45.1 Masonry Construction Details
Key Takeaways
Under R703.8.3, a noncombustible veneer lintel requires at least 4 inches of end bearing. Steel normally needs shop-applied rust-inhibitive paint, with code exceptions for corrosion-resistant steel and protective coatings.
R606.6.1 requires support beneath at least two-thirds of each masonry wythe. Check per-course and total corbel projection separately and apply the special foundation case in R606.6.2 when used.
Table R703.8.4 sizes the cavity by backing and tie system. The wood-stud corrugated-tie detail has a nominal 1-inch airspace from sheathing to veneer. The R703.8.4.2 grouted alternative requires specified water-resistive protection.
Under R606.3.7.2, prescriptive stack bond requires horizontal steel of at least 0.0007 times the vertical wall cross section in bed joints or bond beams spaced at most 48 inches apart. Check the applicable seismic and design details separately.
Read the general first-story and 5-inch limits with the foundation-supported table exceptions. Under R703.8.2, separate exterior framing support outside D0–D2 is limited to 40 psf installed and L/600.
Foundation and Brick Ledge Details
Trace where each masonry layer transfers weight and where its cavity drains. A brick ledge supports veneer above it. Ties connect the veneer laterally to the backing. Match the ledge, wythe and cavity dimensions to the approved section and the Michigan Rule 545 veneer diagrams.
- Bearing. R606.6.1 requires support under at least two-thirds of each masonry wythe. For a 3-5/8-inch-thick wythe, that is 2-5/12 inches. Check installed tolerances and give the specified bearing across the length of the support. The stud-mounted steel angle in R703.8.2.1 separately requires two-thirds of the veneer thickness to bear on the angle.
- Room for the cavity. The R703.8.4 wood-stud corrugated tie detail uses a nominal 1-inch airspace from sheathing to veneer. Check the table for the actual tie and backing and plan for the water-resistive barrier, flashing and edge details.
- Flashing and drainage. R703.8.5 places flashing beneath the first course above finished grade and at other designated supports. Provide weeps immediately above it under R703.8.6. Coordinate the detail with final grade, including any elevation changes.
Where R606 governs, the first bed joint over a foundation is 1/4 to 3/4 inch under R606.3.1. Correct foundation alignment under the approved detail before proceeding if the starting course cannot be set within tolerance. Coordinate below-grade protection and drainage with R405 and R406 and the approved wall detail.
Corbeling a Foundation Support
R606.5 uses solid or filled masonry units and limits each step to the lesser of half the unit height or one-third of its thickness perpendicular to the wall. The cumulative limit depends on whether the wall is bonded multiwythe or a single wythe, veneer or another condition specified in R606.5.2. R606.6.2 is a particular allowance for a cavity wall or veneer on an 8-inch foundation wall. Corbel to the width of the wall above with solid or filled units, fill the space behind the corbel and limit total horizontal projection to 2 inches. Verify both the individual steps and total. For a unit 2-1/4 inches high and 3-5/8 inches thick perpendicular to the wall, the per-course cap is the lesser of 1-1/8 and about 1.21 inches, or 1-1/8 inches. Two 3/4-inch steps project 1-1/2 inches in total and pass those two projection checks. Confirm bearing and the other design conditions before using the detail.
Check R404.1.5.2 where a concrete foundation wall is narrowed to form a veneer shelf. This has its own wall thickness, vertical reinforcement and limited exception. Masonry chimney corbels use R1003.5, with different conditions from the veneer ledge.
For the prescriptive masonry foundation wall cases in R606.2.7.1, use Type M or S mortar. The ASTM C270-12a property route uses lab compressive-strength minima of 2,500 psi for M and 1,800 psi for S. Type N is common for suitable above-grade anchored veneer. An ordinary nominal 8 × 8 × 16-inch CMU commonly measures 7-5/8 × 7-5/8 × 15-5/8 inches before the joints.
Veneer ties must resist corrosion and have at least 1-1/2 inches of embedment and 5/8 inch of cover. Ordinary R703.8.4.1 field limits are 2.67 square feet per tie, 32 inches horizontally and 24 inches vertically. Check the 2-square-foot limit for the specified seismic and wind conditions and provide the supplementary ties at openings greater than 16 inches in either dimension.
| Detail | What to inspect |
|---|---|
| Foundation ledge | Bearing and cavity width, base flashing and weeps above finished grade |
| Steel veneer lintel | At least 4 inches end bearing, correct span and corrosion protection |
| Reinforced masonry lintel in Table R703.8.3.1 | At least 8 inches deep, solid grout in hollow cells, bars extended at least 8 inches into supports |
| Window sill | Outward slope and drip where detailed, flashing under and at ends and integration with the opening |
| Bond beam | Grouted course with specified reinforcement, continuity and connections |
| Pilaster and pier | Approved geometry, bearing, lateral support, anchorage and cap as applicable |
| Masonry arch | Loads, abutments, thrust and temporary centering under the design |
Lintels, Sills, Headers and Bond Beams
Lintels. Under R703.8.3, provide noncombustible support for veneer spanning an opening, with at least 4 inches of end bearing. An ordinary steel lintel uses shop-applied rust-inhibitive paint, with exceptions for corrosion-resistant steel or protective coatings. A structural masonry lintel also follows the applicable loads and R606.10.
For a 6-foot clear opening and 4 inches of bearing at each end, the minimum piece length in the example is 72 + 4 + 4 = 80 inches. Select the section separately from Table R703.8.3.1 or the approved design. With a 3 × 3 × 1/4-inch steel angle and its long leg vertical, the table allows 6 feet with no story above, 4 feet 6 inches with one and 3 feet with two. For two 6 × 3-1/2 × 5/16-inch angles the no-story-above entry is 20 feet. Read the correct row, column, and footnotes. The table also gives a reinforced masonry lintel option. Its bar extension into the support is separate from lintel end bearing.
R703.8.3.2 is a separate strengthened-opening route for spans up to 18 feet 3 inches. It uses at least 18 inches of veneer on both sides, a minimum 5 × 3-1/2 × 5/16-inch angle, at least seven days of shoring, and double-wire reinforcement extending 12 inches beyond each side with at least 12-inch laps. Select the number of reinforced joints by wire size and check the prescribed veneer height: either 3/16-inch wire in the first two bed joints or No. 9 wire in the first three. Use the figure and the height table for that detail.
Sills. Slope an exterior masonry sill outward and use the specified projection and drip. R703.4 calls for flashing under and at the ends of masonry, wood or metal copings and sills. Carry the flashing up at the ends and integrate it with the water-resistive barrier and window opening detail so water exits the assembly. Coordinate prefabricated sills and unit joints with the approved details.
Headers and bond beams. A true masonry header extends into the wall to connect wythes. A bond beam is a grouted and reinforced horizontal course. It can distribute loads or receive structural anchors when designed for that purpose. An architectural header or soldier course may be part of the facing pattern with separate load support. Under R606.3.7.2, prescriptive stack bond uses at least 0.0007 times the vertical wall cross-sectional area in horizontal steel in bed joints or bond beams spaced at most 48 inches apart. Check applicable seismic details separately.
Pilasters and piers. A pilaster thickens or projects from a wall. A properly designed pilaster can provide horizontal lateral support by shortening the wall's span between supports under R606.6.4. A pier carries concentrated loads. Isolated hollow masonry foundation piers under R404.1.9 have an 8-inch nominal minimum thickness, a nominal length no greater than three times thickness and a nominal height no greater than four times thickness when unfilled. The specified solid filling allows up to ten times thickness. R404.1.9.1 also requires the applicable cap detail. Check footing, bearing and anchorage with the design. For isolated piers supporting beams or girders, also check the applicable R606.7 geometry and conditions.
Arches and keystones. A structural masonry arch transfers compression to its abutments, which must resist lateral thrust as well as vertical reaction. The keystone is the crown unit in a traditional arch of voussoirs. The whole arch and its supports carry the loads. Install the specified centering and remove it only when the arch and any required surrounding masonry can support all imposed loads. A decorative facing pattern over a concealed lintel has a different load path. R606.10 addresses designed masonry arches as a method of supporting masonry over openings.
Bond patterns. Running bond normally offsets head joints at least one-quarter of the unit length under R606.3.7. A half-unit offset is common. If the offset is smaller, follow the stack-bond requirement. Common bond uses periodic header courses, English bond alternates header and stretcher courses, and Flemish bond alternates headers and stretchers within a course. Verify overlap, ties and reinforcement rather than inferring structural performance from the visible pattern.
Under 2015 MRC R703.8.3, what minimum end bearing is required for the noncombustible lintel over an opening in anchored masonry veneer?
2 inches
4 inches
6 inches
8 inches
For a veneer wythe bearing on the stud-mounted steel angle under 2015 MRC R703.8.2.1, what minimum fraction of its thickness must bear on the angle?
One-third
One-half
Two-thirds
The full unit thickness