1.8 Electrical Circuits & Power Supplies
Key Takeaways
Series elements carry the same current. Parallel branches share the same terminal voltage.
Use the resistance or impedance appropriate to the circuit and the specified voltage or current units.
A DC supply’s output range, regulation, available load current and protection determine its suitability for the instrument.
Select the meter connection by quantity and check the planned circuit state before testing.
Follow power from the source to the field load
NCCER modules 12116 and 12305 cover electrical power, wiring and instrumentation circuits. Electric generation converts energy from primary sources. A generator can convert mechanical rotation to electrical energy, and photovoltaic cells convert light directly. The utility network moves electric energy from sources to users. Within a typical AC distribution path, transformers change voltage levels. Plant distribution then feeds loads and local power supplies through the equipment shown on the electrical drawings. A cabinet supply may convert the available AC to DC for an instrument or PLC circuit. Use the plant one-line diagram and the actual nameplates. See the U.S. Department of Energy’s Electricity 101.
Voltage is a potential difference between points. Current is the rate of charge flow. In a resistive model, resistance relates voltage drop to current by Ohm’s law, . A DC supply maintains a designated polarity. With steady DC, polarity and current direction stay constant. AC reverses direction periodically, with frequency measured in hertz. For AC equipment, distinguish RMS voltage from peak voltage. In a purely resistive load, real power is . For steady DC, and a resistor dissipates . Ratings and conductor selection also depend on temperature, service conditions and the installation.
Reduce a resistive circuit one group at a time
Series elements carry the same current. Their resistances add, and each drop is that current multiplied by its resistance. Parallel branches see the same voltage across the common nodes. Find each branch current using its own resistance, then sum the branch currents. For two resistances in parallel, the equivalent resistance is their product divided by their sum. It is less than either individual resistance when both are finite and positive. These relationships appear in the NCCER formula sheet.
Worked loaded-circuit example
An ideal 24 V DC source feeds a 120 Ω series resistance and then two branches of 240 Ω and 120 Ω.
+24 V ── 120 Ω ──┬── 240 Ω ──┬── 0 V
└── 120 Ω ──┘
The parallel combination is . The total resistance is 200 Ω, so source current is . The first resistor drops 14.4 V and leaves 9.6 V across both branches. Their currents are and . These sum to 0.12 A. The series resistor dissipates . This is a calculation example. A component choice would also account for derating and the permitted temperature of the installation.
An unexpectedly low loaded voltage can reflect a supply issue, excessive load, or an unintended series drop. Compare voltage across individual portions of the circuit under the authorized test conditions. Use the connection appropriate to the quantity.
| Quantity | Meter connection | What to verify |
|---|---|---|
| Voltage | Across the two test points | Correct voltage function, leads and circuit rating |
| Direct current measurement with a DMM | In series with the measured path | Correct fused input, leads and current rating |
| Resistance | Across the isolated component or circuit | Verify deenergized, discharge energy and account for parallel paths |
See the Fluke meter instructions.
Recognize what changes with AC frequency
An ideal resistor has the same resistance in this basic model regardless of frequency. An ideal inductor opposes changes of current. Its inductive reactance is . An ideal capacitor opposes changes of voltage, and its capacitive reactance has magnitude . The units are ohms when frequency is in hertz, inductance in henries and capacitance in farads. At double the frequency, inductive reactance doubles and capacitive reactance magnitude halves. In AC, inductive and capacitive effects can change the phase relation between voltage and current. An actual solenoid coil includes resistance and inductance, and its inductance can change with armature position. Check the actual electrical rating and response. See Microchip’s reactance equations.
Recognize supply stages and signal types
An example linear supply uses a transformer, a diode bridge for rectification, a filter capacitor to reduce ripple, and a regulator to hold the output near its target under its rated conditions. A switching design uses controlled switching and filtering, sometimes with an isolation transformer, to convert power efficiently. A filter capacitor can store energy after the source is isolated. Use the specified discharge and verification procedure. When choosing or diagnosing a supply, consider input limits, output tolerance and ripple, steady and startup current, protective response, and any isolation requirements. Texas Instruments illustrates both designs.
A 4–20 mA analog signal represents a range of values. A discrete contact or digital input represents defined states, such as made or open, which the receiver interprets using its circuit and thresholds. A digital network can represent a numerical process value as encoded data. Follow the power path and verify what kind of signal the receiver is set to expect.
In the worked mixed circuit, what is the voltage across each parallel branch?
24 V
14.4 V
9.6 V
4.8 V
With ideal L and C fixed, how do the magnitudes of their reactances change when AC frequency doubles?
Inductive doubles and capacitive halves.
Inductive halves and capacitive doubles.
Both double.
Both remain unchanged.
Which stage of the stated linear supply changes the alternating waveform to a unidirectional output before filtering?
Output regulator
Bridge rectifier
Filter capacitor
Protective earth bond