8.3 Renovation Scope and Proposed Construction

Key Takeaways

  • Apply the five-year threshold and the newer-addition rule in Division A 1.3.3.3B. Then distinguish the existing portion, an extension and affected building systems.

  • Basic renovation depends on the permitted scope and retention of performance, with a Fire Code condition for Group B3, hotels and retirement homes.

  • Extensive renovation has distinct tests for new structural and fire-resistance elements, barriers to access, sprinklers and retirement homes.

  • Part 7 can apply to affected plumbing. Existing septic tank work and vertical separations for sewage systems have specific Part 8 requirements.

Last updated: November 2026

Determine the applicable scope

Division A 1.3.3.3B. generally applies Part 11 to the design and construction of an existing building or part that has been in existence for at least five years. Sentence (2) applies Part 11 to the entire building where a building at least five years old includes an addition less than five years old. Distinguish that existing addition from a proposed extension. Under 11.3.2.1., Part 11 applies to the existing portion of a building being extended, and other Parts govern the proposed extended portion. Construction on a newer building outside Part 11 still needs the applicable Code analysis. The reach of changed work, and any change of use, have their own rules. Part 10 separately permits particular substitutes in certain buildings under five years.

Under 11.1.1.2., a building system is a set of elements or components forming a complete major division of construction. For example, a partition system, a foundation system or a fire alarm and detection system can be the affected system. Article 11.1.2.1. calls for compliance with Section 11.3 for proposed work, plus performance evaluation and any required compensating construction under Section 11.4. An existing system that is materially altered or repaired must at least maintain the building’s previous performance under 11.3.1.1. A new or extended system generally follows other Parts under 11.3.1.2., subject to 11.3.3.1. and 11.5.

Identify the type and extent of the work

WorkRule to apply
Reuse, relocation or extension of the same or similar components11.3.3.1. can apply where retaining specified existing features and maintaining performance, without the adverse impacts listed in the article. Work for Group B, Division 3, a hotel or a retirement home must also conform to the Fire Code for this route.
Substantial removal and installation of new interior walls, ceilings, floor or roof assemblies11.3.3.2.(1) requires the structural and fire-resistance elements to comply with the other Parts. The accessibility and sprinkler sentences each have distinct conditions.

For example, relocating a non-load-bearing door using similar components can fit basic renovation if the work retains the relevant feature and does not adversely affect warning and evacuation systems, fire separations or structural adequacy, or create an unhealthy environment. Substantially removing partitions and installing new partitions raises the extensive renovation rule. A finish change alone does not establish the substantial-removal premise.

Check accessibility and sprinklers separately

In an existing suite, 11.3.3.2.(2) checks installation of new interior walls or floor assemblies, suite area greater than 300 m², and one of the specified location conditions. For the first, the existing floor and adjacent ground differ by at most 200 mm. For the second, a normally occupied floor is accessible by the specified passenger elevator or platform-equipped device from an entrance storey meeting the 200 mm limit. Apply Section 3.8 subject to Section 11.5. For other suites with new interior walls or floor assemblies, Sentence (3) can require its specified provisions, subject to its exclusions and Section 11.5. Exactly 300 m² misses the area condition in Sentence (2). It does not settle Sentence (3).

Under 11.3.3.2.(4), the storey undergoing the stated substantial removal and replacement must be sprinklered if it will contain Group C and the building is over three storeys. Sentence (5) requires both conformity with 3.2.2.50.(1)(a)(ii) and dwelling units with means of egress conforming to 3.3.4.4.(8). Sentence (6) requires sprinklers, specified voice communication where the cited condition applies, and self-closing doors for the described retirement-home work, subject to the exterior-door exception.

Suppose a renovation installs new walls in an existing 325 m² suite on a normally occupied upper floor. An elevator reaching that floor can support the second location route only from an entrance storey meeting the 200 mm condition. If the sole entrance to that elevator is on a storey 260 mm above adjacent ground, that route does not apply on those facts. Check the other location route and the separate rule for suites in Sentence (3) before deciding which accessibility provisions apply.

Apply the plumbing and sewage treatment

Under 11.3.4.1., Part 7 applies to plumbing in an extension and the affected portions and plumbing adversely affected by the work. Under 11.3.5.1., material alteration, repair or replacement of an existing septic tank brings its construction under Part 8. Under 11.3.5.2., for an extension, material alteration or repair of a sewage system, Part 8 vertical separation from the water table applies to the existing portions as well as the extended, altered or repaired portions.

Primary references

2024 Compendium, Division A · 2024 Compendium, Division B Part 11 · 2024 Compendium, Division B Part 10 · 2024 Compendium, Division C Part 2

Loading diagram...
Routing Work on an Existing Building
Test Your Knowledge

A building has existed for eight years and one existing addition has existed for two years. How does Division A 1.3.3.3B.(2) apply to this building?

A

Part 11 applies to the entire building for that application rule.

B

Part 11 only applies to the two-year-old addition.

C

No Part 11 analysis applies because the building is partly newer.

D

Part 11 applies only to the original eight-year-old portion under this sentence.

Test Your Knowledge

A building within Part 11 is being extended. Under 11.3.2.1., how is the proposed extended portion treated?

A

It uses Part 11 alone because its foundation is next to an older building.

B

It complies with the other applicable Parts, while Part 11 applies to the existing portion.

C

It must be evaluated only under Part 10 whether or not use changes.

D

It is exempt from the Code during the renovation.

Test Your Knowledge

A 320 m² existing suite has new interior walls installed. Its floor elevation is exactly 200 mm from adjacent ground. What applies under 11.3.3.2.(2), subject to Section 11.5?

A

The suite misses the area threshold.

B

The location fails because the difference must be less than 200 mm.

C

A building permit automatically substitutes for accessibility requirements.

D

The stated facts trigger Section 3.8 for the proposed construction in the suite.

Test Your Knowledge

A four-storey existing building undergoes substantial removal and replacement of interior walls on a storey that will contain Group C. The exception in 11.3.3.2.(5) does not apply. What does Sentence (4) require?

A

No sprinklers if fewer than ten occupants are expected.

B

Sprinkler only the roof assembly.

C

Sprinkler the storey undergoing that work.

D

Sprinkler every storey solely because of Sentence (4).