2.1 Pressure Sensing Elements & DP Measurement
Key Takeaways
Absolute pressure references vacuum. Vented gauge pressure references local atmosphere. Differential pressure is the signed difference between the designated high and low ports.
Bourdon tubes, bellows and diaphragms produce mechanical movement. Pressure transducers can convert deformation into a resistance or capacitance change.
A DP transmitter’s calibrated span, static working pressure, and applicable overpressure limits describe different conditions.
Verify a true zero differential at the sensor using the installed manifold instructions. The output at zero differential depends on the configured range and transfer function.
Identify the pressure reference
Pressure is normal force divided by area, . One pascal (Pa) is one newton per square meter. One bar is 100 kPa, about 14.504 psi. The pressure reference and engineering unit are separate choices.
| Reference | Zero condition and use |
|---|---|
| Absolute | A perfect vacuum is 0 psia. Use absolute pressure in the ideal-gas relation and other calculations that require pressure relative to vacuum. |
| Vented gauge | Atmospheric pressure at the gauge reference port is 0 psig. Pressure below local atmosphere reads negative on this scale. |
| Differential | Equal pressure at the transmitter's H and L ports gives zero differential. The reading is , and can be negative when the pressure at L exceeds the pressure at H. |
For a vented gauge, . If local atmospheric pressure is 13.8 psia and the vessel reads 30.0 psig, the vessel is at 43.8 psia. The standard atmosphere is a defined 101.325 kPa, about 14.696 psi, while actual atmospheric pressure varies. For a DP filter installation, if the upstream H tap is at 64 psig and downstream L is at 60 psig, the difference is +4 psi at the taps. Pressure heads in the legs can alter what reaches the sensor.
For a static column of uniform density, the pressure increment from top to bottom is . Use the liquid reference named for the instrument. A pressure of one psi is about 27.681 inH₂O at 4 °C or 27.71 inH₂O at 60 °F. One psi is about 2.036 inHg at 0 °C. The NIST conversion table lists these reference conditions.
Choose the pressure element and signal
| Element | How it responds | Selection example |
|---|---|---|
| Bourdon tube | Pressure inside a curved tube changes its cross-section and tends to straighten the tube. Tip motion can move a pointer through a linkage. | Use a compatible gauge with the needed range and pressure rating. Spiral and helical designs use several turns. Their range and movement depend on geometry and construction. |
| Bellows | Pressure difference across a corrugated flexible wall produces axial motion. | For a simple spring-restored model, force is approximately and spring deflection is . Check the bellows and spring ratings for the actual gauge or switch. |
| Diaphragm or capsule | A flexible diaphragm deflects under differential pressure. A capsule pairs diaphragms to provide useful motion at low pressures. | A properly rated compound capsule gauge can measure low positive and negative draft in a compatible gas. |
| Diaphragm seal and fill system | A process-side diaphragm transmits pressure through fill fluid to the sensor, directly or through a capillary. | Check wetted materials, temperature, pressure, fill fluid, and any approvals for the actual process. Elevation and temperature can affect the system response. |
See WIKA’s Bourdon gauge explanation, capsule gauge data and Rosemount seal-system options. Elastic elements return toward their original position when unloaded within their design limits. Select for the media, temperature, range, vibration and pressure excursions.
In a strain-gage transducer, a strained sensing element changes resistance. A bridge converts resistance changes into a differential voltage. In an ideal full bridge with two and two arms wired to add, the magnitude is . A quarter bridge gives a different relationship. A TE Connectivity piezoresistive design uses resistors on a silicon diaphragm, whose strain changes the bridge output. The electronics can compensate, amplify and digitize that output.
In the Rosemount 3051ND capacitive design, isolation diaphragms transfer pressure through fill fluid to a central sensing diaphragm. As the central diaphragm moves toward one fixed plate and away from the other, one capacitance increases and the other decreases. In a simplified symmetric cell, . If the nominal gap is and movement is toward the L plate, the gaps are on L and on H. The ideal ratio is . Actual devices are characterized and compensated for temperature and pressure effects. The electronics can report the calibrated result as analog current and digital data, depending on the model.
Separate line pressure, range and overpressure
The configured measurement range sets the lower and upper range values. Their difference is the span. A 0–100 inH₂O range at 4 °C convention has a span of about 3.61 psi, even if the assembly is installed on a much higher pressure line. The maximum working pressure describes allowable normal operation under specified conditions. The lowest applicable rating of the transmitter, manifold, seals and other pressure-containing components can limit the assembly. Check the separately stated overpressure limits and conditions before assuming the cell can tolerate a blocked tap, incorrect lineup or reverse differential. A rated Rosemount 3051S option can still experience a shift after mis-valving exposes one side to full line pressure. Consult the 3051S specifications.
Follow the pressure through the impulse lines
For a conventional Rosemount 3051S flow hookup, sections 3.3.2–3.3.5 of the installation manual show the following examples.
- Liquid. Take pressure from the side of a horizontal pipe and typically mount beside or below the taps. Pitch the lines so gas can return to the process and avoid high points.
- Gas. Take pressure from the top or side and typically mount beside or above the taps. Pitch the lines so condensate drains back to the process and avoid low points.
- Steam. Use the specified water-filled impulse arrangement. Mount below the side taps in the illustrated setup and keep the head contributions equal where the design calls for equal legs.
The cited model recommends at least 1 in/ft of pitch for the liquid and gas cases. Use the actual installation drawing. A leak, plugged leg, trapped gas in a liquid line or unequal liquid columns can bias sensed differential. For example, if one water-filled leg adds 10 additional inches of vertical water head to the L side and the tap differential is +25 inH₂O at the same reference condition, the transmitter senses +15 inH₂O. Removing or accounting for the extra head addresses the physical cause.
Distinguish a static zero check from isolation for service
A three-valve manifold has separate H and L process block valves and an equalizer between their transmitter-side connections.
H process tap L process tap
| |
[H block] [L block]
| |
+----------[Equalizer]----------+
| |
H port L port
For the 3051S coplanar arrangement in Emerson’s manual, section 3.4.5, both blocks are open and the equalizer is closed in service. Starting in that state, the published static-line-pressure zero procedure closes the L block, then opens the equalizer while leaving the H block open. Verify the allowed instrument state and observe the digital DP at equal pressure. Analog current depends on the programmed range and transfer function. With a linear −20 to +20 inH₂O range, zero DP corresponds to 12 mA. Compare the readings with the procedure and tolerance before changing trim. To restore the cited in-service lineup after the check, close the equalizer before reopening the L block.
The initial startup lineup and depressurization steps come from the installed design and approved procedure. For example, the Annubar reference manual gives distinct commissioning procedures for liquid, gas and steam. Its three-valve steam water-leg startup calls for filling and checking the legs before restoring the service lineup. Some five-valve arrangements use one equalizer and two vent/test valves. The natural-gas configuration shown in the same manual has two equalizers, a center vent and its own sequence. Confirm the ports, expected valve states and approved vent routing for the medium. For maintenance that opens containment, apply the required isolation, address retained pressure and verify the safe state under the site procedure and applicable OSHA energy-control provisions. Equal pressure on both sides of the sensor can occur while both sides are still pressurized.
A Rosemount 3051S coplanar three-valve manifold is in normal service. Which valve changes set up the documented static-pressure zero check?
Open the equalizer while both process blocks remain open.
Close the L block, then open the equalizer with the H block still open.
Open both process blocks and vent both sides as the first step.
Close the H block and leave the equalizer closed.
For a local mechanical gauge reading a compatible dry furnace draft between −5 and +5 inH₂O, which instrument is a suitable candidate?
A gauge with a 1,000 psig full scale selected solely for high-pressure tolerance.
An absolute gauge calibrated only around 100 psia.
A compound low-pressure capsule gauge with a suitable draft range and ratings.
A deadweight tester selected as the normal local process display.
A DP instrument has a 0–100 inH₂O calibrated range and a 4,500 psig maximum working pressure. Which fact must you establish before assessing a one-sided overpressure event?
The permitted overpressure conditions and component ratings for the installed assembly.
Whether the configured 100 inH₂O span equals the body burst pressure.
Whether the transmitter automatically opens an internal relief valve.
Whether a 4 mA reading proves there was no damage.