51.1 Fenestration Energy Requirements

Key Takeaways

  • The 2015 Michigan Residential Code’s prescriptive Table N1102.1.1 limits fenestration other than skylights to U-0.32 and skylights to U-0.55 in zones 5A, 6A and 7.

  • Under the component path, up to 15 square feet of glazed fenestration per dwelling unit may be exempt. The code also permits area-weighted compliance and sets separate caps for whole-envelope tradeoffs.

  • U-factor describes heat transfer through the whole product. At equal area and temperature difference, reducing U-factor from 1.00 to 0.30 reduces heat loss through the unit by 70 percent.

  • Read the NFRC rating for the specified configuration. Michigan uses certified U-factors or the applicable defaults and has separate product air leakage limits.

  • Perimeter sealing and draining the opening serve different functions. Michigan’s prescriptive blower-door limit is 4 air changes per hour at 50 pascals.

Last updated: November 2026

Use the 2015 Michigan Residential Code (MRC) for the residential envelope covered by the exam. Rule 500 adopts the referenced model provisions with Michigan exceptions, and Rules 547c and 547d amend the energy chapter. Identify the compliance path before comparing a window schedule to its limits.

Michigan climate zones and the prescriptive limits

Consult the county list in Table N1101.10. Zone 5A includes Wayne County, Zone 6A includes Marquette County and Zone 7 includes Houghton County. The ten Zone 7 counties are Baraga, Chippewa, Gogebic, Houghton, Iron, Keweenaw, Luce, Mackinac, Ontonagon and Schoolcraft.

ComponentMaximum U-factor under Table N1102.1.1 in Zones 5A, 6A and 7
Fenestration other than skylights0.32
Skylights0.55

A Houghton project and a Detroit project use the same table values for fenestration, even though their ceiling and basement-wall insulation requirements can differ. For the component path, amended N1102.3.3 allows up to 15 ft² of glazed fenestration per dwelling unit to be exempt from the table’s U-factor requirement. The glazed exemption is unavailable with the U-factor alternative or total UA alternative. Under N1102.3.4, one side-hinged opaque door assembly of up to 24 ft² can be exempt on the prescriptive component path.

Under N1102.3.1, an area-weighted average can satisfy the applicable U-factor requirement. For example, 20 ft² of windows at U-0.38 and 40 ft² at U-0.29 give (20 × 0.38 + 40 × 0.29) ÷ 60 = 0.32. An arithmetic mean would give 0.335 and would ignore the difference in area. N1102.3.5 has a separate allowance for qualifying thermally isolated sunrooms enclosing conditioned space. Its limits are 0.45 for fenestration and 0.70 for skylights. New glazing separating such a sunroom from conditioned space must meet the envelope requirements.

An alternative compliance calculation can account for tradeoffs. N1102.5 limits the area-weighted average U-factor for non-skylight fenestration to 0.48 in Zone 5 and 0.40 in Zones 6 and 7 when tradeoffs are used. The skylight average cap is 0.75 in these zones. These caps constrain an alternative design. The overall design must also meet the requirements of the selected path.

Conductive heat loss through a window

A U-factor measures whole-product heat transfer, including the frame and glass system, in Btu per hour per square foot per degree Fahrenheit. A lower U-factor gives lower heat flow at the same area and temperature difference. Use the rated window area and hold air leakage and solar gain outside this calculation.

For a 3 ft × 4 ft window, suppose the indoor temperature is 70°F and the outdoor temperature is 20°F. The temperature difference is 50°F. Multiply the U-factor by 12 ft² × 50°F.

Example unitU-factorHeat lossReduction from baseline
Older single-glazed unit, assumed1.00600 Btu/hrBaseline
Unit at Michigan’s non-skylight prescriptive limit0.32192 Btu/hr68%
More insulating unit0.30180 Btu/hr70%

The last unit loses 420 Btu/hr less than the first under these conditions. Divide 420 by 600 to find the 70 percent reduction for the window. The house also loses heat through other surfaces and by air exchange.

Test Your Knowledge

What U-factor limit does 2015 MRC Table N1102.1.1 list for fenestration other than skylights in Houghton County under the ordinary prescriptive component approach?

A

0.35

B

0.40

C

0.32

D

0.55

Read the product rating

Michigan Rule 547c requires U-factors determined under NFRC 100 by an accredited independent laboratory and labeled and certified by the manufacturer. It also recognizes independent NFRC-certified laboratory simulations or approval under MCL 125.1521. If a product lacks a labeled U-factor, apply the applicable default from Table N1101.12.3(1) or (2).

RatingWhat to read
U-factorRate of whole-product heat transfer per unit area and temperature difference. A lower value reduces heat flow.
Solar heat gain coefficient (SHGC)Fraction of incident solar energy admitted directly or as heat flowing inward after absorption. A lower value limits solar gain.
Visible transmittance (VT)Fraction of visible light admitted. A higher value admits more daylight under equivalent conditions.
Air leakage (AL)Airflow per unit area under the rating test conditions. A lower value means less measured airflow.
Condensation rating, when providedRelative resistance to interior surface condensation under the rating conditions.

Michigan excluded model N1102.3.2 and its amended component table has no maximum SHGC column. SHGC remains relevant for comfort and can be an input to a performance analysis. Compare identical product configurations where possible because changing the glass, coatings or sash can change the rating. Under N1102.4.3, the mandatory product infiltration limits are 0.3 cfm/ft² for windows, skylights and sliding glass doors and 0.5 cfm/ft² for swinging doors, with a site-built exception. The code permits the relevant NFRC 400 or AAMA/WDMA/CSA test.

Apply the same distinctions on site

  • Seal the perimeter. Seal the joint between the unit and framing in accordance with the detailing for the assembly and Table N1102.4.1.1. Account for differential movement. Low-expansion window foam or a compatible backer rod and sealant can be used where specified for that joint.
  • Protect the drainage path. Coordinate the sill, jamb and head flashing with the approved installation detail. Preserve the outlet so water has a path out of the opening.
  • Test the enclosure. Under the Michigan-prescriptive N1102.4.1.2, the building or dwelling unit is limited to 4 ACH50. Test after envelope penetrations are made and submit the signed report. Use a certified independent third party if required by the code official.
  • Document the installed configuration. Match the label or default to the schedule, record exemptions or tradeoffs in the compliance documents, and complete the permanent panel certificate under N1101.16. The certificate lists predominant fenestration U-factors, using the value covering the largest area when several apply.

For replacement work, Michigan N1102.3.6 applies the table U-factors when the replacement fenestration product includes sash and glazing. N1101.3.1 exempts glass-only replacement in the existing sash and frame, and storm windows over existing fenestration, if building energy use is not increased.

Test Your Knowledge

Which rating on an NFRC label measures the fraction of solar heat a window admits?

A

Solar heat gain coefficient (SHGC)

B

Visible transmittance (VT)

C

U-factor

D

Air leakage (AL)

Test Your Knowledge

With the same window area and indoor–outdoor temperature difference, replacing a U-1.00 window with a U-0.30 unit reduces heat flow through the assembly by approximately how much?

A

30 percent

B

70 percent

C

50 percent

D

97 percent