40.3 Michigan Barrier-Free Ramps
Key Takeaways
Michigan barrier-free design comes from 1966 PA 1, MCL 125.1351 to 125.1356, and applies to public facilities and facilities used by the public; a privately owned 1 or 2 family dwelling is expressly excluded from that definition.
The 2021 Michigan Building Code uses Chapter 11 for scoping and ICC A117.1-2017 for technical criteria, with Michigan amendments. Check applicable federal requirements separately.
For a typical new accessible ramp, limit a run to 1:12 and 30 inches of rise and provide at least 36 inches of clear width. Landings are at least 60 inches long, and at least 60 by 60 inches clear where the ramp changes direction.
A typical accessible ramp run with more than 6 inches of rise needs handrails at 34–38 inches on both sides. Check handrail extensions, edge protection and exceptions against the applicable standard.
Michigan accessibility is enforced through the state construction code at permit and certificate of occupancy, while the federal ADA is a civil rights law enforced independently, so a project can satisfy one and still violate the other.
Start a ramp layout by identifying which accessibility or residential egress rules apply. Then measure the elevation change and the clear space at doors and turns.
The legal basis
1966 PA 1 governs Michigan public facilities and facilities used by the public. A retail store open to customers is a facility used by the public. Government ownership, a qualifying lease or public funding can make a building a public facility under MCL 125.1351.
Both definitions exclude privately owned one- and two-family dwellings from their housing scope. A ramp at a purely private home is generally evaluated under the Michigan Residential Code. Assess apartments, common areas and public sales spaces for their actual uses.
| Project | Michigan barrier-free review | Reason |
|---|---|---|
| New privately owned 1 or 2 family dwelling | Generally no | Excluded from facility used by the public |
| Apartment building common areas and covered units | Yes | Housing other than a privately owned 1 or 2 family dwelling |
| Retail, office, restaurant | Yes | Facility used by the public |
| Municipal, school or state building | Yes | Public facility |
| Alteration of less than 50 percent of floor area usable by the public or employees | Affected area plus a continuous route to and from the affected area, including the nearest entrance | MCL 125.1352(2)(a) |
| Alteration of 50 percent or more of floor area | Entire facility | MCL 125.1352(2)(b) |
The 2021 Michigan Building Code applies Chapter 11 where appropriate. Michigan-amended §1102.1 (R 408.30427) references 1966 PA 1, the building code and ICC A117.1-2017 except sections 611 and 707. Apply the 2010 ADA Standards separately where federal requirements apply.
Michigan rules versus the ADA
Michigan reviews applicable barrier-free work through construction code enforcement. Federal ADA obligations apply independently and can include existing facilities. Check each applicable rule against its scope, dimensions and exceptions.
Ramp geometry
On an accessible route, a segment with a running slope steeper than 1:20 is a ramp. A gentler walking surface still needs accessible width, cross slope and other applicable features.
| Element | Barrier-free requirement |
|---|---|
| Maximum running slope in new work | 1:12 (8.33 percent) |
| Maximum rise per run | 30 inches before a landing |
| Minimum clear width | 36 inches, between handrails where installed |
| Maximum cross slope of a run | 1:48 |
| Landings | At the top and bottom of each run and between runs where direction changes |
| Landing size | 60 inches clear length; width at least the widest run leading to it. At turns, at least 60 by 60 inches clear |
| Landing slope | No steeper than 1:48 in any direction |
| Handrails on typical runs | Both sides where the rise exceeds 6 inches; 34 to 38 inches above the ramp surface |
| Handrail extensions | 12 inches beyond the top and bottom of each run |
| Edge protection | Provide along runs and landings, subject to the specific §405.9 exceptions |
| Surface | Firm, stable and slip resistant; landings must not collect water |
| Changes in level | No steps or level changes within ramp runs or landings |
Measure the slope of each run independently of its landings. Verify clear landing dimensions and required doorway maneuvering clearance. Section 405.7 permits certain overlaps. Existing facilities with space limitations can use the restricted slope and rise combinations in Table 405.2 when the exception applies.
Worked designs
For a 24-inch rise, the 1:12 maximum slope requires at least 288 inches (24 feet) of horizontal run. The rise is below the 30-inch limit per run. Two 60-inch landings add 10 feet, so a straight layout takes at least 34 feet before any extra door or rail clearances. This run needs handrails because its rise exceeds 6 inches.
For a 36-inch rise, two runs of 18 inches each take 18 feet per run at 1:12. A straight layout uses 36 feet of run, a 5-foot intermediate landing and two 5-foot end landings, or 51 feet total before extra door or rail clearances. A switchback changes the footprint and needs at least 60 by 60 inches clear at the change of direction.
At 1:20, a 24-inch rise takes 40 feet of horizontal travel. A slope of 1:16 or 1:18 is steeper than 1:20 and falls under the ramp requirements on an accessible route.
Exterior ramps in Michigan
For exterior footings in Michigan Residential Code scope, amended R403.1.4 generally requires 42 inches below actual grade in addition to applicable frost provisions. The building official can modify depth based on listed site conditions. For work governed by the Michigan Building Code, use its foundation and frost provisions.
Choose a firm, stable, slip-resistant surface. Drain wet landings without exceeding the 1:48 landing slope limit. Use a graspable handrail under the applicable standard. For example, ICC A117.1 permits a round grip from 1¼ to 2 inches in diameter.
Residential ramps are a different rule
Under 2015 MRC R311.8, a ramp serving the required egress door is limited to 1:12, with an exception up to 1:8 where site constraints make compliance technically infeasible. Other residential ramps may be at most 1:8. Provide landings at the ends, where doors open onto a ramp and where it changes direction, with at least 36 inches perpendicular to the slope. A ramp steeper than 1:12 needs at least one handrail, 34–38 inches above the finished slope, meeting the residential grip and continuity provisions.
What the inspector measures
- Check running slope, cross slope and landing slope separately.
- Measure the narrowest clear width between handrails.
- Verify clear landing dimensions and required door maneuvering clearance.
- Check required handrails for height, grip, continuity, extensions and returns.
- Verify edge protection where required, transitions and drainage.
For a new accessible ramp under ICC A117.1-2017, what are the usual maximum running slope and rise per run?
1:8 slope with a 12 inch maximum rise
1:10 slope with a 24 inch maximum rise
1:12 slope with a 30 inch maximum rise before a landing
1:16 slope with a 48 inch maximum rise before a landing
Which project is excluded from Michigan barrier-free design requirements under 1966 PA 1?
A 40 unit apartment building with a shared laundry room
A restaurant with a new accessible entrance
A township hall built with state grant funds
A privately owned single-family dwelling occupied by its owner