44.1 Brick Veneer & Wall Ties

Key Takeaways

  • Anchored veneer carries gravity load on a ledge or other support, with ties to the backing for lateral loads. Adhered veneer transfers loads through the bond and backing. Use 2015 MRC R703.8 or R703.12 and Michigan Rule 545 figures as applicable.

  • For the wood-stud corrugated-tie detail, Table R703.8.4 gives a nominal 1-inch airspace from sheathing to veneer. Check the strand-wire rows or the grouted alternative when those systems are specified.

  • An ordinary veneer tie serves at most 2.67 square feet with spacing at most 32 inches horizontally and 24 inches vertically. Check the 2-square-foot seismic and wind exception and the supplemental opening ties.

  • Weep holes go in the outside wythe at no more than 33 inches on center and are at least 3/16 inch in diameter, and flashing goes under the first course above grade and at every shelf angle and lintel (R703.8.5, R703.8.6).

  • The R703.8.2 gravity support path is limited to 40 psf installed with L/600 deflection outside D0–D2. Under R703.8.3 a veneer lintel needs at least 4 inches of bearing and the applicable corrosion protection.

Last updated: November 2026

Two Ways to Carry Masonry on a House

In anchored veneer, a ledge, shelf angle or other approved support carries the veneer weight, while ties transfer out-of-plane loads to the backing. In adhered veneer, the bond and the prepared backing carry the units. The backing may need lath and a scratch coat, depending on the assembly. In the 2015 Michigan Residential Code (MRC), anchored veneer is R703.8 and adhered veneer is R703.12. Michigan Rule 545 replaces the typical wall and two exterior-support figures under R703.8. Use the state figures together with the applicable text and tables.

Above a Foundation or Carried by Framing

R703.8 generally limits anchored veneer over wood or cold-formed steel to the first story above grade plane and 5 inches thick, with separate exceptions for listed cases above a noncombustible foundation. For example, the A or B row in Table R703.8(1) permits all stories in the listed one- or two-story steel and one- to three-story wood buildings, with up to 30 feet of veneer above the noncombustible foundation, 5 inches nominal thickness and 50 psf installed weight. The table allows another 8 feet for gable ends subject to its notes and the story-height limits. Category C has its own rows. Table R703.8(2) provides separate limits for qualifying wood-framed detached dwellings in D0, D1 and D2. Installed weight includes mortar and other materials used to install the veneer.

R703.8.2 addresses a different load path. Outside D0, D1 and D2, exterior veneer at up to 40 psf installed may be carried on wood or cold-formed steel construction designed for the veneer and other imposed loads. Limit supporting-member deflection to span divided by 600. Over a 12-foot span that is 144/600 = 0.24 inch. Provide a movement joint where this frame-supported veneer meets foundation-supported veneer. Interior veneer support follows R703.8.1.

The Cavity Wall, Layer by Layer

A drained brick veneer assembly collects rain that reaches the cavity and sends it back outdoors before it reaches the framing.

Layer, inside to outsideWhat it isCode hook and inspection check
Framing2x4 or 2x6 studs, typically 16 in. o.c.Backup stiffness; L/600 deflection limit where the frame supports veneer (R703.8.2)
SheathingWood structural panel or approved sheathingFollow the sheathing installation instructions, including panel spacing
Water-resistive barrierNo. 15 asphalt felt (ASTM D226, Type 1) or an approved WRBR703.2: applied horizontally, upper layer over lower at least 2 in., joints lapped at least 6 in., continuous to the top of the wall
FlashingApproved corrosion-resistant materialR703.8.5: beneath the first course above finished grade and at supports such as shelf angles, structural floors and lintels
Air spaceA clear cavity sized to the tie systemTable R703.8.4 gives a nominal 1 in. from sheathing to veneer for the wood corrugated detail. Its strand-wire rows keep at least a nominal 1 in. from sheathing to veneer and allow up to 4-1/2 in. from backing to veneer
Wall ties22-gage corrugated steel or No. 9 (W1.7) wireR703.8.4: embedded at least 1-1/2 in. into the veneer with at least 5/8 in. of mortar cover
Brick veneerE.g., a facing brick nominally 4 inches wideMatch the unit and grade to the specification and severe-weathering exposure
Weep holesOpen head joints, tubes or wicks in the outside wytheR703.8.6: maximum 33 in. on center, at least 3/16 in. diameter
LintelsNoncombustible support across the openingAt least 4 in. bearing at each end. Check the steel corrosion treatment under R703.8.3

The cavity interrupts capillary contact and lets rain that penetrates the veneer run down to flashing and out through weeps. Protect that path from mortar droppings. Clear the outlet during installation and check that mortar does not bridge the cavity. In Michigan, repeated freezing of saturated masonry can damage the veneer, so drainage matters as well as selecting the proper unit. If the approved assembly uses the grout-fill option in R703.8.4.2, follow that provision for water-resistive protection.

Wall Ties: Size, Spacing and Embedment

Ties transfer out-of-plane loads from the masonry to the backing. Select a tie and a fastening arrangement that perform under the design loads and accommodate the expected relative movement.

R703.8.4 requires corrosion-resistant ties embedded at least 1-1/2 inches into mortar or grout, with at least 5/8 inch of cover from the exposed face. For wood studs, Table R703.8.4 gives a 22-gage corrugated sheet tie at least 7/8 inch wide or a hooked W1.7 strand-wire tie. The ordinary fastener entry is an 8d common nail into framing. In D0, D1 and D2, the wood fastener is at least the stated 8d ring-shank nail. For cold-formed steel use the listed adjustable strand-wire system and No. 10 screw with at least three threads exposed past the steel. Check the approved corrosion-resistant ties and suitably rust-inhibitive or noncorroding fasteners for the installation.

The ordinary R703.8.4.1 layout limits are 2.67 square feet per tie, at most 32 inches horizontally and at most 24 inches vertically. A 32-by-24 layout covers 768 square inches, or 5-1/3 square feet. A 16-by-24 layout covers 384 square inches, or 2-2/3 square feet, and satisfies all three ordinary limits. The area allowance changes to 2 square feet per tie in seismic Categories D0, D1 and D2, for townhouses in Category C, or for wind pressure above 30 psf. A 24-by-12 layout illustrates compliance with the tighter area check if the backing, courses and edges permit it. Add ties around openings greater than 16 inches in either dimension. The opening ties go within 12 inches of the edge and at most 3 feet apart around the perimeter.

A 30-Foot Wall, Counted Out

Assume a solid wall 30 feet long by 9 feet high, with an ordinary 2.67-square-foot allowance, studs at the tie columns and bed joints at the tie rows. Lay out 23 columns at 16 inches on center, starting 4 inches from the left edge and ending 4 inches from the right edge. Lay out five rows, at 6, 30, 54, 78 and 102 inches above the bottom. The top row is 6 inches below the top. Interior tie areas are 16 × 24 = 384 square inches, or 2-2/3 square feet. The two side bands are 4 inches to the edge plus 8 inches to the midpoint between ties. The top and bottom bands are 6 inches to the edge plus 12 inches to the next midpoint. Their tributary areas are smaller than an interior tie's.

The layout takes 23 × 5 = 115 ties. Area alone would give a lower bound of 102, rounding 270/2.67 up. If an opening is added, draw the new field and opening tie positions against the actual courses and framing and check all wall areas. A gross-wall count plus a perimeter quotient does not establish the final layout.

Lintels, Shelf Angles and Inspection Points

R703.8.3 requires a noncombustible lintel for veneer over an opening, with at least 4 inches of bearing at each end. Shop-applied rust-inhibitive paint is the default for steel, with exceptions for corrosion-resistant steel and steel with a corrosion-resistant coating. The veneer carries its own weight. Keep the building's roof and floor loads on their designated structure.

Table R703.8.3.1 gives allowable clear spans by angle and number of stories above the opening. In the tabulated steel-angle path with no story above, a 3 × 3 × 1/4 angle spans up to 6 feet and a 4 × 3 × 1/4 angle up to 8 feet. With one story above, the latter is limited to 6 feet. A qualifying 8-foot opening with no story above can use that listed 4 × 3 × 1/4 angle with its long leg vertical. The minimum piece length with exactly 4 inches of bearing at each end is 104 inches. Other steel members may be used if designed for the loads. R703.8.3.2 is a separate strengthened opening detail, with its own maximum span, side lengths, reinforcement, veneer heights and shoring.

The R703.8.2.1 stud-supported shelf detail uses at least a 6 × 4 × 5/16-inch angle, with the long leg vertical, fastened at double 2 × 4 wood studs or double 350S162 cold-formed steel studs at most 16 inches on center. At each pair use at least two 7/16-inch by 4-inch lag screws into wood or two 7/16-inch bolts with washers into steel. Maintain at least 1/16 inch clear below the angle and support at least two-thirds of the veneer thickness on it. The veneer above this angle is limited to 12 feet 8 inches. Use the required stops above a 7:12 roof slope through 12:12 or an approved detail. Follow Michigan's figure for the angle, flashing and weeps. R703.8.2.2 has a separate roof-supported arrangement. In the state drawing the angle rests on the roof support and is not fastened to the wall stud. Follow the required built-up roof members and connections for that method.

Before the brick covers the work, check WRB laps and continuity, the specified flashing and outlets, ties fastened to the backing at the correct layout and embedment, an open cavity where the detail calls for one, lintel bearing and corrosion protection, and the movement joint at a change between framing and foundation support.

Test Your Knowledge

For the drained wood-stud detail using corrugated ties in 2015 MRC Table R703.8.4, what is the nominal space between sheathing and brick veneer, and what does it do?

A

1/4 inch, to allow for mortar squeeze-out and expansion of the brick

B

1/2 inch, to provide room for insulation between the brick and the sheathing

C

1 inch, to create a drainage plane that carries water down to the flashing and weep holes

D

2 inches, to allow the wall to be grouted solid after the brick is laid

Test Your Knowledge

For an ordinary corrugated-tie installation where the tighter wind and seismic exception does not apply, which field layout satisfies all three limits in R703.8.4.1?

A

24 inches horizontally by 24 inches vertically

B

16 inches horizontally by 24 inches vertically

C

32 inches horizontally by 24 inches vertically

D

24 inches horizontally by 32 inches vertically

Test Your Knowledge

For an ordinary steel lintel without an alternative corrosion-resistant material or coating, what minimum end bearing and steel protection does 2015 MRC R703.8.3 specify?

A

4 inches of bearing, with shop-applied rust-inhibitive coating on steel lintels

B

2 inches of bearing, with field-painted primer applied after installation

C

6 inches of bearing, with no coating required if the lintel is galvanized

D

3 inches of bearing, with a bituminous membrane wrapped around the angle