36.1 Notching & Boring Rules
Key Takeaways
R502.8.1 limits solid-sawn notches away from the ends to one-sixth of actual depth, one-third of depth in length and locations outside the middle third. At the actual end the depth cap is one-quarter.
Joist holes under R502.8.1 may not exceed one-third of the member depth and must stay at least 2 inches from the top or bottom edge, 2 inches from any other hole, and 2 inches from any notch in the same member.
R502.8.1 bans top and bottom notches in the middle third of the span but contains no matching location ban for holes, so a centered hole can be legal exactly where a notch of the same size is not.
The R602.6 figures show a 5/8-inch minimum edge clearance for stud holes. Diameter is at most 60 percent. Exterior or bearing stud holes over 40 percent require doubling, subject to the approved stud-shoe exception and the limit on successive bored pairs.
R602.6.1 addresses plumbing or duct cuts through more than half an exterior or interior bearing top plate. It specifies a galvanized tie with the required dimensions, nails and extension, or an equivalent. Full-side wood structural panel sheathing qualifies for the exception.
Why a Notch or Hole Is a Structural Decision
In a simply supported sawn joist under an even gravity load, bending puts the top in compression and the bottom in tension. Bending stress is lowest near mid-depth, and bending moment is highest near midspan. Vertical shear force is greatest near the bearings in this example. A continuous member or a cantilever can put a different edge in tension.
An edge notch removes highly stressed wood in bending. A bored hole near mid-depth can clear both edges, but it still takes material out of the shear path. R502.8.1 limits both cuts in different ways.
A 3-inch hole centered in the depth of a 9-1/4-inch sawn 2x10 leaves 3-1/8 inches of wood above and below. It can meet the diameter and edge limits at midspan if it also clears other holes and notches by 2 inches. A 1-inch-deep edge notch at midspan fails the location rule.
MRC R502.8.1 governs cuts in solid lumber, and R502.8.2 governs engineered floor members. For sawn roof framing, R802.7.1 applies the R502.8.1 limits with a separate permitted rafter-tail detail.
Joist and Beam Notching — MRC R502.8.1
Identify the actual member depth and whether the notch is at an actual end or elsewhere in the span. Use the applicable depth limit in this table for solid sawn lumber.
| Limit | Verified requirement (R502.8.1) |
|---|---|
| Notch depth away from the actual end | Not more than one-sixth of the member depth |
| Notch length | Not longer than one-third of the member depth |
| Notch location | Not permitted in the middle one-third of the span |
| Notch at the end of a member | Not more than one-fourth of the member depth |
A second, less-known rule applies to heavy members: on members 4 inches or greater in nominal thickness, the tension side shall not be notched except at the ends. On a simply supported 4x10 or 4x12 beam loaded downward in its span, the bottom edge is the tension side, so an interior bottom notch is prohibited. On a 2x10, which is only 1-1/2 inches thick, that thickness trigger is not met — but the one-sixth depth and middle-third rules still control.
Worked example — the midspan notch
A plumber wants to cut a notch in the top edge of a 2x10 SPF joist at midspan for a 2-inch drain line. The proposed notch is 2 inches deep and 4 inches long. The joist spans 14 feet.
- Actual depth of a 2x10 is 9-1/4 inches.
- Depth test: one-sixth of 9-1/4 inches = 1.54 inches. A 2-inch notch is too deep.
- Length test: one-third of 9-1/4 inches = 3.08 inches. A 4-inch-long notch is too long.
- Location test: midspan of a 14-foot span falls inside the middle one-third (from 4 feet 8 inches to 9 feet 4 inches measured along the span from one support). A top-edge notch there is prohibited no matter how shallow it is.
The proposed notch fails three checks. A bored route may work if the hole fits the actual pipe outside diameter and the required clearances. A dropped soffit or chase can keep the joist intact. At the actual end of this joist the maximum depth is 2-5/16 inches (one-quarter of 9-1/4 inches). The one-third-depth length limit is about 3.08 inches, so moving the same 4-inch-long cut to the end still fails.
For a sawn rafter with a cantilevered tail, use R802.7.1.1 and Figure R802.7.1.1. Check the notch at the bearing as shown, retain at least 3-1/2 inches of rafter depth in the cantilevered portion and limit the cantilever to 24 inches under this detail. The ceiling-joist end taper in R802.7.1.2 is separately limited to one-quarter of the member depth.
Boring Holes Through Joists — MRC R502.8.1
Hole rules are stated separately from notch rules and are more generous than many crews assume:
- Diameter: not more than one-third of the member depth.
- Edge clearance: the hole edge must be at least 2 inches from the top or bottom of the member.
- Hole-to-hole clearance: at least 2 inches from any other hole in the member.
- Notch clearance: where the member is also notched, at least 2 inches from the notch.
R502.8.1 has no middle-third exclusion for bored holes. Check diameter and separation from edges, holes and notches at the proposed location. Other load, connection and product constraints can matter where a hole interferes with a bearing detail or a fastener group.
Worked example — the 2-inch hole
A proposed route calls for an actual 2-inch-diameter hole through a dry dressed sawn 2x10. Confirm the outside diameter and clearance needed before selecting a bit for a nominal pipe size.
- One-third of 9-1/4 inches = 3.08 inches, so a 2-inch hole is inside the size limit with about an inch to spare.
- Centered at mid-depth, clear wood above and below the hole is (9.25 - 2) / 2 = 3-5/8 inches each, far past the 2-inch minimum.
- The hole still must be at least 2 inches from any other hole and 2 inches from any notch in the same joist.
The same centered hole can meet the size and edge limits in a 2x8 (one-third of 7-1/4 inches = 2.42 inches), but in a 2x6 (one-third of 5-1/2 inches = 1.83 inches) a true 2-inch hole exceeds the limit. It must be relocated, run through a dropped soffit, or engineered — not bored and forgotten.
Engineered wood is a different rulebook
MRC R502.8.2 permits an engineered member cut, notch or hole only if the manufacturer permits it or a registered design professional specifically considers its effects in the member design. For a web opening, check the size and location in the applicable product chart if using manufacturer permission. Standard I-joist details such as Weyerhaeuser TJI prohibit field alterations through flanges. Floor truss member or component alterations require registered design professional approval under R502.11.3. Roof members are covered by R802.7.2 and roof truss alterations specifically by R802.10.4. Obtain a designed repair for a damaged engineered member.
Nail protection is a separate code
For covered wiring methods in Michigan dwellings, Table E3802.1 as amended by R 408.30537a generally requires the edge of a bored wiring hole to be at least 1-1/4 inches from the framing edge, or requires physical protection. The listed choices include steel plate or sleeve at least 0.0625 inch (1/16 inch) thick, a listed steel plate, or other physical protection. The table’s applicability column matters. A structurally legal hole with its edge 3/4 inch from the narrow face of a stud still needs protection for a covered cable. A plate that protects the cable cannot restore framing strength.
Stud Notching and Boring — MRC R602.6
Studs carry axial load, so a notch or hole is a reduction of the section that resists compression plus wind bending. R602.6 sets limits by wall type, and the wall type matters as much as the size of the cut.
| Member | Notch limit | Hole limit | Prohibited |
|---|---|---|---|
| Stud, exterior wall or bearing partition | 25 percent of stud width (7/8 inch on a 2x4) | 60 percent of stud width in diameter; hole edge at least 5/8 inch from stud edge | A hole in the same section as a cut or notch; boring more than two successive doubled studs |
| Stud, nonbearing partition | 40 percent of a single stud width (1.4 inches on a 3-1/2-inch stud) | Same 60 percent diameter and 5/8-inch edge rule | A hole in the same section as a cut or notch |
| Exterior or interior bearing top plate cut for piping or ductwork (R602.6.1) | Cutting or notching more than 50 percent of plate width needs a galvanized tie | Same threshold applies to drilled plate cuts | A plate cut without the required tie, except where the entire side is sheathed with wood structural panels |
| Sawn joist or rafter (R502.8.1 and R802.7.1) | One-sixth depth, one-third depth long, one-fourth at ends. See the separate cantilevered rafter-tail provision above. | One-third depth in diameter | Top or bottom notches in the middle third of span |
| I-joist, SCL, glulam or CLT (R502.8.2) | Manufacturer permission or consideration in the member design by an RDP | Same rule | Cuts outside either approval path |
| Floor truss (R502.11.3) | Registered design professional approval | Same rule if a component is altered | Member or component alterations without RDP approval |
Use the 5/8-inch minimum edge clearance drawn in Figures R602.6(1) and (2). The 2015 model paragraph has conflicting wording. The figures show the remaining wood the installation needs at the edge. In an exterior wall or bearing partition, holes up to 40 percent of stud width can use a single stud if they meet the other limits. For holes over 40 percent through 60 percent, double the stud and bore no more than two successive doubled studs. The approved stud-shoe exception depends on the manufacturer’s allowed installation. Doubling under this rule applies to bored holes.
Worked example — a 2-inch hole in a 2x4 bearing wall
- Stud width is 3-1/2 inches. Sixty percent is 2.1 inches, so a 2-inch hole passes the diameter test.
- Centered, the hole leaves 0.75 inch on each side, past the 5/8-inch edge minimum.
- But the hole exceeds 40 percent of width (1.4 inches), and this is an exterior or bearing wall, so the standard detail requires a doubled stud, with no more than two successive doubled studs bored. An approved stud shoe may be used under its permitted conditions.
Plate notches — R602.6.1
Where piping or ductwork in or partly in an exterior or interior bearing wall requires a top-plate cut of more than 50 percent of the plate width, the plate must be tied with a galvanized metal tie at least 0.054 inch thick (16 gauge) and 1-1/2 inches wide, fastened across and to the plate at each side of the opening with at least eight 10d nails (0.148-inch shank and at least 1-1/2 inches long) at each side or an equivalent, with the tie extending at least 6 inches past the opening. The exception: where the entire side of the wall with the notch is covered by wood structural panel sheathing.
Practical penetration rules that pass inspection
- Lay out plumbing and electrical before framing, not after the sheathing is on. Moving a drain six inches during layout is free; moving it after drywall is a repair job.
- Lay out each penetration for its net hole diameter and clear distance to the member edges, nearby holes and notches. Check whether the location interferes with a connection.
- In solid-sawn floor framing, keep at least 2 inches between holes and between a hole and any notch, as R502.8.1 requires.
- Never enlarge a notch to make a pipe fit. Use a smaller line, a chase, a dropped soffit, or a furred wall.
- Use the cut limits for the member and wall type. Verify the specific approved stud-shoe detail before relying on the exception.
- When a cut falls outside the prescriptive limits, get a sealed detail from a Michigan-registered design professional. R301.1.3 is the lawful path, and it is cheaper than a failed framing inspection.
A plumber proposes a 2-inch-deep notch in the top edge of a 2x10 joist at midspan. How does MRC R502.8.1 treat that cut?
It is permitted because 2 inches is less than one-third of the 9-1/4-inch joist depth
It is not permitted. Away from the end the depth limit is one-sixth of the joist depth, and the middle third prohibits a notch.
It is permitted if the notch is no longer than 3 inches measured along the joist
It is permitted if a 16-gauge steel tie is nailed across the notch on both sides
Which listed bit makes the largest hole within the R502.8.1 diameter limit for a dry dressed sawn 2x8 floor joist, before checking clearances?
1-7/8 inches
2-1/4 inches
3-5/8 inches
2-5/16 inches
A 2-inch hole is proposed in a 3-1/2-inch stud in an exterior bearing wall. It clears the edges and any notch, and no approved stud shoe is used. Which R602.6 detail applies?
The stud must be doubled, because the hole exceeds 40 percent of the stud width, and no more than two successive doubled studs may be bored
Nothing further, because the hole is under the 60 percent of width limit
The hole is prohibited, because no exterior wall stud may be bored more than 25 percent of its width
The entire wall segment must be redesigned by a registered design professional