8.3 Daylight Metrics (DF, sDA, ASE) and ASHRAE 90.1 Daylight Zones
Key Takeaways
Daylight factor uses a stated sky distribution and excludes direct sun. Annual metrics use a time series of sun and sky conditions.
Under LM-83-23, report the sDA shading conditions and distinguish gross and net annual sunlight exposure.
Check direct-sun risk and view-dependent glare separately when interpreting annual daylight results.
Use the adopted energy-code edition for zone geometry, connected wattage, exceptions, and photocontrol requirements.
Compare static and annual metrics
Daylight factor (DF) at a point is the indoor illuminance due to a specified sky, divided by the simultaneous outdoor horizontal illuminance under that same unobstructed sky. Exclude direct sunlight from both values. The CIE Standard Overcast Sky is a common assumption. For example, . A higher result may reflect more accessible sky, more transmitted light or brighter reflecting surfaces. Its significance depends on the task. One sky condition cannot represent the annual effects of direct sun, site weather or moving shades.
ANSI/IES LM-83-23 defines two annual metrics. Use the same analysis area and calculation grid for both, with the prescribed hourly weather inputs. The default analysis period is 8 a.m. to 6 p.m. local clock time each day, 3,650 hours per year. Record any permitted variation.
- Spatial daylight autonomy (sDA) reports the fraction of the analysis area attaining the selected illuminance for the selected share of analysis hours. For sDA₃₀₀/₅₀%, the thresholds are 300 lx and 50% of the analysis hours, or 1,825 hours under the default schedule. LM-83-23 allows a separate 150 lx threshold for eligible spaces. Report sDA with blinds fully open, fully closed and operating. The standard algorithm closes blinds by window group so direct sunlight of 1,000 lx or more reaches at most 2% of analysis points at each hour. A specified fully automated daylight-management system can instead be modeled with its documented sequence.
- Annual sunlight exposure (ASE) reports how much of the analysis area receives direct-beam sunlight of at least 1,000 lx for more than 250 analysis hours under the default thresholds. It examines the direct beam without reflected and diffuse components. Gross ASE leaves blinds open and considers dynamic image-preserving glazing at maximum transmittance. Net ASE excludes the apertures with fully automated daylight management from the sunlight contribution. Use the same analysis area when comparing the two. A high result signals investigation of potential direct-sun discomfort. Consider sightlines, reflections and thermal loads using the appropriate separate analyses.
For example, an equal-area 100-point grid can have 78 points meeting the sDA thresholds with blinds operating, 24 points meeting the gross ASE conditions, and 12 meeting the net conditions. Report sDA of 78%, gross ASE of 24%, and net ASE of 12%, with the other required sDA conditions. The two ASE values provide information about how much exposure remains when calculating without light through the automatically managed apertures. They do not describe occupant comfort after installation.
Useful daylight illuminance (UDI) reports the time when daylight at a point falls inside a stated band. The original research used 100–2,000 lx. Report the band and time schedule when using the metric. Daylight glare probability (DGP) predicts discomfort for a selected view using vertical eye illuminance and characteristics of bright sources such as luminance, apparent size and position. Choose representative seats, view directions and sun or shade conditions.
Example energy-code approach
ANSI/ASHRAE/IES Standard 90.1-2022 is the example edition. The jurisdiction determines the adopted edition, amendments and compliance path. Code daylight areas are defined geometrically and trigger specific electric-lighting controls. They have a different purpose from an annual simulation grid.
- Primary sidelighted area: The depth is one head height measured from the window wall, limited by the distance to an opaque vertical obstruction at least 5 ft high. From each edge of the window, the lateral extension is one half of the head height or the distance to such an obstruction, whichever is smaller.
- Secondary sidelighted area: It starts beyond the primary area. It has a further head-height depth and the same lateral rule, subject to obstruction limits. If an opaque vertical obstruction at least 5 ft tall already ends the primary area, there is no secondary area beyond it.
- Toplighted areas: For a skylight, the unobstructed extension on each side below the opening is 0.7 times the ceiling height, subject to the standard’s obstruction criterion. Roof monitors have a separate geometry rule.
For the cited edition and subject to exceptions, automatic daylight-responsive control applies at 75 W or more in the primary area, or in a combined skylight and roof-monitor area. 150 W or more combined across primary and secondary areas triggers control of both. Determine the actual input power of general luminaires completely or partially within the zones. Where required, continuous dimming reaches 20% or less of electric lighting power and off. Calibration adjustments may be no higher than 11 ft above the finished floor, and adjustment processing must work without a person physically at the sensor. When general lighting is in overlapping toplighted and sidelighted areas, count the overlapped lighting with the toplighted controls under the cited provisions. Verify other applicable exceptions in the adopted edition.
Worked geometry and input power
An office has a centered ribbon window 40 ft wide with a 9 ft head height on a 60 ft wall. There are no limiting obstructions. Each side adds , so the width is 49 ft. Primary and secondary areas each extend for a depth of 9 ft and each occupies . A fixture schedule identifies 120 W fully or partially in the primary area and 90 W of additional general lighting in the secondary area. Both require control in this case because and . Assume no exception applies.
In a separate unobstructed lobby with ceiling height 16 ft, a 6 ft by 8 ft skylight opening gives an 11.2 ft extension on each side. The toplighted area is . If the affected general lighting has 80 W of input power and no exception applies, it meets the 75 W trigger. Use actual fixture loads and overlaps in the controls schedule as well as the zone drawing.
References: CIE daylight factor, ANSI/IES LM-83-23 §§2–4, Nabil and Mardaljevic UDI research, Wienold and Christoffersen DGP research, ASHRAE 90.1-2022 Addendum r terminology, and DOE 90.1-2022 reference manual, pp. 76–79.
An LM-83-23 report lists gross ASE of 24% and net ASE of 12% for the same area. What explains the distinction?
The net run includes only the electric-light contribution.
The gross run uses 300 lx for half the year.
The two results use different analysis areas in the same room.
The net run excludes sunlight through apertures with fully automated daylight management.
In the ANSI/ASHRAE/IES 90.1-2022 example, a 20 ft wide window has an 11 ft head height and an unobstructed floor area. What are the primary sidelighted depth and width?
Depth 16.5 ft, width 20 ft.
Depth 11 ft, width 31 ft.
Depth 22 ft, width 31 ft.
Depth 11 ft, width 24 ft.
For the 90.1-2022 example, a designer is specifying calibration controls for a required photocontrol. Which detail meets the stated calibration conditions?
An adjustment 12 ft above the floor, with remote processing.
An adjustment 9 ft above the floor that requires someone to remain at the sensor during processing.
An adjustment 10 ft above the floor, with processing that does not require anyone physically present at the sensor.
An adjustment on a 14 ft high sensor that only staff can access.