30.1 Foundation Wall Types: Concrete, Masonry & ICF

Key Takeaways

  • MRC R404.1.1 requires an engineered design where a foundation wall is subject to hydrostatic pressure from ground water, or where it supports more than 48 inches of unbalanced backfill without permanent lateral support at the top or bottom.

  • Unbalanced backfill is measured from exterior finish grade down to the lower of the top of the footing or the interior finish ground level; where an interior slab-on-grade bears against the wall, it may be measured to the top of that slab.

  • At 8 ft of unsupported height and 8 ft of unbalanced backfill in SC soil, the applicable 8-inch flat concrete wall table R404.1.2(3) lists No. 6 vertical bars at a maximum of 26 inches on center under its stated assumptions.

  • Under R404.1.3.3.4 and .5, stay-in-place foundation forms require slump greater than 6 inches and internal vibration except for approved qualifying self-consolidating concrete. Removable forms have a 6-inch maximum with a separate approval exception.

  • Under R606.3.5, grout lifts are limited to 8 ft. If the total pour exceeds 8 ft, use lifts no higher than 64 inches and provide special inspection. Reinforced cells must be filled solidly.

Last updated: November 2026

Three ways to build a foundation wall

A foundation wall can transfer building loads and resist lateral loads from retained soil. The 2015 Michigan Residential Code provides prescriptive options for concrete, concrete masonry and qualifying ICF walls within its stated limits. Permanent wood foundation assemblies use the design paths covered in Section 30.2.

Where the tables stop

MRC Section R404.1.1 is the gate. A concrete or masonry foundation wall must be designed in accordance with accepted engineering practice when either condition exists:

  1. The wall is subject to hydrostatic pressure from ground water, or
  2. The wall supports more than 48 inches of unbalanced backfill and does not have permanent lateral support at the top or bottom.

Neither trigger is about wall thickness. Check whether groundwater exerts pressure on the wall and how the wall is supported permanently. The prescriptive concrete wall tables assume lateral support at the top and bottom. Construction bracing serves a separate purpose while the permanent assembly is incomplete.

Unbalanced backfill is the measurement that drives every table. The code defines it as the difference in height between exterior finish grade and the lower of (a) the top of the concrete footing or (b) interior finish ground level. Where an interior slab-on-grade is in contact with the inside face of the wall, you may measure down to the top of that slab instead. That allowance matters on a full basement: if exterior grade is 9 feet above the footing top and the interior slab in contact with the wall is 2 feet above it, the permitted slab reference gives 7 feet of unbalanced fill.

Soil class sets the lateral load

Use the soil classification from the approved project basis. This grouping appears in the selected reinforced masonry and flat concrete basement wall tables. Check the actual table’s classes, footnotes and applicable design limits:

Soil groupDesign lateral load
GW, GP, SW, SP — gravels and clean sands30 psf per foot of depth
GM, GC, SM, SM-SC, ML — silty or clayey gravel and sand groups and low-plasticity silt45 psf per foot of depth
SC, ML-CL, inorganic CL — clayey sand and listed fine-grained soils60 psf per foot of depth

The tabulated soil loads increase per foot of depth and assume moist soil without hydrostatic pressure. Some tables list different classes. For example, the plain masonry table R404.1.1(1) includes MH, which the illustrated flat concrete table omits. Follow each table’s own notes. The illustrated flat concrete table prohibits both unlisted soil classes and interpolation.

Poured concrete walls

Concrete foundation walls are selected and built under MRC Section R404.1.3. Check the strength, slump and consolidation specified for each wall:

  • Strength (Table R402.2): concrete not exposed to weather needs 2,500 psi at 28 days; basement walls, foundation walls and other vertical concrete exposed to weather need 3,000 psi where weathering is severe, which is all of Michigan. The specified total air content for that exposed vertical concrete is 5 to 7 percent. Check the freeze-thaw-during-construction note for otherwise unexposed concrete and the applicable R404.1.3.3.1 seismic minimum.
  • Slump (R404.1.3.3.4): stay-in-place concrete must exceed 6 inches. Removable-form concrete has a 6-inch maximum unless an approved segregation-resistant mix meets the form manufacturer’s recommendations.
  • Consolidation (R404.1.3.3.5): stay-in-place forms require internal vibration, unless an approved self-consolidating mix with a slump of at least 8 inches is specified for placement without vibration.

Wall thickness follows Table R608.3, which lists flat walls at 4, 6, 8 and 10 inches nominal. As-built flat wall thickness may be no more than 1/2 inch under or 1/4 inch over nominal. A concrete foundation wall also may not be thinner than the wall in the story above it (R404.1.5.2), and where a wall is reduced for a brick ledge, apply the geometry and reinforcement rules and limited exception in R404.1.5.2.

The reinforcement the tables actually require

Vertical steel comes from Tables R404.1.2(2) through (8), organized by nominal thickness, maximum unsupported wall height, maximum unbalanced backfill and soil class. For the 8-inch flat wall table R404.1.2(3), the following are listed vertical reinforcement values. Use the table assumptions, including centered Grade 60 bars, concrete of at least 2,500 psi and the applicable permanent support. Other code provisions can require greater strength or added reinforcement:

Wall heightUnbalanced backfill30 psf/ft soil45 psf/ft soil60 psf/ft soil
8 feet6 feetnone requirednone required#6 at 37 inches
8 feet7 feetnone required#6 at 36 inches#6 at 35 inches
8 feet8 feet#6 at 41 inches#6 at 35 inches#6 at 26 inches
9 feet9 feet#6 at 35 inches#6 at 25 inches#6 at 18 inches
10 feet10 feet#6 at 27 inches#6 at 17 inches#6 at 13 inches

In this table, NR means no vertical reinforcement from the table. Check independent requirements, including walls supporting above-grade concrete and the applicable seismic provisions. Horizontal steel is simpler: under Table R404.1.2(1), a wall up to 8 feet high gets one No. 4 bar within 12 inches of the top and one No. 4 near mid-height; taller walls get the top bar plus bars near the third points. Use the spacing cap for the specific row. R404.1.3.3.7.6 also limits bar spacing to a range from half the wall thickness through 48 inches for its covered requirements.

Minimum cover under R404.1.3.3.7.4 depends on the placement: 3 inches where concrete is cast against earth, 1-1/2 inches for No. 5 and smaller bars and 2 inches for No. 6 and larger in removable forms exposed to earth or weather, and 3/4 inch in stay-in-place forms or where the concrete will not be exposed. Vertical bars taken from Tables R404.1.2(2) through (7) are centered in the wall; Table R404.1.2(8) uses different locations with up to 1-1/4 inches of cover from the inside face. Where a wall opening interrupts required vertical reinforcement, R404.1.3.3.7.3 requires additional bars of the same size within 12 inches of each side.

Curing and bracing before backfill

Check R404.1.7 and the table notes before backfilling. The wall must have sufficient strength and be anchored to the floor above or sufficiently braced. The bracing exception applies below 4 feet of unbalanced backfill. At 4 feet or more, provide the required top and bottom support before backfilling. Coordinate temporary bracing and the permanent support requirements with the approved design.

Concrete masonry (CMU) walls

A standard block is called 8 by 8 by 16 inches, but that is its nominal size. With a 3/8-inch mortar joint the actual unit measures about 7-5/8 by 7-5/8 by 15-5/8 inches, which is why three courses of 8-inch block rise exactly 24 inches and an 8-foot wall is 12 courses. Use the nominal module to count courses and the actual unit size for details such as bar clearances.

Masonry foundation walls follow Table R404.1.1(1) for plain walls and Tables R404.1.1(2), (3) and (4) for reinforced 8-, 10- and 12-inch walls. Mortar must be Type M or Type S, and units are laid in running bond. The reinforced tables are limited by the depth of steel: d, the distance from the soil-side face to the center of the vertical bar, must be at least 5 inches in an 8-inch wall, 6.75 inches in a 10-inch wall and 8.75 inches in a 12-inch wall. The illustrated reinforced masonry table uses Grade 60 minimum bars. Follow its specific alternative bar rules, spacing and mortar and grout requirements.

For a qualifying 8-inch reinforced masonry wall with 8 ft of unsupported height, 8 ft of unbalanced backfill and d of at least 5 inches, Table R404.1.1(2) lists: #5 at 48 inches in 30 psf/ft gravel, #6 at 48 inches in 45 psf/ft silty soil, and #6 at 32 inches in 60 psf/ft clay. For the same nominal block size, the higher lateral design loads require larger bars or closer spacing.

Grouting hollow cores

Grout is neither concrete nor mortar. Under R606.2.11 it must comply with ASTM C476 or the code's proportion table, and Type M or Type S mortar with enough water added to reach pouring consistency may be used as grout. Placement rules in R606.3.5.1 are strict, because grout that bridges a core leaves an unreinforced wall:

  • Grout must be placed before initial set and within 1-1/2 hours of adding water, and consolidated by puddling or mechanical vibration, then reconsolidated after excess moisture is absorbed while it remains plastic.
  • Grout is poured in lifts of 8 feet maximum. Where a total pour exceeds 8 feet, lifts may not exceed 64 inches and special inspection is required during grouting.
  • If work stops for an hour or longer, all tiers stop at the same elevation with grout 1 inch below the top, forming a construction joint.
  • Where the building official requires cleanouts for a pour deeper than 64 inches, they go in the bottom course; in solid grouted masonry they are spaced not more than 32 inches on center.
  • Cells containing reinforcement must be filled solidly, and vertical bars are held at top, bottom and at intervals no greater than 200 bar diameters (R606.3.5.3).

Minimum grout space also matters. Table R606.3.5.1 requires, for example, at the 24-ft maximum pour row, 3-by-3-inch hollow-unit cells for fine grout and 3-by-4-inch cells for coarse grout, subject to the table notes about clear space and reinforcement. Pour height and lift height are separate checks. Bars are placed before the pour, not dropped in afterward, and anchor bolts must reach 7 inches into grouted cells (Section 30.3).

Insulating concrete forms (ICF)

ICF walls are stay-in-place expanded polystyrene (EPS) forms filled with reinforced concrete. The foam remains as insulation, plastic or metal webs hold the rebar and receive finishes, and the finished wall is a sandwich of foam and concrete. The code treats them as concrete foundation walls with extra protection requirements:

  • Form standard: flat ICF wall system forms must conform to ASTM E2634 (R404.1.3.3.6.1).
  • Core geometry: In Table R608.3, the 6-inch waffle-grid row lists an 8-inch width and 5.5-inch thickness for the elliptical core, maximum spacing of 12 inches for vertical cores and 16 inches for horizontal cores, and webs at least 2 inches thick. The 6-inch screen-grid row lists a 6.25-inch diameter circular core and 12-inch spacing limits both ways. The footnotes give separate criteria for alternate core shapes.
  • Mix and consolidation: slump must exceed 6 inches. Provide internal vibration unless the approved self-consolidating mix is designed to be placed without it and has slump of at least 8 inches under R404.1.3.3.5.
  • Protection of foam: interior foam must be covered as required by R316, using the required thermal barrier or a permitted alternative; exterior foam needs an approved wall covering that shields it from sunlight and physical damage.
  • Termites: the code restricts foam below grade on foundation walls only where termite infestation probability is "very heavy." Michigan’s amended Table R301.2(1) refers to the termite probability map and local damage history. Apply R318.4 and its exceptions where the applicable infestation category is very heavy.

Pour sequencing is a manufacturer's instruction, not a code table. ICF walls are filled in lifts around the perimeter with bracing in place, and the forms and ties must be capable of resisting the fluid pressure of fresh concrete (R404.1.3.3.6). Follow the form maker's written lift height and pour rate, and use the approved consolidation method.

Comparing the three systems

CriterionPoured concreteCMUICF
Typical thickness8 or 10 inches8, 10 or 12 inches nominal6 to 12 inch concrete core plus foam
Site speedfast, but needs forms and a pump or chuteslow and modular; good on tight lotsfast erection, careful pour
Insulationnone built in — added per energy codenone built incontinuous foam plus thermal mass
Moisture riskcold joints and tie holes need patchingdetail mortar joints and parging or approved direct-applied treatmentfoam hides leaks, so penetrations must be detailed
Finish attachmentfurring or direct-applied systemsfurring on blockscrews into webs
Reinforcement driverheight, backfill, soil classheight, backfill, soil class, d distancecore size plus engineering

For each wall, check the applicable table or design for height, soil conditions and support. Verify required drainage, dampproofing or waterproofing and sill anchorage separately.

Test Your Knowledge

A concrete basement wall will retain 5 feet of unbalanced backfill and has no permanent lateral support at either the top or the bottom. Under MRC R404.1.1, what is required?

A

The wall must be at least 10 inches thick

B

The wall must be designed in accordance with accepted engineering practice

C

The concrete must be 3,000 psi with 5 to 7 percent air

D

The exterior must be waterproofed rather than dampproofed

Test Your Knowledge

An 8-inch flat concrete basement wall is 8 feet high and retains 8 feet of unbalanced backfill in soil classified as SC (60 psf per foot of depth). Assume all conditions for Table R404.1.2(3) are met. What vertical bar size and maximum spacing does that table list?

A

No vertical reinforcement is required

B

#5 bars at 48 inches on center

C

#6 bars at 41 inches on center

D

#6 bars at 26 inches on center

Test Your Knowledge

What are the default slump and consolidation rules for a foundation wall placed in stay-in-place insulating concrete forms under R404.1.3.3.4 and .5? Assume no approved self-consolidating exception.

A

Slump must exceed 6 inches, and the concrete must be internally vibrated

B

Slump must not exceed 6 inches, matching removable-form work

C

Slump must be exactly 4 inches with no vibration

D

Slump is unlimited and vibration is prohibited

Sections you finish are checked off in the contents.