7.3 Point-by-Point Calculations: Inverse-Square and Cosine Laws
Key Takeaways
Check whether the far-field intensity distribution represents the luminaire at the target distance.
For a horizontal receiving plane below the luminaire, use the cubic cosine form with height above the plane.
For a vertical surface facing the source’s horizontal projection, use the sine of the nadir angle as the incidence factor.
Sum unobstructed contributions, each with its applicable light loss factor, for the maintained direct component.
Beyond Averages: Direct Point-by-Point Calculations
While the Lumen Method estimates spatial average illuminance across an entire room, many lighting tasks require knowing the exact illuminance at a specific point—on a retail mannequin, a museum painting, an exterior sidewalk, or a surgical table. Point-by-point calculations solve for this direct component using intensity ( in candelas) from a luminaire's photometric report, the slant distance , and the angle at which light strikes the target surface.
Remember one vital limitation: basic hand point-by-point formulas compute direct light only. They omit room surface interreflections, which can still be substantial in light-colored interior rooms.
Decide when a far-field intensity is adequate
The calculation approximates a luminaire as a point source at its photometric center. Whether that approximation is adequate depends on the size and distribution of its luminous aperture, the direction and distance to the target, and the error acceptable for the task. A single distance multiple cannot establish accuracy for all luminaires.
If a long linear luminaire sits close to a wall or task, verify a near-field measurement or use an optical model supported by information about the emitting sections. Subdividing the overall intensity equally into arbitrary segments may give a misleading distribution. Check the method against reliable field or modeled evidence at the relevant distance.
Normal, Horizontal, and Vertical Illuminance Equations
1. Normal Illuminance
When a surface is oriented perpendicular (normal) to the incoming ray of intensity at slant distance , illuminance follows the pure Inverse-Square Law:
Using in feet yields footcandles (); using in meters yields lux (). To convert initial illuminance to maintained direct illuminance, multiply this contribution by the applicable factor for the luminaire and operating condition. Use a separate model for reflected contributions.
2. Horizontal Illuminance
Most interior and site workplanes are horizontal. Let be the vertical height of the luminaire above the workplane, be the horizontal offset from directly beneath the luminaire (nadir), and be the vertical angle measured from nadir ( straight down). Because and the angle of incidence onto the horizontal surface equals , the receiving-surface cosine factor gives:
The term combines the receiving surface’s projected area with the increase in slant distance. As the angle increases, the geometric term decreases. The intensity in the actual direction may increase or decrease, depending on the optic.
3. Vertical Illuminance
For a vertical surface (wall, sign, display plaque, or standing person's face) positioned in the same vertical plane as the luminaire and directly facing it, the surface normal is horizontal. The incidence angle is , and since :
If the vertical surface normal is rotated horizontally by an azimuth angle away from the luminaire's vertical plane, include an additional factor: . Use zero direct contribution if the source is on the back side of the receiving surface. Directly under a downlight (), , so a single overhead fixture delivers zero vertical illuminance directly beneath itself in this direct point-source model.
4. Tilted Workplane and Vector Dot Product
For an obliquely tilted surface (such as a sloped drafting board or angled solar/display sign) where the incoming ray meets the surface normal at incidence angle :
In 3D coordinates, if points from calculation point to luminaire with , and is the unit normal pointing away from the illuminated surface, then , giving the general simulation formula:
The angles in the intensity term are the emission direction in luminaire coordinates. The vector projection uses the receiver’s normal. For an aimed fixture these angles generally differ. A physical obstruction can also reduce the direct contribution to zero.
Superposition of Multiple Luminaires
Illuminance is linearly additive. By the principle of superposition, the total direct illuminance at point from luminaires is the sum of each unobstructed fixture's contribution:
Apply the loss multiplier for each fixture before summing the maintained result. A common multiplier can be applied to the sum if the same value applies to every contribution.
Worked Example 1: Two-Fixture Superposition (IP Footcandles)
Two identical recessed downlights ( and ) are mounted above a horizontal counter with . Point sits directly beneath Downlight (, ) and horizontally from Downlight . Photometry gives and .
- Fixture A (, ):
- Fixture B (, ): By the 3-4-5 right triangle, , , , and .
- Total Maintained Horizontal Illuminance:
- Maintained Vertical Illuminance on a small display card at facing Fixture : Fixture contributes (), while Fixture delivers:
Worked Example 2: Aimed Museum Accent (SI Lux)
A track spotlight above the floor is aimed directly at a painting center above the floor () from a horizontal offset from the wall. Because the spotlight is aimed at the painting center, use its center-beam intensity rather than a nadir value. Here and . With :
References: CIE photometric distance law, CIE photometric inverse-square law, and IES treatment of near-field data.
A 4 ft linear luminaire is mounted 6.5 ft above a desk. Its available intensity file was verified only for far-field use. Before relying on the predicted illuminance directly below the fixture, what should the designer check?
Use the far-field intensity value because the calculation point lies on the luminaire axis.
Whether the far-field distribution is valid at the target distance or a near-field measurement or supported model is needed.
Split the overall candela equally among four segments without checking how each segment emits.
Use the optical aperture’s overall length instead of the distance from the luminaire to the desk.
A point-source downlight is mounted above a workplane. At point , located horizontally from nadir (slant distance ), the luminaire intensity is and . What is the maintained direct horizontal illuminance at point ?
A track spotlight mounted above the floor is aimed directly at a plaque above the floor at a horizontal distance of from the track (, ). If intensity along the aimed ray is and , what is the maintained direct vertical illuminance on the plaque facing the track?