48.4 Spray Foam Insulation
Key Takeaways
Closed-cell foam usually provides more R-value for a given thickness. Read product data for installed R-value, air impermeability and vapor-retarder class separately.
R316.4 provides gypsum wallboard, wood structural panel and qualifying NFPA 275 options. Check exceptions for the exact location and approved assembly.
Service-access attics and crawl spaces have different lists of ignition barriers. R316.6 recognizes tested, specifically approved configurations under the applicable exception.
The rim exception depends on thickness, density and the stricter 25/450 surface-burning limits together. R316.3’s general limits are 75/450.
For unvented roofs, confirm R806.5 insulation placement and condensation control in addition to total thermal performance.
Open-Cell and Closed-Cell Spray Foam
Two-component spray polyurethane foam expands and cures in place. Open-cell material is generally lighter and more vapor permeable. Closed-cell foam is typically more rigid and provides greater thermal resistance for the same thickness. Check three properties separately when selecting a product.
| Property | What the documents should establish |
|---|---|
| Thermal resistance | Find the tested or reported R-value at the planned thickness. Use the table when the rating changes with thickness. |
| Air impermeability | Verify the product qualifies at the installed thickness and provide continuous connections to the adjacent air barrier. |
| Vapor control | Check the permeance or vapor-retarder class at installed thickness and whether it fits the wall or roof design. |
For example, Huntsman lists R-3.7 per inch of aged thermal resistance for Classic Ultra Select open-cell foam. ICC-ES ESR-3835 lists R-6.8 at 1 inch, R-13 at 2 inches and R-22 at 3-1/2 inches for the evaluated ProFoam ProSeal closed-cell product. The thicknesses used to establish air and vapor performance are separate from these thermal values. Use the current instructions and approval that apply to the exact product on the job.
Application and Inspection
Use trained installers following the product's substrate, temperature, mixing, lift and cure requirements. The manufacturer establishes the maximum thickness per lift and any wait between lifts. Check continuity, thickness and adhesion before concealment, particularly near framing and penetrations. Coordinate ventilation, work-area isolation and PPE, and follow the product's re-entry and re-occupancy instructions. EPA guidance notes that these times vary and depend on cure, ventilation and cleanup. Under N1101.12.1, the installer documents spray polyurethane foam thickness and installed R-value in the insulation certification.
Choose the Assembly First
Foam can fit irregular rim and sill spaces, wall cavities, specified portions of crawl spaces and roof assemblies. Follow Michigan Table N1102.1.1 for the thermal component values. The table's R-15/19 crawl-wall entry distinguishes continuous and cavity insulation options. The vapor strategy depends separately on the location and products. Use amended R601.3 for the interior vapor control of frame walls and check below-grade conditions and other listed exceptions. Adding sheet polyethylene can reduce drying toward the interior.
For an unvented attic or enclosed rafter assembly, check all conditions of R806.5. One path uses air-impermeable insulation directly against the underside of the roof sheathing. Another uses a specified R-value of rigid board or sheet insulation directly above the deck and air-permeable insulation directly below. A hybrid can place the qualifying air-impermeable layer against the deck with air-permeable insulation beneath it. The cold-zone provision requires Class II vapor control for the air-impermeable insulation or a Class II coating or covering directly against its underside. Check the applicable condensation-control values and the separate total energy-code R-value. Confirm the intended drying path.
Thermal and Ignition Protection
R316.3 generally limits foam plastic to a flame-spread index of 75 and a smoke-developed index of 450 at the maximum intended thickness and density, using ASTM E84 or UL 723. Foam over 4 inches can use the stated test-thickness exception where its intended thickness, density and use are approved under R316.6. R316.2 covers package identification and labeling.
- Thermal barrier (R316.4). Unless an exception applies, separate foam from the interior with an approved thermal barrier. The prescriptive materials include 1/2-inch gypsum wallboard and 23/32-inch wood structural panel. Other materials must meet both the temperature transmission and integrity tests of NFPA 275.
- Service-access attic and crawl space (R316.5.3 and R316.5.4). When access is required by the respective section and entry is only for repair or maintenance, the prescribed ignition protection can substitute. Both lists include 1-1/2-inch mineral fiber, 1/4-inch wood structural panel, 3/8-inch particleboard, 1/4-inch hardboard, 3/8-inch gypsum board and corrosion-resistant steel with 0.016-inch base thickness. The attic list also includes 1-1/2-inch cellulose and 1/4-inch fiber-cement panel, soffit or backer board. A specifically approved end-use configuration tested under R316.6 can satisfy the applicable exception. Check the listing details before accepting an unprotected application or a coating.
- Sills, headers and perimeter joist spaces (R316.5.11). The thermal barrier can be omitted for the stated application at no more than 3-1/4 inches thick, with density 0.5 through 2.0 lb/ft³ and flame spread no more than 25 and smoke developed no more than 450 under ASTM E84 or UL 723. Confirm all three conditions. General foam-plastic surface-burning compliance alone does not meet this exception.
Worked Estimate — Board Feet at a Rim Joist
One board foot of foam covers 1 square foot at 1 inch of thickness. Suppose 40 feet of exposed rim is 9-1/4 inches high and will receive 2 inches of foam. The gross area is 40 × (9.25 ÷ 12) ≈ 30.83 ft². Multiply by the 2-inch thickness to get about 62 board feet of installed volume. Adjust the takeoff for actual blocking, voids and product yield. Determine installed thermal value from the selected report.
Two inches is within the thickness limit of the R316.5.11 rim-joist exception. A product with a density of 2.2 lb/ft³ does not qualify under that exception even at 2 inches. Check surface-burning evidence and the other approval paths, then include the required interior protection in the estimate.
An evaluated foam delivers R-13 at 2 inches and qualifies as a Class II vapor retarder at that thickness. Which insulation type commonly combines those properties?
Open-cell polyurethane foam
Blown cellulose
Kraft-faced fiberglass batt
Closed-cell polyurethane foam
A contractor wants to leave 2 inches of 2.2 lb/ft³ spray foam exposed in a basement perimeter joist space. No other approval or exception applies. What does the 2015 MRC require?
A single coat of standard latex paint.
An approved R316.4 thermal barrier, such as 1/2-inch gypsum wallboard.
No barrier because 2 inches is below the rim-joist thickness cap.
A sheet of polyethylene over the foam.
An above-grade framed wall has closed-cell foam and the crew proposes an interior 6-mil polyethylene sheet. What should the contractor check?
Polyethylene is prohibited anywhere foam insulation is present
The foam loses R-value wherever it touches plastic sheeting
Check the installed foam’s vapor permeance, the required interior vapor control, and whether the wall can still dry.
Polyethylene must be installed on the exterior side instead