1.9 Instrument Wiring, Grounding & Shielding
Key Takeaways
Use the wire schedule, terminal IDs and actual cable markings to establish conductor function.
Protective equipment bonding provides a fault-current path. Signal common defines a measuring reference.
Specify cable routing, twisting and shielding for the noise mechanism and equipment.
Follow the particular shield termination design. Analog instrumentation and industrial buses can specify different arrangements.
Identify each conductor by its function
NCCER module 12306 covers grounding and shielding, wire identification and induced noise. Begin with the instrument tag, cable ID and loop drawing. Trace the conductor from the source terminal through any junction box to the receiver. Compare both endpoint labels, the pair number and polarity with the wiring schedule. A cable can have several colored pairs, numbered wires, overall and individual shields, or drain wires. Colors and drain arrangements vary by product and project. Resolve discrepancies in the drawing and terminal labels before moving a wire.
Conductor size in American Wire Gauge (AWG) is one selection parameter. For the same material and length, a larger cross-sectional area gives lower resistance. In the AWG convention a lower number represents a larger conductor size. Compare voltage, temperature, insulation, installation and environment ratings as well as the conductor size. For instance, Belden’s 8761 data sheet lists a stranded 22 AWG pair, polyethylene conductor insulation, an overall foil shield with a drain, a PVC jacket and a 300 V CM/AWM rating under the specified listings. Its companion 87761 data sheet identifies a distinct jacket and plenum listing. Choose from the approved cable schedule and applicable requirements for that route. Alternate cables of the same AWG can have different temperature, environment or listing limits.
Follow three distinct paths on the wiring drawing
| Path | What it does | Typical identification |
|---|---|---|
| Equipment grounding and bonding | Connect exposed equipment as required to maintain a permanent, continuous and effective fault-current path. | Grounding conductor, cabinet or frame bond, designated grounding terminal |
| Signal and reference | Carry the measurement and its return or define the measurement reference. | Pair polarity, input common, isolated or differential input |
| Cable shield and drain | Intercept unwanted coupling and connect the shield system at the specified locations. | Overall or individual shield, drain wire, shield clamp or designated terminals |
A metal cabinet, mounting panel and protective conductor can be part of one bonded system. The exact requirements depend on the installed equipment. A device can have an intentionally isolated signal reference, a grounded supply common, or a differential input with a limited accepted common-mode voltage. Connecting a signal reference to an extra chassis point can create a new current path. Preserve the approved protective connections when investigating signal noise. See OSHA’s U.S. general-industry grounding provisions and the Rockwell wiring and grounding guidance.
Recognize how interference reaches a signal
- Capacitive coupling transfers a disturbance from changing voltage through the electric field between nearby conductors. Separation, an appropriate shield and its specified termination reduce this path.
- Inductive coupling transfers a disturbance caused by changing current and magnetic field. Twisting a pair reduces the effective loop area exposed to an external field. Route sensitive signals away from high-current and switching conductors as specified.
- Common impedance allows current in a shared return segment to produce a voltage drop that affects more than one circuit. Trace and separate the designed load and instrument paths where the drawings require it. Ground potential differences can also drive current through multiple conductive connections.
Inspect cable routing near drives, switched loads and power conductors. Where an approved plan calls for crossing incompatible routes, follow the specified separation and crossing arrangement. Compare noise onset to equipment operation and check the signal at more than one point in the authorized test. Coupling can occur through the supply as well as the signal pair.
Worked shield diagnosis
A Rosemount 3051 analog loop starts fluctuating when a drive runs. Its drawing calls for the shield to be continuous through a junction box and terminated at the supply end. A field inspection finds the drain clamped to the instrument body in addition to the intended supply-end termination. With the approved isolation and test procedure, compare the installation with the drawing. Insulate the drain at the transmitter as specified and preserve the separate housing bond. Inspect the route and verify the input signal with the drive operating under authorized test conditions. The coincident noise identifies when to measure, and repeating the check tests whether the correction helped. See the Rosemount 3051 wiring instructions.
A network can specify different shield treatment. The Siemens PCS 7 PROFIBUS compendium describes connecting the cable shield at both ends with suitable potential equalization. Trace the governing design for each cable before applying a connection practice.
Two 22 AWG shielded cables have different jacket and installation listings. What determines whether one can replace the other on a specified route?
The wire color at the panel.
The shield coverage alone.
The applicable cable listings, environment and approval for that installation.
The conductor size by itself.
A technician moves from an analog loop with a supply-end shield termination to a PROFIBUS segment documented for both-end termination. Which reference governs work on the segment?
The analog-loop drawing, because both cables have shields.
Cable color if it matches the analog cable.
The analog device’s terminal labeling.
The approved network drawing and equipment instructions, including their potential equalization requirements.
Which mechanism best describes a changing motor current creating a magnetic field that induces voltage in a nearby signal loop?
Rectification
Inductive coupling
Analog scaling
A static voltage drop through a shared return