smoke alarm locations. The listed exemptions include exterior-surface work such as replacing roof covering, siding, windows or doors, adding a porch or deck, and work installing, altering or repairing electrical, plumbing or mechanical systems. Evaluate the scope of the project before using an exemption.
There is a separate rule for a building constructed before November 6, 1974, with no permit-triggering alteration, addition or change in occupancy. R314.3.2 calls for alarms in each sleeping room and on every floor including the basement, with its stated split-level provision. R314.3.3 sets equipment, audibility, owner maintenance and rental-occupant testing duties for that setting. It includes an exception for installations approved under the requirements in effect at the time.
Coordinate power, interconnection and model instructions
Under R314.6, when commercial power serves the building wiring, an ordinary new-construction smoke alarm takes primary power from permanent building wiring and uses battery backup. The circuit may only be disconnected by the required overcurrent protection. Battery operation is allowed in buildings without commercial power and for alarms installed under the R314.2.2 alteration provision. Under Michigan’s amended R314.4, more than one required smoke alarm must operate together. Listed wireless interconnection is an option if all sound together. Existing areas are exempt from the interconnection requirement.
Use UL 217 for a smoke alarm and UL 217 plus UL 2034 for a combination smoke and CO alarm. A household fire alarm system is an alternative when it meets R314.7, including the NFPA 72 requirements and UL 268 for its smoke detectors. The unit or system must also fit the approved locations.
R314.3.1 addresses nuisance alarms near permanently installed cooking appliances. Measure horizontally and apply the applicable minimum, unless it would prevent placement required by R314.3.
| Smoke sensing type | R314.3.1 horizontal separation |
|---|---|
| Ionization | 20 feet |
| Ionization with an alarm-silencing switch | 10 feet |
| Photoelectric | 6 feet |
Select and position the listed model according to its instructions and applicable NFPA 72 provisions. Compare the instructions for ceiling or wall mounting, ceiling geometry, air movement and bathroom proximity before placing a box. A product-specific dimension is not a statewide rule for all alarms.
Distinguish the smoke alarm sales law
2024 PA 98, MCL 29.533, took effect April 2, 2025. The device standards apply to covered smoke alarms distributed, sold, offered for sale or imported beginning October 2, 2026, 18 months later. A covered device must provide at least 10 years of power from a nonremovable, nonreplaceable battery or another new-technology power source. Statutory exceptions include devices powered from the building or electronically connected to a centrally monitored or supervised system, qualifying ancillary components, low-power radio-frequency signals and specified wireless network notification devices. The maximum civil fine is $500. Apply R314 separately when selecting the alarm for a particular building.
Determine what triggers carbon monoxide protection
Carbon monoxide is a poisonous gas that people cannot see, taste or smell. Fuel-burning equipment and vehicle exhaust from an attached garage can create an exposure. The alarm’s job is to warn occupants before they rely on symptoms to recognize it.
- New construction: Under R315.2.1, either a fuel-fired appliance or an attached garage with an opening communicating with the dwelling triggers the code requirement. An all-electric house can still have the garage trigger.
- Existing construction: Retained R315.2.2 addresses permit-level alterations, repairs or additions, and newly created sleeping rooms, with listed exterior-surface and plumbing or mechanical exceptions for that provision. Michigan Rule 520, which amends R315.3, separately requires CO alarms where work requiring a building permit occurs in an existing dwelling that has an attached garage or contains fuel-fired appliances. Check the Michigan amendment before relying on an exception in the model text.
For example, the building-permit trigger applies when remodeling an existing kitchen in a home with an attached garage. Evaluate CO protection even if the new range is electric. Use the actual room and garage layout in the approved alarm plan.
Locate and specify the CO device
Michigan’s Overbeck law, MCL 125.1504f, authorizes the director to provide for approved, operational devices in the stated new construction, permitted renovation and bedroom-creation settings. It identifies the vicinity of the bedrooms, areas within the dwelling adjacent to an attached garage, and areas adjacent to fuel-burning appliances. One device can serve nearby bedrooms when it detects CO near all of them. The law makes the adopted IRC requirements applicable once effective. Verify the approved locations, the actual sleeping-area layout and manufacturer instructions before rough-in. Michigan local guidance places alarms outside and near separate bedroom areas. A fixed distance such as 20 feet is not a statewide code allowance, and there is no general CO requirement stated as one device on every story.
Under R315.5, primary building power with battery backup is the ordinary new-construction approach where commercial power is available. The stated battery-only exceptions are buildings without commercial power and installations under R315.2.2. Use the code’s arrangements for the job rather than reading the statute’s device-power list as a separate exemption.
| Device | Applicable listing or system requirement |
|---|---|
| Standalone CO alarm | UL 2034 |
| Combination smoke and CO alarm | UL 217 and UL 2034 |
| Household CO detection system | R315.6 and NFPA 720, with UL 2075 for CO detectors |
| Combination detector on a household fire or CO system | UL 268 and UL 2075 where permitted by R314.7 or R315.6 |
The Overbeck law defines an approved CO device by its UL 2034 or UL 2075 listing and installation to manufacturer instructions. Its limited liability provision for an Article 24 licensee concerns operation, maintenance or effectiveness of the device when the licensee satisfies the stated compliance and installation conditions.
Inspect and test the installation
Before covering wiring or closing an inspection stage, obtain approval under amended R109.4. At final, check required room and story coverage, model listings, permanent power and backup, and actual interconnection. Test each unit using its instructions, and confirm other required interconnected alarms sound. Teach occupants to identify different signals. For example, Kidde describes repeating three beeps for smoke and repeating four beeps for CO. Compare the actual device instructions for those signals and the low-battery and end-of-life indications.
Record the device locations and model dates for handoff. The U.S. Fire Administration advises monthly smoke-alarm tests, replacement of typical replaceable batteries at least annually, and smoke-alarm replacement at ten years. Follow the manufacturer’s test, cleaning and end-of-life instructions for CO and combination alarms. Keep required devices in service. Under amended R110.1, obtain the required certificate of occupancy before using or occupying the dwelling.
Under 2015 Michigan Residential Code R314.3 as amended by Rule 546, what smoke-alarm coverage is required for an ordinary new dwelling?
Only in a bedroom hallway and the basement
In each sleeping room and the attached garage
In each sleeping room or its immediate vicinity, and on each additional story including basements and habitable attics
On each story and at the top of every stair, with no sleeping-room coverage requirement
Which condition triggers carbon monoxide alarms for a new Michigan dwelling under R315.2.1?
A dwelling with a fuel-fired appliance or an attached garage that communicates with the dwelling
Only a dwelling heated by a natural gas furnace
Only a dwelling with an attached garage and no fuel-fired appliances
Every new dwelling, regardless of appliances or garage
For a smoke alarm subject to Michigan’s Smoke Alarm Battery Standard Act and offered for sale on or after October 2, 2026, what power source meets the act?
A replaceable 9-volt battery plus a low-battery chirp
A battery that lasts at least one year and is replaceable by the homeowner
Power for at least 10 years from a nonremovable, nonreplaceable battery or another new-technology source
A Wi-Fi connection that notifies the local fire department