3.2 Mechanical, Electrical & Non-Contact Level Technologies

Key Takeaways

  • A float follows a selected liquid surface or interface. A suspended displacer reports a change in buoyant load.

  • A fully submerged interface displacer responds to the difference in liquid densities. Guided-wave radar locates an interface from the reflected microwave signals.

  • Capacitance, ultrasound and radar respond to different physical properties. Check probe insulation, echo quality and the usable span for the selected device.

  • An external radiometric system infers level from calibrated detector counts and operates under the applicable radiation safety program.

Last updated: November 2026

Read buoyancy as motion or load

A free float moves with the surface where it is designed to ride. At rest its weight is balanced by buoyancy. A suspended displacer remains supported and senses a change in apparent weight when liquid covers more or less of it. In the Fisher 249 caged sensor, the lever moves around a knife-edge bearing and the torque tube acts as a torsional spring. The torque-tube shaft transfers rotation to the instrument, which converts it to a pneumatic or electrical signal depending on model. Some digital controllers detect that movement with a Hall sensor.

For a uniform liquid of density ρ\rho, the buoyant force is Fb=ρgVdispF_b=\rho g V_{disp}, with VdispV_{disp} the submerged volume. A uniform cylindrical displacer with cross-sectional area AA submerged over length hh has Vdisp=AhV_{disp}=Ah, within the active length. The downward support force is the displacer weight minus buoyancy. In a training case, a 12.0 lbf displacer of volume 100 in³ is fully submerged in solvent with specific gravity 0.80. Take reference water’s specific weight as 0.0361 lbf/in³ and neglect air buoyancy. The displaced solvent weighs 100×0.0361×0.80=2.888100\times0.0361\times0.80=2.888 lbf, leaving a support load of about 9.11 lbf.

For a liquid–liquid interface measurement using a fully submerged displacer, the total liquid level stays above the active length. As the denser lower liquid covers more of that length, it replaces lighter upper liquid around the displacer. With displaced volumes VLV_L and VUV_U, the force is g(ρLVL+ρUVU)g(\rho_L V_L+\rho_U V_U). If the interface sweeps the full active volume VV, the change in buoyant force is gV(ρL−ρU)g V(\rho_L-\rho_U). Determine whether that load change exceeds the actual sensor’s required span and resolution. Enter the actual liquid densities and displacer data as the Fisher controller setup requires. If the total level drops into the active length, part of the displacer is exposed to vapor and the interface-only calculation no longer holds.

Follow a magnetic float

A Rosemount 9930 magnetic level indicator uses a magnet-equipped float in a chamber connected to the vessel. The magnet flips flags outside the chamber to mark the float’s position. Select the float for the liquid density or the intended interface. Verify that the chamber communicates freely with the vessel and that the float can move. A blocked connection can trap the chamber at an unrepresentative level.

A compatible Magtech magnetostrictive transmitter uses an electrical pulse in a waveguide. Where it interacts with the float’s magnetic field, it produces a torsional wave. The return time locates the float. Read the device rating and mounting drawing for the permitted temperature, accuracy, sensor position and interface arrangement.

Select a capacitance probe and reference

In the ideal plate model C=ϵA/dC=\epsilon A/d. A level probe uses the change in effective capacitance as the covered length changes. Geometry, deposits and the material between electrodes influence the reading.

ApplicationMeasurement pathWhat to check
Low-conductivity liquidThe liquid and vapor form part of the dielectric between the probe and its reference electrode.Check dielectric contrast, reference geometry and calibration.
Conductive liquidA fully insulated rod can use its insulation as dielectric while the liquid forms the outer conductive path.Check conductivity, sheath integrity and compatibility. Use the supplied reference arrangement for the vessel.
Coating or buildupAdmittance sensing or a guarded or compensated design can reduce a coating-related error.Verify the specific device’s buildup limits and perform the required check when coating changes.

The Liquicap FMI51 technical information describes a fully insulated probe, a counter-electrode tube for a nonconductive vessel and phase-selective buildup compensation. Drexelbrook RF admittance documentation describes a separate coating-rejection design. For aqueous caustic service, evaluate the insulated configuration along with process temperature, materials and allowable pressure.

Check the echo path and measuring span

An ultrasonic level sensor measures the round-trip time tt of an acoustic pulse. If the effective sound speed is cc, the distance to the echo is d=ct/2d=ct/2. The level above an established lower datum is the distance from the sensor reference face to that datum minus dd. For example, a 5.00 m empty distance, a 20.0 ms round trip and a sound speed of 343 m/s yield d=3.43d=3.43 m and a level of 1.57 m. Use the actual sound propagation conditions. At fixed gas composition, the ideal-gas sound speed varies with the square root of absolute temperature. Gas composition and temperature gradients can affect the echo. Acoustic measurement needs a propagation medium.

In Endress+Hauser’s Prosonic S example, an NTC sensor supports temperature compensation. The configured span cannot enter the transducer’s blocking distance. Verify the model’s actual blocking distance and the selected high-level limit. Check for weak or false echoes from foam, vessel fittings, angled surfaces or other obstructions.

Free-space radar sends microwaves through an antenna. A model such as the Rosemount 5408 uses a frequency sweep. The difference between the transmitted and returned frequencies encodes distance. Check dielectric reflectivity, beam clearance, nozzle geometry and the condition of the antenna. Foam and turbulence can weaken or vary the echo.

Guided-wave radar (GWR) sends pulses along a contact probe. A change in electrical impedance returns part of the pulse. In an approved top-down oil/water arrangement, some of the signal returns at the oil surface and some continues through the oil to the water interface. The transmitter needs distinguishable echoes and sufficient dielectric contrast. It also uses the upper liquid’s dielectric properties to interpret travel through that layer. Review probe type, minimum and maximum detectable upper-layer thickness, coating and emulsion effects in the Rosemount interface application note. Vapor properties can matter. The 5301 dynamic vapor compensation option addresses specified high-pressure steam applications and has its own working limits.

Top-mounted GWR         Reflection used for
       |
~~~~~~~|~~~~~~~ oil     Total liquid surface
       |
=======|======= water   Liquid–liquid interface
       |
   Probe continues through measuring region

Infer level from an external radiation measurement

In a fixed radiometric gauge, a shielded sealed source and a detector can be installed outside the vessel. The material in the beam attenuates radiation. The received signal depends on density, path length and the vessel and source geometry. In the ideal narrow-beam model, intensity follows I=I0e−μxI=I_0e^{-\mu x} for thickness xx and linear attenuation coefficient μ\mu. That relationship does not supply a universal count-to-height curve. The VEGA FIBERTRAC instructions use count rates at known levels to establish the response. The instrument’s calibration, checks and applicable license still govern the work. In the United States, apply the relevant NRC or Agreement State authority and the license conditions for the fixed gauge.

Test Your Knowledge

A displacer weighs 12.0 lbf and displaces 100 in³ of solvent at full submergence. The solvent SG is 0.80 and reference water’s specific weight is 0.0361 lbf/in³. Neglect air buoyancy. What is the apparent weight?

A

12.0 lbf.

B

9.11 lbf.

C

2.89 lbf.

D

6.40 lbf.

Test Your Knowledge

A plant is considering a Liquicap FMI51 capacitance measurement for a conductive aqueous caustic. Which option fits the measurement principle if all wetted materials and ratings are approved?

A

A bare rod bonded directly to the vessel wall.

B

A copper jumper shorting the probe and reference.

C

An ultrasonic receiver connected in place of the probe.

D

A fully insulated rod probe with the specified counter-electrode path.

Test Your Knowledge

In a qualified top-down guided-wave radar application for oil over water, what lets the transmitter distinguish the two liquid levels?

A

The probe can return separate echoes from the oil surface and the dielectric change at the water interface.

B

The probe measures the difference in acoustic velocity between the liquids.

C

Two isolated pressure cells measure hydrostatic head inside the radar probe.

D

The radar measures heat conduction through the probe.

Sections you finish are checked off in the contents.