9.4 IES Design Framework, Layering, and Illuminance Selection

Key Takeaways

  • Use the applicable IES Recommended Practice and Illuminance Selector entry for the task, plane and criterion.

  • Evaluate task visibility, glare, appearance, installation and maintenance together.

  • Check local tasks and surroundings when comparing task-ambient and general lighting schemes.

  • Calculate example connected power using a consistent delivered-lumen basis.

Last updated: November 2026

Turn design intent into measurable criteria

The IES Lighting Library connects applications and related lighting practices. IES LP-2, Designing Quality Lighting for People and Buildings, addresses quality as a design process. Start by describing what occupants must see, which features the design should reveal, the project’s operating and environmental constraints, and how the system can be maintained. An inspection workstation, a lobby feature wall and a pedestrian crossing have different visual tasks and different evidence of success.

A useful review includes the following questions:

  • People and tasks. What is the item to be seen and at what plane and angle? Consider target contrast, the surround, reflections, user needs and consequences of error. A face, a vertical label and a desktop require different calculations.
  • Architecture and appearance. How do lit surfaces communicate paths, form and visual hierarchy? Richard Kelly described ambient luminescence as general light, focal glow as light that calls attention, and play of brilliants as deliberate sparkle. These describe perceptual roles. They need not correspond one-for-one to circuits or luminaire types.
  • Operation and environment. Check power, hours, maintenance, access and the effects of the installation on other areas. For an outdoor project, verify relevant views and boundary conditions in addition to luminaire ratings.

Select the appropriate IES recommendation

Use the IES Illuminance Selector or applicable recommended practice and check its notes. Identify the application and the specific task. Then identify whether the row specifies horizontal, vertical or other measurement planes, and whether it uses an average, minimum, uniformity ratio or another criterion. If a row distinguishes user or task groups, use its own definitions and footnotes. Do not apply a single historical scoring table to every space. An older or more demanding task population can prompt review of the visual conditions and the relevant published guidance.

For example, an electronics inspection station reports adequate horizontal average illuminance. Defects remain difficult to see on shiny dark metal. Check the required inspection plane, the viewing direction, local illuminance and the appearance of defects. A different angle or distribution can reveal detail that disappears in a specular reflection. Confirm the applicable maintained criterion and test the chosen geometry. The physical task and viewer determine the recommendation, including when greater light alone is insufficient.

Document the source and edition, the numerical criterion and plane, any task-specific adaptation, and the planned test. Treat the code’s power limit and control requirements separately from the illuminance design criterion.

Layer light for the project

General or ambient light provides coverage of occupied space and circulation. Task lighting adds light where work occurs. Accent lighting uses contrast to direct attention to a feature. Decorative lighting can support a visual concept, provided its view and output are suitable. One luminaire may contribute to more than one role.

With task-ambient lighting, check room brightness, facial lighting, uniformity, glare and all task locations before reducing overhead output. Layouts change and some desks may lack a usable task light. For a mock-up, measure several positions with task lights both on and off and gather feedback at the usual seats. A proposed connected-power reduction only describes one aspect of the result.

Suppose a library introduces detailed craft work at the same tables used for general reading. Keep adequate ambient light for circulation, faces and the background, and compare a separately controlled task layer at the work surface. A local source can create a shadow if it is always on the same side as the user’s working hand. It can also form a reflected image in a tablet or glossy cutting guide. Test the source positions with representative left- and right-handed users and verify the scene when furniture moves. Record which lights belong to the general scheme and which users can adjust.

Worked comparison of connected power

Consider a 2,000 ft² office. The example uses initial delivered efficacy of 110 lm/W, a room utilization factor of 0.65 matched to delivered lumens, and an LLF of 0.80 for the overhead systems. At a stipulated 50 fc maintained average from the overhead system, the estimated initial delivered flux is 50(2,000)/(0.65×0.80)=192,308 lm50(2{,}000)/(0.65\times0.80)=192{,}308\text{ lm}. The estimate is about 1,748 W or 0.874 W/ft². At an overhead target of 25 fc with the same documented assumptions, the estimate halves to about 874 W.

If 16 task lamps draw 8 W each, the second option uses about 874+128=1,002 W874+128=1{,}002\text{ W}, or 0.501 W/ft². The reduction in estimated connected watts is around 42.7%. Verify by modeling or measurement that local lighting supplies the needed increment and that the combined design meets the task and surround criteria. This exercise includes the task lamps in project connected power. Formal energy-code accounting follows the adopted standard, including any rules for portable lighting.

References: IES design quality practice, IES Illuminance Selector, Richard Kelly’s original descriptions, DOE task-ambient lighting project, and IES utilization definitions.

Loading diagram...
Design Criteria and Lighting Layers
Test Your Knowledge

A metal inspection bench meets its horizontal average target, but an operator cannot see fine flaws when the part is tilted. What should the designer check next?

A

The inspection plane, viewing angle, and reflected images under the applicable task guidance.

B

Only the lamp’s nominal CCT.

C

The floor illuminance in a remote corridor.

D

The driver address before looking at the task.

Test Your Knowledge

An IES application entry gives separate horizontal and vertical criteria. The designer verifies horizontal readings and wants to close the check. What is the appropriate next step?

A

Take another horizontal reading and treat it as the vertical value.

B

Multiply every horizontal value by a fixed fraction.

C

Infer the vertical readings from the luminaire’s color rendering score.

D

Verify the specified vertical plane at the relevant locations and use the stated statistic.

Test Your Knowledge

An overhead scheme draws 1,748 W. A second scheme uses 874 W overhead plus sixteen 8 W task lamps in a 2,000 ft² office. What is the second scheme’s connected power density for this exercise?

A

0.437 W/ft².

B

0.501 W/ft².

C

0.874 W/ft².

D

1.002 W/ft².