3.3 Differential Pressure Flowmeters & Primary Elements
Key Takeaways
At fixed density and meter conditions, the normalized flow in a zero-based unidirectional DP measurement is the square root of the normalized differential pressure.
Trace where square-root extraction happens. Raw-DP and flow-linear signals have different values at the same physical flow.
Use actual bore and pipe dimensions for beta. Apply the correct primary-element standard, pressure tappings and operating conditions.
Use the specified impulse routing and manifold lineup. Equalized sensor pressure does not by itself identify the analog current.
Relate flow to differential pressure
For steady incompressible flow, continuity relates volumetric rate to average velocity and area : . In an ideal horizontal contraction with negligible energy loss, Bernoulli’s relation gives
Where the section narrows, velocity increases and static pressure falls. Substituting shows why differential pressure increases roughly with the square of flow at fixed conditions. With two circular sections, bore , pipe internal diameter , and , the ideal area ratio . For a practical incompressible restriction model with an applicable discharge coefficient ,
Here is the bore area and measured is the static difference between the specified taps for the installed element. In SI units, area in m², pressure in Pa and density in kg/m³ give m³/s. For real meters use the element's geometry, tap locations, Reynolds range and coefficient method. Gas or steam calculations may need an expansibility factor and density at the specified conditions. Mass flow uses density and volume rate on the same basis. See WIKA’s DP flow instructions and ISO 5167-1:2022 scope. ISO 5167 covers specified, full circular conduits with subsonic, single-phase flow and gives requirements for nonpulsating service.
Normalize before taking a square root
Consider a unidirectional, zero-based range with stable density and coefficient. Set and let . An ideal 4–20 mA linear DP output is mA. A flow-linear output is mA. The table assumes the signal stays in its stated range and ignores the effects of configured low-flow cutoff.
| Flow | DP | Linear DP current | Flow-linear current |
|---|---|---|---|
| 0% | 0% | 4.00 mA | 4.00 mA |
| 10% | 1% | 4.16 mA | 5.60 mA |
| 25% | 6.25% | 5.00 mA | 8.00 mA |
| 50% | 25% | 8.00 mA | 12.00 mA |
| 70.71% | 50% | 12.00 mA | 15.31 mA |
| 100% | 100% | 20.00 mA | 20.00 mA |
When the transmitter sends flow-linear current, scale the receiving input linearly across the flow range. If the transmitter sends linear DP, a downstream function can extract the square root after the DP has been correctly scaled and normalized. Applying square root at both the transmitter and receiver maps 25% actual flow to 50% displayed flow, an error of 25 percentage points, or +100% relative to the actual 25% value. Check the input configuration, output configuration and display before changing any trim.
Near zero DP, small errors become large flow fractions. For example, a positive DP bias of 1% of full scale at zero actual flow produces 10% indicated flow in the ideal model. Diagnose zero shift, leaks or impulse head differences before masking a signal. The Rosemount 4051S manual’s cutoff example defines pressure cut-in and cutoff settings for its flow calculation. A 0.5 inH₂O threshold with a 100 inH₂O upper range is 0.5% of DP and corresponds to about 7.07% of ideal full-scale flow. Match the setting and units to the actual device and the required low-flow performance.
Identify the element and the pressure pickup
| Element | Where the signal comes from | What to verify |
|---|---|---|
| Concentric orifice | A centered restriction produces a difference between the specified pressure taps. | Bore size, tap arrangement, edge and orientation, pipe size, straight run and coefficient basis. |
| Eccentric or segmental orifice | The opening is offset or segment-shaped for a defined service. | Orientation and coefficient for the specific design. Significant second-phase flow can be outside the scope of a standard concentric calculation. |
| Flow nozzle | A contoured entrance accelerates fluid into a throat. | Nozzle geometry, service, tappings and applicable meter standard. |
| Venturi tube | A convergent section develops velocity head at the throat. A downstream diffuser recovers part of the static pressure. | Geometry, operating limits and actual permanent loss for the installation. |
| Pitot or averaging pitot | A probe samples impact pressure and a reference pressure. | For a simple local Pitot-static tube, the low-speed incompressible relation is . Use the profile or applicable factor for pipe flow. |
The ISO 5167 series specifies distinct types of primary element. The Rosemount 1495 drawing shows the designated inlet face for that plate. A specified vent hole near the top of an orifice plate can allow entrained gas to pass in liquid service. A specified drain opening can let condensate pass in gas service. These features may change the calculation basis. Use the approved drawing and element data. ISO/TR 15377:2023 treats some geometries and conditions beyond the scope of ISO 5167. See KROHNE’s orifice plate configurations.
For an example with actual inner pipe diameter 6.065 in and bore 3.0325 in, beta is . Its bore area is 25% of the pipe cross-section. Beta alone does not establish compliance, the meter’s range or its accuracy. A single-point Pitot measurement samples local velocity. The Rosemount Annubar averaging design samples high pressure at front openings and low pressure at the rear, and uses its own flow coefficient. The tap differential is used for measurement. Permanent pressure loss is the pressure that remains lost after downstream recovery. A well-designed Venturi diffuser usually reduces this loss compared with a sharp-edged orifice, with the actual loss determined for the installation.
4. Keep the impulse legs and manifold in the intended state
The Rosemount 3051S installation manual shows side taps with the transmitter beside or below them for liquid service. Gas arrangements use top or side taps with the transmitter beside or above them so condensate can drain back. Steam service can use water-filled legs with the transmitter below the taps and equal head contributions in the two legs. Use the pitch, support and fill requirements on the approved drawing. An extra liquid head on the L side decreases the pressure difference at the transmitter. Trapped gas in liquid service and liquid in gas service can also affect the signal.
A three-valve manifold has an H block, an L block and an equalizer between their transmitter-side connections. For the specified 3051S coplanar assembly in normal service, both blocks are open and the equalizer is closed. In the manufacturer’s static-pressure zero procedure, close the L block and open the equalizer with the H block still open. Observe digital DP within the required tolerance at equal pressure. Verify the analog reading against the selected transfer function and range. With an LRV of zero DP and a 4–20 mA output, the range mapping gives a nominal 4 mA. Return the specified assembly to service by closing the equalizer before reopening the L block. Startup, venting, isolation and the valve arrangement on five-valve manifolds depend on the installation. See the pressure sensing section and the approved procedure for the actual model.
In the ideal zero-based model, a DP flowmeter spans 0–100 inH₂O and 0–400 gpm. Density and coefficient are unchanged, low-flow cutoff is inactive and the transmitter sends a flow-linear current. What are the current and indicated flow at 25.0 inH₂O?
8.00 mA and 100 gpm.
12.00 mA and 282.8 gpm.
12.00 mA and 200 gpm.
16.00 mA and 300 gpm.
The actual pipe inside diameter is 6.065 in and the concentric bore is 3.0325 in. The approved plate also has a small upper vent hole for liquid service. Which beta ratio and purpose fit the drawing?
2.00, to drain settled sediment.
0.50, to let entrained gas pass.
0.25, to relieve the line’s design pressure.
0.70, to supply the DP transmitter with purge gas.
The manual and test plan have established zero differential at the sensor. The transmitter has a 4–20 mA output with a linear −10 to +30 inH₂O range. What analog current should the range mapping yield?
4 mA.
8 mA.
12 mA.
0 mA.