7.3 Valve Sizing, Flow Characteristics (Cv) & Cavitation/Flashing Mitigation

Key Takeaways

  • Use the U.S. Cv relation for turbulent, nonchoked Newtonian liquid flow under its stated assumptions. Use the applicable complete method for liquids with choking or fittings and for compressible service.

  • Read the manufacturer’s coefficient versus travel and installed flow data. Installed flow depends on how the system and valve share available differential pressure.

  • At fixed temperature, cavitation can occur when local pressure falls below vapor pressure and then recovers above it. In flashing, vapor persists below the vapor pressure downstream.

  • Use the named trim’s recovery data for limiting capacity. Select pressure staging for suitable cavitating service and erosion mitigation for flashing service.

Last updated: November 2026

Valve Sizing, Flow Characteristics, Cavitation and Flashing

Start with the required minimum, normal and maximum flow and the pressure available across the valve at each condition. Then check whether a candidate trim can regulate over that range and whether its materials, pressure rating, actuator and shutoff match the service.

Calculate the required flow coefficient

The U.S. coefficient CvC_v uses US gallons per minute of reference water for a pressure drop of 1 psi. The value can be stated at a particular travel. Rated CvC_v applies at rated travel. The metric KvK_v uses cubic metres per hour of reference water at a pressure drop of 1 bar. The Spirax Sarco capacity reference gives Cv≈1.156KvC_v\approx1.156K_v or Kv≈0.865CvK_v\approx0.865C_v. Confirm the units when comparing catalog values.

For turbulent, nonchoked Newtonian liquid flow with no attached-fitting correction, the U.S. calculation simplifies to:

Cv=QSGΔP,Q=CvΔPSG,ΔP=SG(QCv)2.C_v=Q\sqrt{\frac{SG}{\Delta P}}, \qquad Q=C_v\sqrt{\frac{\Delta P}{SG}}, \qquad \Delta P=SG\left(\frac{Q}{C_v}\right)^2.

Use QQ in US gal/min, ΔP=P1−P2\Delta P=P_1-P_2 across the valve in psi, and fluid specific gravity SGSG at flowing conditions relative to the reference water density. Subtract pressures on the same basis. For comparison with vapor or critical pressures use absolute pressures. The full IEC 60534-2-1 sizing method accounts for conditions such as attached fittings, liquid choking or non-turbulent flow. Gas and steam use compressible-flow sizing. Slurry selection requires application-specific methods.

Worked liquid sizing example

A hydrocarbon service requires 450 US gal/min, with SG=0.81SG=0.81, P1=145P_1=145 psig and P2=120P_2=120 psig for the specified case. Assume nonchoked turbulent liquid flow and that attached fittings do not require correction. The valve differential is 25 psi. Then:

Cv=4500.81/25=450(0.9/5)=81.C_v=450\sqrt{0.81/25}=450(0.9/5)=81.

If the two hypothetical trims have rated coefficients of 54 and 115 at full travel, the 54 cannot meet this case under the stated assumptions. The 115 has enough nominal capacity. The required 81 is about 70.4% of 115. Use the actual travel curve to find its position. Then check the minimum and normal cases, usable travel, differential limits, noise, shutoff, and actuator sizing. Valve line size alone does not establish its coefficient.

Compare inherent and installed flow

The inherent characteristic relates travel to flow under fixed pressure drop and fluid conditions. The installed characteristic includes the pressure changes in the actual system.

Inherent characteristicWhat changes with travel
LinearEqual increments of travel give roughly equal increments of coefficient.
Quick openingMuch of the flow change occurs near the low-travel end.
Equal percentageEqual travel increments multiply the existing coefficient by the same factor over the specified modulating range.

For an ideal equal-percentage trim over its characterized range, Cv=Cv,min⁡RxC_v=C_{v,\min}R^x, with R=Cv,max⁡/Cv,min⁡R=C_{v,\max}/C_{v,\min} and xx from 0 to 1 across that range. At R=50R=50, a 0.10 increase in xx multiplies the coefficient by 500.10≈1.47950^{0.10}\approx1.479, a 47.9% increase. The model's lower coefficient is the minimum controllable value in that range. It does not represent the seat leakage at shutoff or guarantee a 50:1 operating flow ratio after installation.

In a simple constant-head system with pipe loss approximated by kQ2kQ^2, the available pressure drop divides between the valve and piping. For water with SG=1SG=1 in the U.S. equation and 16 psi total available differential, assume k=0.0003k=0.0003 psi per squared US gal/min. With full-travel Cv=100C_v=100, 16=(0.0003+1/1002)Q216=(0.0003+1/100^2)Q^2 gives 200 US gal/min. The valve takes 4 psi and the piping takes 12 psi. In this example the full-open valve authority is 4/16=0.254/16=0.25. An ideal linear trim at half travel has Cv=50C_v=50. The same balance gives about 151 US gal/min, nearly 76% of the full-open flow. An equal-percentage curve can sometimes offset this shape change. Compare the actual installed curves, including the pump curve and any other changing head.

Read the liquid pressure profile

As liquid accelerates through the restriction, static pressure falls and often reaches a minimum near the vena contracta, the narrow section of the jet. As the flow expands downstream, some static pressure can recover. Compare the local pressure and downstream pressure with the fluid's vapor pressure PvP_v at the relevant temperature.

Pressure behaviorInterpretation
Local pressure drops below PvP_v and subsequently recovers above it.Vapor can form and collapse. This is cavitation. Rough pitting, vibration and noise can support a diagnosis.
Pressure drops below PvP_v and the downstream pressure stays below it.Vapor persists downstream as a two-phase stream. This is flashing. Flow-path erosion often has a smoother appearance.

A drop across the valve is different from the local drop into the jet. A high-recovery valve can have a deep local pressure depression even with a modest measured upstream-to-downstream drop. Use the liquid pressure recovery factor FLF_L for the actual trim and travel. For liquid choking with no attached fittings, the Fisher sizing bulletin gives:

ΔPchoked=FL2(P1−FFPv),\Delta P_{\text{choked}}=F_L^2(P_1-F_F P_v),

where FFF_F is the liquid critical pressure ratio factor. In the sizing calculation, use the lesser of this limit and the available pressure drop. For FL=0.80F_L=0.80, FF=0.90F_F=0.90, P1=100P_1=100 psia, Pv=20P_v=20 psia and P2=40P_2=40 psia, the actual drop is 60 psi but the limiting drop is 0.64(100−18)=52.480.64(100-18)=52.48 psi. This calculation limits the predicted capacity increase when reducing P2P_2 further at fixed inlet conditions and travel. The factors are specified for this example. Choking does not supply a damage threshold and damaging cavitation can begin before choking.

A suitable multistage or multihole trim manages local pressure and energy dissipation in cavitating service. Use the manufacturer's staging and solids constraints. For example, Fisher specifies Cavitrol III for clean cavitating liquids and DST for specified dirty-service applications. A fixed division of total pressure drop into equal pieces does not determine the minimum pressure in each stage. If downstream service pressure remains below vapor pressure, flashing persists. Evaluate body shape, discharge path, materials and downstream piping to manage erosion. Reducing the liquid temperature or increasing the downstream pressure, where the process design permits, changes the conditions that produce flashing.

Test Your Knowledge

A turbulent, nonchoked liquid service needs 360 US gal/min at a flowing specific gravity of 0.64. The valve inlet is 160 psig and its outlet is 124 psig. Assume Newtonian flow and no attached-fitting correction. What Cv is required?

A

6.4

B

48.0

C

60.0

D

75.0

Test Your Knowledge

A water system provides 16 psi across a valve and its piping. Pipe differential is 0.0003 × Q² psi, with Q in US gal/min. For a linear trim with Cv = 100 at full travel, the installed full-travel flow is 200 US gal/min. At one-quarter travel Cv = 25. What percentage of the installed full-travel flow will the valve pass under the same simplified nonchoked model?

A

25%

B

12.5%

C

75%

D

About 46%

Test Your Knowledge

Liquid enters a valve at a steady temperature. At this temperature the vapor pressure is 40 psia. Static pressure falls to 32 psia at the vena contracta and recovers to 55 psia downstream. Which mechanism can occur in this pressure profile?

A

Cavitation, because vapor can form locally and collapse where pressure recovers.

B

Flashing through the downstream pipe, because the downstream pressure is below 40 psia.

C

Water hammer, because steady downstream pressure recovery indicates a transient from rapid closure.

D

Gas choking, because every liquid pressure recovery above vapor pressure is a sonic limit.