5.4 Fire Safety, Hazard Abatement and Fire Certificates
Key Takeaways
Use the applicable gazetted building by-laws for design, inspection and the stage forms. Apply the designated premises order separately to determine the ongoing Fire Certificate requirement.
Under the designated premises schedule, an office qualifies at 30 metres in height or 10,000 square metres in total floor area, inclusive of the threshold.
Section 8 fire-hazard notices, section 13 court closing orders, section 35 prohibitory orders and section 28 Fire Certificates serve different statutory purposes.
Check Circulars 007 and 009 for the professional scope and stage signatories. Separate the G8 passive work from the G9 active mechanical fire-fighting work.
Connect fire protection design to occupation and operation
On a project using Selangor's Uniform Building By-Laws, check the applicable version, purpose group, occupancy, height and geometry. Passive design uses fire-resisting construction, compartmentation, protected escape routes and access for emergency responders. Active protection uses systems such as detection and alarms, fire-fighting water supplies, sprinklers and risers. Read the actual by-law, schedules and any referenced standards for the project before choosing dimensions or equipment. Changes such as an enlarged storage area may affect both travel distances and the coverage of the installed system.
During plan submission and construction, coordinate the passive drawings, mechanical fire-fighting plans and electrical interfaces for the actual work. Assign each package to a qualified professional acting within the relevant branch and authority. Obtain the required approval and verify the installed work, testing and clearances applicable to it. BEM Circular 007 identifies the G8 submitting person as the Architect or Civil PEPC, subject to the joint building plan categories. The G9 active fire-fighting submitting person is the Mechanical PEPC. Electrical design interfaces, such as essential power, must be coordinated in their own scope. Circular 009 supplies the building plan categories, including single-storey factories in Appendix C. Keep the respective certifications, site records and applicable authority clearance together for the PSP to consider before issuing Form F. Check the local forms and associated conditions even where a BEM guide illustrates a reference or exception.
The 2025 amending Act A1764 also introduced separate registration controls. Section 36C applies to preparation of fire risk analysis reports. Section 36D addresses who can install, test or service prescribed equipment, and section 36K addresses registration of the prescribed equipment or installation itself. The 2026 equipment regulations took effect on 3 February 2026 and identify the items in their Schedule. Check the registration, role and any applicable transition when selecting or commissioning equipment. The product registration and the premises Fire Certificate have separate requirements.
Apply the Fire Services Act 1988 to actual premises
| Act 341 route | Trigger and consequence |
|---|---|
| Section 8 fire-hazard abatement notice | The Director General may require abatement by the specified time, with recipients determined by the facts under section 8(1). Section 8(2) can address recurrence. A locked escape route can warrant investigating the hazard. |
| Sections 11–13 | Section 11 permits abatement work after noncompliance with a notice. Section 12 provides for urgent abatement in the stated danger conditions. Under section 13, where the specified noncompliance, recurrence and risk circumstances apply, the Director General may apply to the court for a closing order. |
| Section 35 serious risk to persons or property | The Director General may apply to court for a prohibitory order restricting or prohibiting use of premises, whether or not designated, where the statutory fire risk test is met. |
| Sections 27–29 and 33 Fire Certificate | A designated premises requires a renewable annual Fire Certificate unless the statutory exception applies. The Director General arranges inspection on due application and issues the certificate on the statutory basis. Where no certificate is in force for designated premises to which the requirement applies, section 33 makes the owner liable on conviction to up to RM50,000 or five years' imprisonment or both. |
Section 28(3) covers premises appropriated to and used solely or mainly for public religious worship and a house occupied as a single private dwelling, including premises comprised in such a house. The provision retains the power to require periodic inspection and issue directions where the Director General considers there is a fire hazard. A current CCC and the operational Fire Certificate arise from separate routes. Check both before the client relies on occupation or renewed operation.
Worked example: office with a material alteration
A completed Selangor office has a height of 32 metres and a total floor area of 7,000 square metres. The designation schedule applies the height and area thresholds as alternatives for offices, so this building is designated on height. The owner, occupier or person with overall management needs to address the fire safety organisation requirement under section 27A. The amended Fire Certificate Regulations require the prescribed application with the organisation's certificate of establishment, a Fire and Emergency Response Plan and Fire Safety Report. The fire safety organisation prepares the plan and report. The Fire and Rescue Department (JBPM or BOMBA) uses an application and inspection process for certification.
If an occupier later proposes a material alteration while the Fire Certificate is in force, for example rearranging enclosed floors in a way that changes escape routes, section 32(2) requires notification to the Director General before the changes begin. Verify the effect on the certified use, fire equipment and escape provision. Under section 32(3), the Director General can specify steps where the change would make the equipment or installation inadequate for a covered use. Record the required decisions before undertaking the affected work.
Act 341, sections 8–13 and 27–35 · Designated Premises Order, consolidated schedule · Fire Certificate regulations, 2020 amendment · Selangor building by-laws · BEM Circular 007 · BEM Circular 009 · BEM stage form guide · Act A1764, section 11 · Equipment registration regulations, P.U. (A) 46/2026
A completed 32-metre office in Selangor with total floor area of 7,000 square metres has a CCC. No Fire Certificate is in force, and the office is subject to the designated-premises requirement. What is the owner’s maximum section 33 exposure on conviction?
RM25,000 or two years’ imprisonment
RM50,000 or five years’ imprisonment or both
RM250,000 or ten years’ imprisonment or both
RM50,000 or five years’ imprisonment or both, plus a daily fine prescribed by section 33
A single-storey Selangor factory under Appendix C uses G8 and G9. The approved scope includes passive compartmentation and a mechanical sprinkler system. Which assignment follows the BEM stage certification rules?
Civil PEPC or Architect for G8 as applicable to the approved scope, and Mechanical PEPC for G9
One Mechanical PEPC as submitting person for both G8 and G9 in every factory
Electrical PEPC as G9 submitting person because the pump has an electrical motor
Any PEPC can sign both forms once the contractor supplies test results
Match each action to its authority or record in a Selangor building project.
Match each item on the left with the correct item on the right
Act 341 section 8
Act 341 section 35
Act 341 section 32(2)
Selangor stage Form G8
Selangor stage Form G9