7.2 Light Loss Factors (LLF): Recoverable and Nonrecoverable

Key Takeaways

  • Record the point in service life at which maintained performance must be evaluated.

  • Identify the baseline photometry and avoid counting equipment effects already included in the test.

  • Cleaning and replacement can restore output lost to dirt, lumen depreciation or outages. Some site or material effects require a different remedy.

  • Multiply the applicable factors and check whether the maintenance plan can actually support them.

Last updated: November 2026

Set the baseline before using a factor

Light loss factors (LLFs) account for effects that alter light relative to a stated baseline. A baseline can describe reference lamps or an initially measured complete luminaire, together with a documented room model. Initial field illuminance can already differ from a test-based prediction. For example, an operating temperature that changes output may affect the system as soon as it is installed. Maintained illuminance is evaluated under the specified maintenance assumptions. State the evaluation time or condition and compare the correct plane and statistic to the criterion.

When independent corrections apply to the same baseline, their combined multiplier is their product. When the luminaire was tested with its installed driver and setting, that baseline already includes those effects. When a model includes dirty room surface reflectances, adding a separate factor to account for the same reflectance loss counts it twice.

Depreciation affected by maintenance

FactorWhat changesEvidence to check
Lamp lumen depreciation (LLD)Operating-hour-related decline in output of the light sourceUse applicable manufacturer maintenance data at the design horizon, at the specified operating conditions.
Luminaire dirt depreciation (LDD)Dirt on luminaire optical surfaces can reduce and redistribute lightCheck luminaire design, environmental exposure and expected time between cleanings.
Room surface dirt depreciation (RSDD)Dirt reduces the effectiveness of surfaces that reflect light into the spaceCheck room finishes, maintenance, and reliance on interreflection for the actual distribution.
Lamp burnouts (LBO) or survivalFailed sources are out of service until repaired or replacedCheck documented failure or survival assumptions and the actual replacement response.

For a replacement program, model the output and availability through the proposed interval. A fluorescent catalog can give initial and mean lumens. Check the stated life basis before using those values. For integrated LED products, use the appropriate product or source maintenance evidence for the factor being modeled. A TM-21 projection from source data does not establish whole-product survival. Track separate possible driver failures and whether prompt replacement is feasible.

Indirect systems rely heavily on light reflected from the room. If a ceiling is a major contributor, dirt on that surface can affect the delivered light more than it would for a primarily direct layout. Use the modeled distribution, condition of the finish and cleaning cycle to evaluate that sensitivity. Deposits on luminaire optics are a different loss, and a badly discolored optic may need replacement even after cleaning.

Effects outside routine cleaning or relamping

Check the equipment’s ability to operate at the design temperature, electrical supply and orientation. Ballast factor compares lamp output on a specified ballast with output on the reference ballast. Use it when the baseline requires that conversion. Read the test configuration before applying a ballast or driver adjustment to delivered lumens. Confirm voltage or temperature effects with applicable product data. Do not infer an output correction from a voltage change alone.

Dirt on a diffuser can be removed with a suitable cleaning method. Permanent material changes such as yellowing require a separate assumption if they affect the calculation. Record when the effect applies. A permanently discolored surface observed at the end of a specified cycle may have been new at the initial measurement, even if routine cleaning cannot reverse the discoloration.

Worked example: maintenance plan and connected quantity

A 4,000 ft² machine shop calls for a maintained workplane average of 50 fc. Each LED luminaire delivers 12,000 lm at its reference operating condition. Utilization based on delivered lumens is 0.72. For this exercise the project documents a 0.96 output factor for the installed operating temperature. The end-of-cycle assumptions are LLD 0.88, LDD 0.82, RSDD 0.96, and survival 0.95, with an additional irreversible optical factor of 0.97 near the end of the cycle. Assume that the factors are separately modeled and that the initial product has no discoloration.

LLFmaintained=(0.88×0.82×0.96×0.95)(0.96)(0.97)=0.61282\text{LLF}_{\text{maintained}}=(0.88\times0.82\times0.96\times0.95)(0.96)(0.97)=0.61282

The count is 50(4,000)/(12,000×0.72×0.61282)=37.7750(4{,}000)/(12{,}000\times0.72\times0.61282)=37.77, so the average estimate requires at least 38 fixtures. At 38 fixtures, predicted initial field illuminance is 38(12,000)(0.72)(0.96)/4,000=78.80 fc38(12{,}000)(0.72)(0.96)/4{,}000=78.80\text{ fc}. The predicted maintained average is 38(12,000)(0.72)(0.61282)/4,000=50.30 fc38(12{,}000)(0.72)(0.61282)/4{,}000=50.30\text{ fc}. With all factors omitted, the calculation would select 24 fixtures, which under the maintained assumptions would provide only 31.77 fc.

If the shop cannot reach these luminaires for cleaning as planned, revisit the dirt assumption and access provisions. Recheck both life stages before increasing fixture count. Confirm the layout and verify minimum and average values on the required task grid.

References: IES light loss factor, IES nonrecoverable light loss factor, CIE maintenance of indoor electric lighting, IES recoverable light loss factor, and ISO/CIE TS 22012.

Loading diagram...
Inputs to Initial and Maintained Light Loss
Test Your Knowledge

Which combination lists ONLY recoverable Light Loss Factors?

A

Lamp Lumen Depreciation (LLD), Ballast Factor (BF), and Luminaire Dirt Depreciation (LDD)

B

Luminaire Ambient Temperature Factor (LATF), Room Surface Dirt Depreciation (RSDD), and Lamp Burnouts Factor (LBO)

C

Lamp Lumen Depreciation (LLD), Luminaire Dirt Depreciation (LDD), Room Surface Dirt Depreciation (RSDD), and Lamp Burnouts Factor (LBO)

D

Voltage-to-Luminaire Factor (VLF), Luminaire Surface Depreciation Factor (LSD), and Equipment Operating Factor (EOF)

Test Your Knowledge

A luminaire installation has recoverable factors LLD=0.90\text{LLD} = 0.90, LDD=0.85\text{LDD} = 0.85, RSDD=0.95\text{RSDD} = 0.95, LBO=0.98\text{LBO} = 0.98, and nonrecoverable factors BF=0.88\text{BF} = 0.88, LATF=0.95\text{LATF} = 0.95, LSD=0.96\text{LSD} = 0.96 (with VLF=1.00\text{VLF} = 1.00 and EOF=1.00\text{EOF} = 1.00). What is the total Light Loss Factor (LLF\text{LLF})?

A

0.570.57

B

0.710.71

C

0.800.80

D

0.650.65

Test Your Knowledge

A design changes from direct to indirect lighting. The ceiling has the same scheduled cleaning interval and equipment conditions are unchanged. Which depreciation term specifically describes the effect of a soiled ceiling on ceiling-reflected light?

A

Ballast Factor (BF)

B

Voltage-to-Luminaire Factor (VLF)

C

Lamp Burnouts Factor (LBO)

D

Room Surface Dirt Depreciation (RSDD)

Sections you finish are checked off in the contents.