3.4 Color Rendering Metrics: CRI (Ra, R9) and ANSI/IES TM-30

Key Takeaways

  • General CRI averages the first eight special color rendering indices against a reference illuminant at the same correlated color temperature.

  • The saturated-red index R9 is reported separately. A high general CRI can coexist with a low R9.

  • ANSI/IES TM-30-24 uses 99 sample spectra. Rf describes average fidelity, Rg compares gamut area, and hue-bin details identify local shifts.

  • A gamut index above 100 means larger gamut area than the reference. It does not establish that every hue gained chroma.

  • Illuminant metamerism can make a material pair match under one lamp and mismatch under another. Inspect samples under the intended lighting.

Last updated: November 2026

CIE Color Rendering Index (CRI / RaR_a)

Because CCT describes only the white point of a light source, lighting designers need color rendering metrics to predict how faithfully illuminated objects appear. The CIE Color Rendering Index (CRI) method compares color shifts across standard test samples when illuminated by a test source versus a reference illuminant of the exact same CCT:

  • Test sources <5000 K< 5000\text{ K}: Reference is a Planckian (blackbody) radiator at that CCT.
  • Test sources ≥5000 K\ge 5000\text{ K}: Reference is a CIE D-series daylight illuminant at that CCT.

General CRI (RaR_a) is the arithmetic mean of only the first eight special indices (R1R_1 through R8R_8), representing eight low-to-moderate saturation (pastel) Test Color Samples (TCS 01–08) with 100100 as the upper limit. Poor matches can produce negative individual indices.

Special Indices (R9R_9–R14R_{14})

Six additional samples (R9R_9 through R14R_{14}) are measured separately and excluded from RaR_a:

  • R9R_9: The index for a strong red test sample. Two products can both report Ra=90R_a=90 and have very different R9R_9 values. Check it separately when the project specifies it.
  • R10R_{10} to R14R_{14}: Other special indices. They address different test samples, including strong yellow, green and blue and samples representing a complexion and leaf green.

Interpret general CRI in context

A 2700 K source and a 5000 K source are each evaluated against their own reference. Equal general CRI scores do not imply the same visual appearance. A mean of the first eight indices also hides differences in how individual objects look. Because the index scores fidelity, a chromatic shift can lower the score even if a designer prefers the more vivid result. Narrow spectral peaks can make a small test set less representative of the materials in a particular room. Review product spectra, supplemental indices, or physical samples when a choice depends on a particular hue.

ANSI/IES TM-30-24

The Illuminating Engineering Society method evaluates 99 color evaluation samples spanning a broad range of reflectances. It compares scores with a reference at the test source’s CCT. Compared with the abrupt reference transition in CRI, the TM-30 method uses a gradual blend of Planckian and daylight references across its transition range.

Report itemWhat it meansHow to use it
Fidelity index RfR_fAverage magnitude of color differences from the reference, expressed with 100 at the high-fidelity endCheck the average and see whether individual hues important to the project depart more than it suggests.
Gamut index RgR_gRatio of average gamut polygon areas, scaled so that 100 represents equal areaAbove 100 signals larger area. Look at the hue bins to see which areas of color space account for the difference.
Color vector graphicGraph of shifts across 16 hue binsCompare the direction and size of shifts. Two similar average scores can hide different local effects.
Local red fidelity and chroma shiftFidelity and signed chroma change in the first hue binA positive chroma shift describes increased chroma for that bin. It does not make the source universally better or replace a required R9R_9 value.

Metamerism

Metamerism occurs when two object samples with different spectral reflectance curves produce identical tristimulus values (X,Y,Z)(X, Y, Z) under one light source's SPD—appearing to match perfectly—yet visibly mismatch when viewed under a second light source with a different SPD. For example, a designer who pairs a painted wall swatch with a dyed carpet under 3500 K3500\text{ K} tri-phosphor office lighting can discover an unmistakable clash near a north-facing daylight window. Compare the specific finish samples under both the proposed electric scene and representative daylight. A high average fidelity index is no guarantee that a particular material pair will match.

Set the project acceptance criteria

Start with the task. For a gallery, the curator may favor faithful rendition of the displayed work while also limiting exposure. A retail brief may favor a particular chroma shift for the merchandise. A patient examination brief can require a specific red rendering index in addition to general CRI. Identify the project specification and relevant facility guidance before deciding whether a submitted fixture qualifies. In any application, compare like-for-like reports and inspect the actual materials or targets where possible.

Worked Specification Examples

Example 1: Computing RaR_a Without Falling for the R9R_9 Trap

A luminaire photometric report lists R1R_1 through R8R_8 as 92,94,90,91,93,92,88,8892, 94, 90, 91, 93, 92, 88, 88 and reports R9=24R_9 = 24. The owner’s project specification requires Ra≥90R_a \ge 90 and R9≥50R_9 \ge 50. Does the product meet both criteria?

  1. Compute RaR_a: Sum only R1R_1–R8R_8: 92+94+90+91+93+92+88+88=72892 + 94 + 90 + 91 + 93 + 92 + 88 + 88 = 728. Divide by 88: Ra=728/8=91.0R_a = 728 / 8 = 91.0. (Mistakenly including R9R_9 and dividing by 99 would yield 83.683.6, which is incorrect.)
  2. Evaluate suitability: Ra=91R_a=91 meets the stated average criterion. R9=24R_9=24 misses the stated red criterion, so the submittal fails this specification.

Example 2: Interpreting TM-30 Submittals

Compare two 3000 K3000\text{ K} retail tracks: Fixture P reports Rf=81R_f = 81, Rg=94R_g = 94, Rcs,h1=−8%R_{cs,h1} = -8\%; Fixture Q reports Rf=80R_f = 80, Rg=110R_g = 110, Rcs,h1=+9%R_{cs,h1} = +9\%. Despite nearly identical fidelity (8181 vs. 8080), P reports a negative average chroma shift in the red hue bin. Q reports a positive shift there and has a larger gamut area than the reference. If the owner values increased chroma for this hue bin, Q is the better candidate on that measure. Compare physical merchandise before approving either option.

References: CIE 13.3-1995 CRI method, CIE test sample data, DOE and IES overview of ANSI/IES TM-30-24, and CIE metamerism.

Loading diagram...
Comparing CIE CRI and ANSI/IES TM-30 Evaluation Workflows
Test Your Knowledge

A patient examination room specification requires general CRI of at least 90 and R9 of at least 50. A submittal reports R1 through R8 as 92, 94, 90, 91, 93, 92, 88, and 88, plus R9 = 24. How should you evaluate the color submittal?

A

Ra is 83.6 and fails the average criterion.

B

Ra is 91.0 and both criteria are met.

C

Ra is 83.6 after including the red sample, so both criteria are met.

D

Ra is 91.0 and meets the average criterion, while R9 misses its separate minimum.

Test Your Knowledge

Under ANSI/IES TM-30-24, how should you read a report showing Rf = 84 and Rg = 109?

A

The reference gamut area is larger than the test gamut.

B

Rf gives average fidelity and the test gamut area is 109% of the reference area.

C

The light source has a correlated color temperature 9% above the reference.

D

Every hue bin has exactly 9% more chroma than the reference.

Test Your Knowledge

An interior designer verifies that a painted drywall sample and a custom textile match closely under 3500 K tri-phosphor fluorescent office lighting, yet the two materials appear noticeably mismatched beside a daylight window. Which phenomenon explains this?

A

Lambertian depolarization

B

Total internal reflection

C

Illuminant metamerism

D

Positive Duv shift