4.2 Current Loops (4–20 mA), Pneumatic Signals (3–15 psi) & Signal Conversion Formulas
Key Takeaways
A 4–20 mA series loop carries the same current through every element while the circuit can supply the required voltage at that current.
In linear examples, 4 mA or 3 psig maps to the low endpoint. A live zero can help the receiver distinguish that endpoint from signal loss.
Diagnostic current and measurement saturation depend on configuration. Use the receiving system’s documented detection settings.
Convert a linear measurement by mapping its fraction of input span to the same fraction of output span.
Check loop voltage at the highest required current and the actual operating conditions. Verify any separate communication or installation limits.
Match the signal to the configured range
For a specified linear analog signal, the low and high output values correspond to two configured input values. Common ranges are 4–20 mA DC and 3–15 psig. The ISA50 committee identifies its 4–20 mA signaling standard. A Fisher 846 I/P transducer is an example of an instrument that can convert 4–20 mA to a pneumatic range of 3–15 psi. An I/P takes current and delivers pressure. A P/I such as the Moore Industries PIT takes pressure and outputs current.
The 3–15 psig range has a 12 psi span. Be clear about the two units and configured endpoints. Under NIST SP 811 conversion factors, 3–15 psig is approximately 20.68–103.42 kPa gauge. A model’s nominal 20–100 kPa or 0.2–1.0 bar range may be documented alongside 3–15 psig. Use the units and endpoints specified for the actual setup. Select dry, clean supply air for the equipment and project. ISA-7.0.01 addresses instrument air quality.
The same DC current flows through each element in a closed series loop. A transmitter can maintain the commanded current while it has adequate terminal voltage. Cable and connection resistance still consume part of the voltage budget. In one receiving circuit, the current flows through a 250 Ω burden resistor. By , 4–20 mA through it produces a measured drop of 1–5 V. The voltage input measures across the shunt. A dedicated current input can have its own burden. Check its documentation and the actual signal terminals before adding any resistor.
2. Distinguish live zero, saturation and diagnostic current
A 4–20 mA range maps 4 mA to the low endpoint of the configured measurement. A 3–15 psig pneumatic range similarly has a 3 psig low endpoint. A broken conductor or lost supply in a powered series current loop can leave little or no current at the receiver. The receiver can distinguish that from a valid 4 mA low-end reading, although low current alone cannot identify the exact cause.
NAMUR’s NE 43 revision notice explains the distinction between the measurement signal and the standardized failure information. The 2021 revision addresses detection margins and startup behavior. The Rosemount 3051S manual, table 2-4 lists separate saturation and failure alarm values by configuration. For the stated NAMUR-compliant 4–20 mA configuration, low and high saturation are 3.8 and 20.5 mA, and the published alarm limits are at or below 3.6 mA on fail-low and at or above 22.5 mA on fail-high. Default and custom options can differ. A saturated signal can indicate that the measurement exceeded the mapped range. Use the transmitter’s diagnostics and receiving-system quality to decide how to use the value.
Set and verify the transmitter alarm, loop power and receiver detection according to the approved design. Check how the system handles the fault signal, signal loss and initialization. An off-scale current by itself cannot determine which process action will occur.
Calculate the fraction of span
With explicitly paired low and high endpoints, define input span as high input minus low input. For a linear mapping, calculate
Here is input, is output and is the percent of span. In a direct 4–20 mA mapping, in mA. For direct 3–15 psig mapping, in psig. The table uses an ideal 250 Ω burden and the stated linear ranges.
| Percent of span | Loop current | Voltage across 250 Ω | Pneumatic signal |
|---|---|---|---|
| 0% | 4 mA | 1 V | 3 psig |
| 25% | 8 mA | 2 V | 6 psig |
| 50% | 12 mA | 3 V | 9 psig |
| 75% | 16 mA | 4 V | 12 psig |
| 100% | 20 mA | 5 V | 15 psig |
- Temperature to current. For −50 to +250 °F and an input of 130 °F, . The current is 13.60 mA.
- Current to head pressure. At 15.20 mA, . For a DP input with a 0–120 inH₂O calibrated range, that is 84.0 inH₂O. This unit is pressure. A vessel level calculation may need liquid density and installation head.
- Pressure to current. For a linear P/I setup with input 3–15 psig and output 4–20 mA, 10.20 psig gives and an output of 13.60 mA. In the opposite I/P direction with the same endpoints, 13.60 mA gives 10.20 psig.
Check available voltage at the transmitter
For a simple loop-powered transmitter and series loads, the supply voltage must cover the transmitter’s required terminal voltage and the drops through the other elements. If an element requires a specified fixed drop, subtract that voltage separately. Treat wire and resistive burdens with Ohm’s law. Follow the actual loop diagram for powered isolators, references and barriers. A voltage budget alone cannot approve an intrinsically safe installation.
+ supply ── loop-powered transmitter ── receiver burden ── supply return
include all outbound and return wire resistance
Suppose a 24.0 V supply and the assumed transmitter require at least 11.0 V at its terminals at 20.0 mA. The series receiver is 250 Ω and a second series element is 280 Ω. Assume both are resistive at the test condition. The permitted total series burden for this calculation is Ω. The field cable allowance is Ω for both conductors together. If the cable pair is specified at 13.0 Ω per 1,000 ft of route length, that is about 9,230 ft for this resistive 20 mA calculation. At 22.0 mA, a 650 Ω burden would drop 14.3 V, leaving only 9.7 V at the transmitter. The required range and fault signaling, cable limits and worst-case supply can give a lower usable length. Use the actual manufacturer’s load curve and wiring limits. See the Rosemount 3051S data sheet’s power and load figures, which also give documented communication conditions for applicable configurations.
Identify how the power and the signal are connected
| Example arrangement | Follow the wiring |
|---|---|
| Two-wire loop-powered | The same pair carries operating power and the regulated current signal. A Micro Motion 4200 Coriolis transmitter is one example. Check its operating voltage and load. |
| Three-wire with shared return | The instrument has a power lead, a signal lead and a common return serving both circuits. Follow the diagram for the actual reference, current direction and voltage limits. |
| Four-wire with separate power | Two connections power the device and two carry the current signal. A separately powered transmitter may still offer either an active or a passive output. |
The Rosemount 8750W has a separate operating supply and a selectable internally or externally powered analog output. Use an active current output with a compatible receiving burden. A passive output needs an appropriate current-loop supply path, which may be in the receiving module. Verify isolation, common and equipment bonding from the actual wiring requirements.
A linear 4–20 mA temperature transmitter covers −20 to +140 °C. Under normal measurement it sends 16.80 mA. What temperature does that current represent?
80.0 °C.
96.0 °C.
108.0 °C.
112.0 °C.
At the specified 20.0 mA calculation point, a 24.0 V supply feeds a transmitter needing 11.5 V, a 250 Ω receiver and a 320 Ω resistive series element. What total outgoing-plus-return wire resistance fits this voltage budget?
55.0 Ω.
120.0 Ω.
375.0 Ω.
625.0 Ω.
A Rosemount 3051S current-loop device uses the manufacturer’s NAMUR-compliant settings and is configured for fail-low. What current limit distinguishes its stated failure output from its low saturation?
Exactly 4.00 mA.
Exactly 3.80 mA.
At or above 22.50 mA.
At or below 3.60 mA.