35.1 Bracing, Bridging & Hangers

Key Takeaways

  • Under R502.7, restrain joist ends with suitable full-depth blocking, a full-depth rim or header, an adjoining stud or another detail that prevents rotation.

  • R502.7.1 bridging applies only to joists exceeding nominal 2 x 12; when triggered, solid blocking, diagonal bridging or a continuous 1 x 3 bottom strip is required at intervals not exceeding 8 feet.

  • R507.1 requires a positive deck connection. Under the 2015 table’s stated conditions, 1/2-inch lag screw spacing ranges from 30 inches on center at six feet or less to 10 inches for spans over 16 through 18 feet.

  • R502.6.2 gives the approved anchor or nominal 2x2 ledger paths for a joist into the side of a wood girder. R502.6 separately gives standard end-bearing minima and authorized alternatives.

  • For deck rotation restraint, a hanger or blocking must be at least 60 percent of joist depth when used for that purpose. A restraining rim uses the fastener count and dimensions in R507.5.1.

Last updated: November 2026

Why a Deep, Narrow Joist Needs Lateral Help

A dry dressed 2x10 is 1-1/2 inches thick and 9-1/4 inches deep, over six times as deep as it is wide. In a simple span under gravity load its top is in compression. Without restraint, a slender member can rotate and move laterally under load. Keep the compression edge and the bearing connections stable as the floor assembly requires.

Check three separate requirements. Restrain joist ends at the bearings, add intermediate bridging where R502.7.1 applies, and select a bearing or hanger detail that transfers the reaction into the support.

Lateral Restraint at Supports — R502.7

R502.7 requires joists to be supported laterally at their ends by one of the following:

  • full-depth solid blocking not less than 2 inches nominal in thickness;
  • attachment to a full-depth header, band or rim joist;
  • attachment to an adjoining stud; or
  • any other approved means that prevents rotation.

The exception sends trusses, structural composite lumber, glued-laminated members and prefabricated I-joists to the manufacturer's recommendations. In Seismic Design Categories D0, D1 and D2, lateral restraint is also required at each intermediate support.

The end detail must actually restrain rotation. A routine joist toe nail or midspan strip alone does not demonstrate that end restraint. Check the rim connection back to the plate or the approved restraint provided by the connector and adjacent framing.

Bridging — R502.7.1

The bridging rule is short and often misquoted. R502.7.1 applies to joists exceeding a nominal 2 inches by 12 inches. Those joists must be supported laterally by solid blocking, diagonal bridging (wood or metal), or a continuous 1-inch by 3-inch strip nailed across the bottom of the joists perpendicular to the joists, at intervals not exceeding 8 feet.

Two consequences decide quiz questions:

  1. A 2 x 10 or 2 x 12 does not trigger the bridging rule, because neither exceeds nominal 2 x 12. A 12-inch-deep I-joist is not governed by the section at all — the manufacturer's instructions govern, and those may require blocking at a stated interval or none at all.
  2. A 2 x 14 or deeper sawn joist does trigger it. On a 16-foot clear span that means one row at midspan, because 8 feet is the maximum distance from each bearing.

If you have seen study material cite a "depth-to-thickness ratio of 6:1" as the bridging trigger, that ratio is not in R502.7.1. The code text keys on the nominal 2 x 12 dimension. Answer the code, not the rule of thumb.

Bridging can hold joists in alignment during framing and can help distribute load when the floor assembly connects the members. Follow the selected layout. A room that feels bouncy still needs the actual span, stiffness, fastening and bearing checked.

Bridging and Blocking Methods Compared

MethodWhat it isWhere it appliesFastening
Solid blockingFull-depth lumber cut between joists, at least 2 inches nominal thick where R502.7 or R502.4 specifies itEnd restraint, separated double joists, the supported end under the applicable cantilever table, or panel-edge backing as detailedFasten blocking per its connection detail. Blocking to a sill or top plate is 8d common at 6 inches on center, or 8d box at 4 inches (Table R602.3(1), item 22)
Wood cross-bridgingPairs of diagonal wood stripsAn R502.7.1 option where bridging is triggered2-10d (3 in. by 0.128 in.) at each end, toe nailed (Table R602.3(1), item 29)
Metal bridgingProprietary metal diagonal bracingAnother R502.7.1 bridging optionPer the manufacturer's published pattern
Continuous 1 x 3 bottom stripOne strip nailed flat across the bottoms of the joists, perpendicular to themAn explicitly permitted alternative under R502.7.1 where bridging is triggeredNailed to each joist at the 8-foot maximum interval
Rim, band or full-depth headerFull-depth member nailed to joist endsOne end-restraint method under R502.7For a rim or band joist, item 26 includes three 16d common end nails. Use the applicable connection detail for a header. Deck rims used for restraint follow R507.5.1.
Manufactured hangerSteel seat and straps sized to the memberA tested connection for the specific supported member, support and loadsUse fasteners and patterns listed for the connector, including approved screw options where available

Hangers, Bearing and Ledgers

Bearing (R502.6). The standard minimum is 1-1/2 inches on wood or metal and 3 inches directly on masonry or concrete. For a sill plate used at a masonry or concrete support, use at least nominal 2-inch thickness and 48 square inches of nominal bearing area. Other paths are a 1x4 ribbon strip with the joist nailed to the adjacent stud, or an approved joist hanger. Check the applicable span-table footnotes for any increased requirement.

Opposing joists over a support need a 3-inch minimum lap with at least three 10d face nails or an equivalently strong wood or metal splice (R502.6.1). Joists framing into the side of a wood girder use approved framing anchors or a ledger strip at least nominal 2x2 (R502.6.2). A deck joist framing into a ledger or a beam uses approved joist hangers under R507.7.

Select the hanger for the supported member width and depth, support material and required capacity. Double-shear describes a fastening arrangement into both the joist and header, independent of the number of joist plies.

  • Check the model, actual joist fit and support member. Seat the joist fully and keep the end gap within the specified tolerance.
  • Use the manufacturer’s specified fasteners and fill pattern. Where the instructions allow a substitute, use its listed load and any reduction. Confirm the connector and fasteners suit the exposure.
  • Check the support itself. A hanger transfers load to its header or ledger. The supporting member and its connections must carry that load onward.

R507.5.1 requires deck joist ends and bearing locations to resist rotation. Where hangers or blocking supply that restraint, their depth must be at least 60 percent of joist depth. Where a rim supplies the restraint, secure it to each joist end with at least three 10d (3-inch by 0.128-inch) nails or three No. 10 by 3-inch wood screws.

Deck Ledger Attachment — R507

An attached deck needs a positive vertical and lateral load path into the primary structure under R507.1. Toenails and nails subject to withdrawal do not provide the prescribed attachment. If the positive connection cannot be verified during inspection, make the deck self-supporting. Michigan excludes the model R507.2.3(1)/(2) lateral-load figures and replaces model R507.2.4 with a flashing provision. Use an approved lateral-load detail under the applicable design, separately from the Table R507.2 ledger fastening.

For the prescriptive ledger route, R507.2 directs the connection to Table R507.2. Other species, grades, loadings and connections require design under R301. For 1/2-inch lag screws with up to 1/2 inch of sheathing, the on-center spacing is 30 inches for joist spans of 6 feet and less, 23 inches for 6'-1" to 8 feet, 18 inches for 8'-1" to 10 feet, 15 inches for 10'-1" to 12 feet, 13 inches for 12'-1" to 14 feet, 11 inches for 14'-1" to 16 feet and 10 inches for 16'-1" to 18 feet. The spacing row assumes deck live load 40 psf, dead load 10 psf and snow load up to 40 psf. Snow and live loads are not taken concurrently in that table. The sheathing in the stated lag row is wood structural panel or solid-sawn lumber.

Details that fail inspection:

  • The ledger must be at least 2 x 8 nominal, pressure-preservative-treated southern pine, incised treated hem-fir, or approved naturally durable No. 2 or better (R507.2.1).
  • Ledgers shall not support concentrated loads from beams or girders, and shall not be supported on stone or masonry veneer.
  • The band joist must be at least 2-inch nominal solid-sawn spruce-pine-fir or 1-inch by 9-1/2-inch Douglas fir LVL, and fully supported by a wall or sill plate below (R507.2.2).
  • Fasteners under the table must be hot-dipped galvanized or stainless steel (R507.2.3). Use the Michigan ledger placement figures and the state’s approved corrosion-resistant flashing above the ledger (R 408.30523 and R 408.30523a).

Blocking Under Partitions and at Panel Edges

R502.4 governs joists under parallel bearing partitions: they must be sized for the load, and where double joists are separated to make room for piping or ducts, the pair must be full-depth solid blocked with lumber at least 2 inches nominal at intervals not more than 4 feet on center. A bearing partition running perpendicular to the joists may not be offset from a supporting girder, wall or partition by more than the joist depth unless the joists are sized for the added load. Trace an offset partition into the joists or a bearing member before moving it.

Blocking also serves as nailing backing. R502.2.2 allows blocking for fastening panel edges or fixtures to be utility grade lumber, and Table R602.3(1) requires the floor perimeter to be supported by framing members or solid blocking where sheathing edges land.

Worked Examples and an Inspection List

Example 1 — does this joist need bridging? A 16-foot clear span framed with 2 x 12 No. 2 SPF at 16 inches on center. Under R502.7.1, bridging is not triggered, because a nominal 2 x 12 does not exceed nominal 2 x 12. End restraint is still required by R502.7. A full-depth rim with the item 26 connection at each joist is one option. Verify the restraining connection at both ends. Change the member to a 2 x 14 and one row of blocking or bridging is required within 8 feet of each bearing — at midspan on a 16-foot span.

Example 2 — ledger screws. Assume a qualifying 20-foot ledger, 12-foot joist span, 1/2-inch lag screws and no more than 1/2 inch of eligible sheathing. The table gives 15 inches maximum at exactly 12 feet. With the first and last screws 5 inches from the ends, the covered run is 240 − 10 = 230 inches. Round 230 / 15 up to 16 spaces, for 17 screws. Their uniform horizontal spacing would be 14-3/8 inches. Stagger the screws between two rows and verify the edge, end, row and band joist conditions under Michigan’s figures. The tips must extend beyond the inside face of the band joist.

Example 3 — blocking at a cantilever. Table R502.3.3(1) permits a cantilever supporting a light-frame bearing wall and roof only where the backspan-to-cantilever ratio is at least 3:1, a full-depth rim joist is installed at the unsupported end, solid blocking is installed at the supported end (waived only for cantilevers 24 inches or less in Seismic Design Categories A, B or C), and the connection resists the tabulated uplift.

Rough-framing inspection checklist:

  1. Verify end restraint and any required intermediate-support restraint under R502.7.
  2. Bridging or bottom strip at 8-foot intervals wherever joists exceed nominal 2 x 12 — R502.7.1.
  3. Hangers seated, correctly sized and installed with the model’s specified fasteners.
  4. Ledger treated, flashed, lag spacing per Table R507.2, and no toenails carrying the deck.
  5. Verify blocking where required, including separated double joists and applicable cantilever supports.
Test Your Knowledge

Under MRC R502.7.1, when does the code require intermediate bridging or blocking along a sawn-lumber floor joist span?

A

Where the sawn joist exceeds the nominal 2x12 size threshold

B

Whenever the joist span exceeds 8 feet, regardless of member size

C

Whenever joists are spaced wider than 16 inches on center

D

Only for engineered I-joists and open-web trusses

Test Your Knowledge

Which of the following satisfies the lateral restraint requirement at the ends of a floor joist under MRC R502.7?

A

Toenailing the joist to the sill plate with three 8d nails

B

Full-depth solid blocking at least 2 inches nominal, or attachment to a full-depth header, band or rim joist

C

A 1 x 3 strip nailed across the bottom of the joists at midspan

D

Mounting the joist in an unverified hanger detail with no demonstrated resistance to rotation

Test Your Knowledge

A deck ledger is being attached to a house band joist. Which statement matches MRC R507?

A

Toenails are acceptable if the ledger is pressure-treated and flashed

B

A ledger may bear on stone or masonry veneer if the lag screws are long enough

C

The attachment must be positive and must not rely on toenails or nails subject to withdrawal; where a positive connection cannot be verified, the deck must be self-supporting

D

Ledgers are permitted to carry concentrated loads from deck beams and girders