9.1 Control Strategies: Switching, Dimming, Occupancy, and Daylight Harvesting

Key Takeaways

  • Distinguish auto-on occupancy, manual-on vacancy, and partial-on operating modes.

  • Choose sensor locations and logic from recorded coverage and conditions at the site.

  • A closed-loop photosensor responds to the controlled electric light. An open-loop sensor is positioned to measure a daylight signal independently.

  • Verify high-end trim, scenes, scheduling and energy performance at actual operating settings.

Last updated: November 2026

Define what the controls must do

Start with the task, the hours of use and the space. An on/off relay controls a group as a unit. Step switching selects discrete levels, which depend on the circuits or driver settings. Continuous dimming allows adjustment over a range. Use the tested combination of controller, driver and luminaire to confirm the usable minimum, behavior near off and the fade.

Occupancy control describes how the system responds to a detection input. Auto-on starts lights on detection and can turn them off after an unoccupied delay. Vacancy requires a manual action to turn lights on and turns them off automatically after vacancy. Partial-on starts at a specified fraction with a way to reach the remaining output if needed. Check the adopted energy and life-safety provisions by space type, including exceptions, before choosing mode, maximum delay or unoccupied level. If occupants frequently work by daylight alone, manual-on may avoid some unnecessary starts. The effect depends on actual use.

Choose and place the occupancy sensor

SensorHow it detects changesField check
Passive infrared (PIR)Detects changes in thermal infrared signals across the sensor’s detection zonesVerify the line of sight and walk-test across zone boundaries. Partitions or stationary occupants may impede detection.
UltrasonicEmits sound and detects changes in its echoes from movementCheck coverage around furnishings, small motions at the task and unintended detection near moving air or equipment.
Dual technologyCombines sensing methods such as PIR and ultrasonicRead how each signal affects turn-on and hold-on. Test the selected logic under actual occupied and vacant conditions.
Microwave motion sensingUses radio-frequency reflections to detect motionTest the intended boundary. Some assemblies can detect motion across lightweight partitions, depending on sensor and materials.

A tenant reports nuisance shutoff at desks after installing high partitions. Test the small motions of a seated user, not only a person walking through the doorway. Check whether the existing detector can see each occupied position. Consider more sensors or different locations and confirm that motion in the adjoining corridor or air movement does not control the wrong lights. Dual-technology behavior is model dependent.

Schedule and daylight response

A time schedule can switch zones at regular times or provide after-hours control. An astronomical schedule estimates dawn and dusk from date and location. Set local time and any offsets, then test representative seasonal, holiday and manual override behavior. If the specification calls for a warning or time-limited override, include it explicitly in the sequence and verify its duration.

An open-loop daylight sensor reports a daylight signal largely independent of the electric lighting it controls. Locate it so the signal represents daylight for the controlled zone. A sensor outside the window may miss the effect of interior blinds. A closed-loop sensor sees the combined contribution from daylight and the controlled electric light, generally through the surfaces it views. Its reading need not equal a meter reading at the desk. Check the view, gain, time response and any switching thresholds or hysteresis. A zone that repeatedly changes output under stable daylight needs a check of its feedback and other control inputs.

Tuning, scenes and temporary demand reduction

High-end trim limits the maximum commanded level. Verify illuminance where the work takes place and measure input watts at that setting. A change in light output percentage is not a measurement of power savings. Lumen maintenance can reserve output initially and increase it later under a defined schedule or feedback strategy. It needs adequate output reserve and a realistic maintenance plan. Scenes store different zone settings, such as presentation and discussion modes. Test the actual view and interaction with occupancy and daylight controls in each scene.

Demand response can temporarily reduce electric load in selected zones. OpenADR is a way to communicate event signals to a participating system. The project must specify its response, duration, limits, and recovery. Test effects on occupied tasks and required lighting instead of assuming a reduction goes unnoticed.

Worked operating-cost comparison

A private office uses 120 W at full output. Over 260 days, the baseline is 10 on-hours per day, or 0.120(10)(260)=312 kWh0.120(10)(260)=312\text{ kWh}. In an auto-on trial it runs 7.5 hours per day at the same load, or 234 kWh. During a manual-on and trim trial, it averages 6 hours per day at a measured 96 W, or 149.76 kWh. Against the baseline that is 162.24 kWh, a 52% decrease. At a flat $0.15 per kWh, the corresponding energy-charge difference is about $24.34 per year. The example assumes no material off-state load and comparable operating days. This comparison does not attribute the entire change to either control feature.

References: DOE school lighting guidance, Lutron occupancy and vacancy sensor guide, Lutron daylight sensor guide, PNNL field evaluation, and OpenADR program guidance.

Loading diagram...
Daylight Signals and Electric-Light Feedback
Test Your Knowledge

An office adds high partitions and the PIR sensor now misses quiet work at two desks. What is the best first design check?

A

Shorten the vacancy delay before checking coverage.

B

Map coverage at the actual seat positions and test additional or relocated sensing with normal airflow and neighboring traffic.

C

Aim a high-sensitivity sensor at the supply diffuser.

D

Select a detection pattern from the open-room plan without testing the new partitions.

Test Your Knowledge

Electric lights in a closed-loop daylight zone cycle between levels while sky conditions remain steady. Which check tests an explanation linked to the feedback loop?

A

Confirm the longitude in an unrelated exterior time clock.

B

Assume the driver input wattage is constant.

C

Observe the sensor response as the controlled fixtures change, and verify its field of view, gain and thresholds.

D

Move the perimeter fixtures to an untested central photosensor.

Test Your Knowledge

A 120 W lighting zone runs six hours per day. At the commissioned trim setting it draws 96 W and still meets the task criterion. How much energy is saved in one six-hour day with the same schedule?

A

0.144 kWh.

B

0.024 kWh.

C

0.576 kWh.

D

1.44 kWh.