34.3 Suspended & Above-Grade Concrete Slabs
Key Takeaways
A suspended slab spans between permanent supports and transfers loads to them. A slab on ground bears on its base and subgrade.
MRC R506 applies to concrete floors on ground. Use the accepted engineering design path for a suspended system beyond the MRC prescriptive limits and check the applicable documentation and approval requirements.
Reinforcement follows engineered bending and shear demands. Bottom steel commonly carries positive moment, and top steel carries negative moment where continuity or cantilever action creates it.
Check slab type, support and connections at walls, beams, columns or permanent deck against the approved drawings.
At 150 lb/ft³, a 16 × 24 ft slab 6 inches thick contains 192 ft³ of concrete and weighs 28,800 lb before other loads.
Quick Answer: Follow the permanent load path. A suspended slab carries its loads to discrete supports such as walls, beams or columns. Its span, depth, reinforcement and connections come from the design.
A floor can be higher than exterior grade and still be supported on compacted fill. A garage floor over an open basement spans to supports. The support condition determines how the slab handles bending and shear.
How to Tell Which One You Have
Check the section and structural drawings before identifying the slab system:
- Review whether the slab spans an open space or bears continuously on prepared ground.
- Locate the permanent bearing lines or points and trace their loads to the foundation.
- Identify the slab system and the supports and connections shown in the details. A formed soffit, ribbed slab or corrugated deck signals details to verify.
- Check the slab depth, reinforcement and openings against the structural drawings.
Residential examples include a garage floor over a basement, a balcony or landing over open space, and an addition over a crawl space. Check which elements remain after stripping.
| Type | Permanent load path | Example |
|---|---|---|
| Slab on ground | Base and subgrade | Basement floor at grade |
| Beam-and-slab | Slab to beams and then to walls or columns | Garage over basement |
| Flat plate or flat slab | Slab directly to columns, with drop panels or capitals where detailed | Engineered open floor |
| Slab on metal deck | Structural slab and supporting frame, with composite action only where designed | Steel-framed addition |
| Precast units and topping | Units to their bearings, with topping participation as designed | Precast floor |
| Insulated permanent forms | Reinforced concrete ribs or slab to supporting structure | Insulated concrete floor system |
Who Designs It
MRC R506 addresses floors on ground. Where a suspended slab is outside the prescriptive scope, R301.1.3 requires design of the nonconforming elements under accepted engineering practice, with compatibility with the conventional portions. ACI 318 provides the structural concrete design provisions where applicable.
For a Michigan builder this has practical consequences:
- Provide construction documents adequate to show the design and load path under the applicable permit requirements. Michigan’s licensing law includes an exemption for qualifying detached one- and two-family residences with calculated floor area no greater than 3,500 ft². Check whether a seal is required for the project, and follow the applicable accepted design and approval path.
- Arrange required inspections before work is concealed. Check slab depth and reinforcement, cover, openings, connections, embeds and applicable temporary works against their respective approved plans.
- Get approval for revisions that affect strength, use, loads or detailing. A new partition, heavier vehicle or hot tub can change the original load assumptions.
Thickness and Reinforcement
Where ACI 318-14 Table 7.3.1.1 applies, it gives minimum thickness for eligible solid nonprestressed one-way slabs without a separate deflection demonstration. Use it for the stated support, normal-weight concrete and Grade 60 reinforcement, and check the limitations for attached or supported construction sensitive to deflection. Let ℓ be the applicable span length, or the clear projection for a cantilever.
| Support condition | Tabular thickness | For ℓ = 12 ft |
|---|---|---|
| Simply supported | ℓ/20 | 7.2 in. |
| One end continuous | ℓ/24 | 6.0 in. |
| Both ends continuous | ℓ/28 | About 5.14 in. |
| Cantilever | ℓ/10 | 14.4 in. for a 12-ft clear projection |
These are deflection-control dimensions under the table’s assumptions. Strength, shear, detailing and other limits still need checking. The design may use a calculated deflection path. Never use the table to specify thickness from garage plan dimensions alone.
Place steel for the analysis and connection details:
- Positive bending in a typical gravity span puts tension near the bottom at midspan.
- Negative bending over continuous supports or at a cantilever root puts tension near the top. Locate each bar where detailed and support it during placement.
- Match cover, development, lap lengths and edge or opening details to the plans. Do not cut or substitute reinforcement without approval.
Check shear at supports, including punching shear at columns where applicable. Verify the anchors or the development of reinforcement at beams, walls and other supports.
Placement, Connections and Service Conditions
Plan access, concrete distribution and curing to suit the assembly. The separate lesson on shoring suspended concrete explains the temporary load path and release sequence. Before placing, verify the temporary system and that steel, embeds and openings are in their approved locations.
Construction joints must follow the approved locations and force-transfer details. Keep any sawcut or groove within the designed detail. A slab-on-ground contraction grid cannot be carried over to the suspended slab.
Curing maintains moisture and temperature under the governing specification. Protect the exposed upper face promptly and maintain any required treatment of surfaces exposed after stripping.
Connections and Load Path
Typical details to verify
- Wall bearing. Verify bearing length, anchors or dowels, edge distance, and specified development into the slab and wall.
- Cast-in-place beams. Follow the placement and reinforcement continuity details for the slab-to-beam load transfer.
- Metal deck. Verify deck attachment, closures and edge details. Form deck can serve as a permanent form. Composite deck and composite beams have separate design requirements and use their specified attachment or shear connectors.
- Insulated forming systems. Verify reinforcement and continuity of the concrete ribs and slab or topping. Check the support and bearing details for the specific system.
- Diaphragm connections. Verify the specified paths through which wind or seismic forces reach the walls and other resisting elements.
Confirm the load path at terminations as well as midspan. Unsupported penetrations and changed attachments can interrupt designed force transfer.
Slab-on-Ground Versus Suspended Slab
| Feature | Slab on ground | Suspended slab |
|---|---|---|
| Permanent support | Prepared ground and base | Walls, beams, columns or a designed structural deck |
| Load behavior | Distributed soil support | Bending and shear between supports |
| Design path | Applicable MRC R506 requirements or approved design | Engineered path for elements beyond prescriptive limits |
| Reinforcement | Required by the selected design or details | Defined by structural action and detailing |
| Forming | Can use edge forms with bearing on prepared base | Removable or permanent form system designed for construction loads |
| Field checks | Subgrade, base, retarder, thickness and any reinforcement | Supports, openings, placement limits, reinforcement, cover and connection details |
Worked Example — Concrete Weight of a Garage Slab
Use a 16 × 24 ft suspended slab whose approved design specifies 6 inches of uniform thickness. This calculation estimates concrete quantity and self-weight for the stated geometry.
Area: 16 × 24 = 384 ft².
Concrete volume: 384 × 0.5 = 192 ft³, or 7.11 yd³.
Concrete weight: 192 × 150 lb/ft³ = 28,800 lb. This is 75 psf of slab self-weight before added layers, attachments or live loads.
Same footprint at grade: At 4 inches thick, volume would be 128 ft³ (4.74 yd³). At this footprint, increasing from 4 to 6 inches adds 50% to slab volume. The arithmetic does not set the thickness for either floor.
Before pricing the structural slab, include any ribs, edge beams and other geometry in the concrete takeoff. Use the separate shoring lesson for construction loads and support checks.
What makes a concrete slab a suspended slab rather than a slab-on-grade?
It has a vapor retarder directly over gravel.
It spans between permanent supports and carries loads to them in bending and shear.
It is more than 4 inches thick.
It is above the local frost line.
A 16 ft by 24 ft suspended garage slab is 6 in. thick. Using normal-weight concrete at 150 lb per cubic foot, what is the weight of the concrete alone?
14,400 lb
19,200 lb
28,800 lb
57,600 lb