51.3 Safety Glazing
Key Takeaways
R308.3.1 generally uses CPSC 16 CFR 1201 Category II. Table R308.3.1(1) permits Category I for certain smaller panes. Where the ANSI alternative applies, check the Class A or B criteria in Table R308.3.1(2).
A visible manufacturer’s designation or permitted label identifies hazardous-location glazing under R308.1. Check the exceptions and the markings for small multipane assemblies.
Glazing in fixed or moving door panels is generally hazardous under R308.4.1. A nearby fixed panel is evaluated under its own height, proximity and exception tests.
For a large, low window, all four R308.4.3 conditions must be present. A pane outside that rule can still be hazardous under another provision.
Glazing in walls, enclosures or fences containing or facing a pool or other listed wet location is hazardous when the bottom edge is below 60 inches above a standing or walking surface and the horizontal exception does not apply. Check each pane in multiple glazing.
Glass near a walking or bathing surface can be struck by a person who slips or mistakes a panel for an opening. Safety glazing reduces injury by limiting dangerous breakage under the relevant impact test. Fully tempered glass typically breaks into small particles. Laminated glass uses an interlayer that can retain fragments after a break. Specify a product tested and marked for the required use. The glass type alone does not establish its impact classification.
Select the impact classification
Under R308.3.1, use CPSC 16 CFR 1201 Category II where required unless the applicable table provides otherwise. Category I corresponds to a 150 ft·lbf impact and Category II to a 400 ft·lbf impact. The federal product scope covers items such as doors and tub and shower enclosures. The MRC uses its own hazardous-location rules to decide which locations in a house require impact-tested glazing.
| Location covered by Table R308.3.1(1) | Exposed area of one side of one lite up to 9 ft² | More than 9 ft² |
|---|---|---|
| Ordinary doors, storm or combination doors, and R308.4.2 door-adjacent panels | Category I | Category II |
| Large, low window panels under R308.4.3 | No requirement under this column | Category II |
| Patio-type sliding glass doors and wet-location doors or enclosures covered by the table | Category II | Category II |
R308.3.1 also allows ANSI Z97.1 where its exception for glazing outside the specified doors and wet enclosures applies. Use Class A unless Table R308.3.1(2) permits a different result. For example, the table permits Class B for a qualifying door-adjacent lite up to 9 ft² when the ANSI route applies. Check the required category even when the location itself has no pane-size threshold. R308.3 has separate exceptions for louvered windows and jalousies subject to R308.2, glass supported by continuous backing, and glass unit masonry complying with R607.
Verify the identification in the field
Under R308.1, look for the designation identifying who applied it, the glass type and the test standard. It must be visible in the completed work and can be etched, embossed or applied so removal destroys it. The code permits a label in place of the designation. For glass other than tempered, the official can approve other evidence such as a certificate or affidavit. Tempered spandrel glass can have a removable paper designation. Under R308.1.1, an assembly of panes each no larger than 1 ft² needs a full designation on at least one pane. Mark the other panes with the applicable test standard.
Assume no listed exception applies. Which location is hazardous under R308.4 regardless of exposed pane area?
A glazed panel in a swinging, sliding or bifold door
Any pane over 9 square feet regardless of location
A window with its bottom edge 70 inches above the bathroom floor, 48 inches from the bathtub water’s edge
A fixed picture window 5 feet from the nearest walking surface with a bottom edge 24 inches above the floor
Identify the hazardous location
| MRC section | Apply this test |
|---|---|
| R308.4.1 | Glazing in fixed or operating panels of swinging, sliding or bifold doors. Exceptions apply to decorative glazing and an opening that will not pass a 3-inch sphere. |
| R308.4.2 | A panel with its bottom exposed edge less than 60 inches above the floor or walking surface, within 24 inches of either side of the door in its closed plane. Also check a perpendicular wall within 24 inches of the hinge side of an inward-swinging door, using the same height test. |
| R308.4.3 | A fixed or operable window panel satisfying all four tests. One exposed pane exceeds 9 ft², its bottom is less than 18 inches above the floor, its top is more than 36 inches above the floor, and a walking surface is within 36 inches horizontally in a straight line. |
| R308.4.4 | Glazing used in guards and railings, including structural and infill panels, regardless of area or height. |
| R308.4.5 | Glazing in walls, enclosures or fences containing or facing a pool, hot tub, spa, whirlpool, sauna, steam room, bath or shower. The bottom exposed edge is less than 60 inches vertically above a standing or walking surface. Each pane in multiple glazing must comply. |
| R308.4.6 | Glazing with a bottom exposed edge less than 36 inches above the plane of the adjacent walk surface of a stair, an intermediate landing or a ramp. |
| R308.4.7 | Glazing less than 36 inches above a bottom stair landing and in the area within a 60-inch horizontal arc of less than 180 degrees from the bottom tread nosing. A compliant R312 guard with the glass plane more than 18 inches from it excepts this condition. |
Check exceptions at the location that triggers the rule. Under R308.4.2, an intervening wall or permanent barrier, decorative glazing, and glazing adjacent to a patio door’s fixed panel are exceptions. For a door into a closet or storage area 3 feet deep or less, apply R308.4.3 to the adjacent glazing. The glass in the patio door’s own panel is separately evaluated under R308.4.1.
For R308.4.3, the exceptions include decorative glazing and outboard panes of multiple glazing with the bottom edge at least 25 feet above an adjacent grade, roof or other qualifying surface. Both R308.4.3 and R308.4.6 allow a rail on the accessible side or sides, installed 34–38 inches above the walk surface, with a cross-sectional height of at least 1½ inches and capacity for 50 lb per linear foot horizontally without contacting the glass. R308.4.6 also has an exception for glazing at least 36 inches horizontally from the walking surface.
Under R308.4.5, measure horizontally and in a straight line. The wet-location exception begins more than 60 inches from the water’s edge of a pool, bath, hot tub, spa or whirlpool or from the edge of a shower, sauna or steam room. Other hazardous-location rules still apply.
Apply the tests to two nearby panels
A 12-ft² fixed window with its bottom edge 30 inches above the floor fails the low-edge condition for the large-window rule. If it is in the same plane as a nearby entry door, 20 inches from the door edge, it satisfies the separate door-adjacent test unless an exception applies. A narrower sidelight with the same position can also qualify, because R308.4.2 applies its own proximity and height criteria. Next, select the impact classification by the individual lite size and verify the markings before installing it.
Assume no exception applies. Under MRC R308.4.3, which set of conditions makes the exposed pane of a window hazardous?
Pane larger than 9 ft² with any sill below 44 inches
Bottom edge below 18 inches with a walking surface within 60 inches
Pane larger than 20 ft², top edge above 42 inches, walking surface within 24 inches
Pane larger than 9 ft², bottom edge below 18 inches, top edge above 36 inches, and a walking surface within 36 inches horizontally
A nondecorative fixed sidelight sits in the closed plane of an entry door, 20 inches from its edge. The bottom of the glass is 40 inches above the floor and there is no intervening barrier. What does R308.4.2 require?
Nothing — the bottom edge is above 18 inches and the pane is under 9 square feet
Safety glazing — glazing within 24 inches of the door in the door's plane with a bottom edge below 60 inches is a hazardous location
Safety glazing only if the door swings over the sidelight
Nothing — only glazing on the hinge side of a perpendicular wall is hazardous