5.1 Water Supply Fixture Units (WSFU) & Demand

Key Takeaways

  • Nonpublic fixtures use Table 382.40-1b: a lavatory is 1.0 wsfu, a kitchen sink 1.5, a gravity-tank water closet 2.0 and a flushometer water closet 6.0.

  • A nonpublic bathroom group with bathtub, lavatory and flush-tank water closet is 4.0 wsfu total; with a flushometer water closet it is 8.0.

  • Public fixtures use Table 382.40-2, where a gravity-tank water closet is 3.0 wsfu and a flushometer water closet 6.5.

  • Table 382.40-3 converts wsfu to gpm on separate curves; 20 wsfu is 35 gpm on the flushometer curve but 14 gpm on the flush-tank curve.

  • Continuous-flow equipment is added in gpm at its anticipated flow rate, not converted through fixture units (SPS 382.40 (6) (b)).

Last updated: October 2026

The load factor for water piping

SPS 382.40 (6) (a) says the load factor for intermittent fixtures "shall be computed in terms of water supply fixture units as specified in Tables 382.40-1b and 382.40-2." Fixture units are then converted to gallons per minute with Table 382.40-3 (or Table 382.40-3e for treatment devices). The water side is completely separate from the drainage dfu values in Table 382.30-1. A lavatory is 1 dfu and also 1.0 wsfu, but a nonpublic water closet is 4 dfu and only 2.0 wsfu (flush tank).

Each table gives hot, cold and total columns. Use the hot or cold column when sizing piping that carries only that water, and the total column for the building supply and water service.

Nonpublic fixtures (Table 382.40-1b)

FixtureHotColdTotal
Automatic clothes washer1.01.01.5
Bathtub, with or without shower head1.51.52.0
Dishwashing machine1.0-1.0
Hose bibb, 1/2 inch-3.03.0
Hose bibb, 3/4 inch-4.04.0
Kitchen sink1.01.01.5
Laundry tray1.01.01.5
Lavatory0.50.51.0
Shower, per head1.01.01.5
Water closet, flushometer-6.06.0
Water closet, gravity flush tank-2.02.0
Manufactured home-1515
Bathroom group: tub, lavatory, water closet (flush tank)2.03.54.0
Bathroom group: tub, lavatory, water closet (flushometer)2.07.58.0
Bathroom group: shower stall, lavatory, water closet (flush tank)1.53.03.5
Bathroom group: shower stall, lavatory, water closet (flushometer)1.57.07.5

Fixtures not listed may be assigned a value by comparison with a listed fixture that uses water at similar quantities and rates.

Public fixtures (Table 382.40-2), selected values

FixtureHotColdTotal
Lavatory0.50.51.0
Shower, per head2.02.03.0
Bathtub2.02.03.0
Clothes washer, individual commercial2.02.03.0
Kitchen and food preparation sink, per faucet2.02.03.0
Service sink2.02.03.0
Flushing-rim sink-7.07.0
Drinking fountain-0.250.25
Urinal, syphon jet / washdown-4.0 / 2.04.0 / 2.0
Water closet, flushometer-6.56.5
Water closet, gravity flush tank-3.03.0
Wall hydrant, 1/2 inch / 3/4 inch, hot and cold mix2.0 / 3.02.0 / 3.03.0 / 4.0

Commercial dishwashers and large-capacity commercial washers use the manufacturer's gpm (footnote b).

Converting wsfu to gpm (Table 382.40-3)

The conversion has two curves. Use the flushometer column when the system is predominantly flushometer water closets or syphon-jet urinals, and the flush tank column when it is predominantly flush-tank closets or washdown urinals.

wsfugpm, predominantly flushometergpm, predominantly flush tank
4104
10278
203514
304020
505128
1006842
2009265
500142125
1,000208208

The curves meet at 1,000 wsfu. Values between rows may be interpolated. Example: 15 wsfu on the flush-tank curve lies halfway between 8 and 14 gpm, or 11 gpm.

Table 382.40-3e is a separate conversion for water treatment devices serving an individual dwelling (for example, 8 wsfu = 6.5 gpm, 40 wsfu = 9 gpm). It may not be used for hose bibbs, hydrants or high-flow fixtures. Devices that treat water to meet Table 382.70-1 use Table 382.40-3 instead.

Continuous-flow devices (SPS 382.40 (6) (b))

Equipment demanding a continuous flow, such as a cooling tower makeup, a process line or a lawn irrigation zone, is computed at its anticipated flow rate in gpm. Add that gpm to the gpm you get from converting the intermittent fixtures. Don't convert it to fixture units.

Worked example: a single-family home

Fixturewsfu (total)
2 bathroom groups, tub/lav/flush-tank closet2 x 4.0 = 8.0
Kitchen sink1.5
Dishwashing machine1.0
Clothes washer1.5
Laundry tray1.5
2 hose bibbs, 1/2 inch2 x 3.0 = 6.0
Total19.5 wsfu

The house is predominantly flush tank, so 19.5 wsfu converts to about 13.7 gpm (interpolating between 10 wsfu = 8 gpm and 20 wsfu = 14 gpm). The hot-water piping carries only the hot column: 2 x 2.0 + 1.0 + 1.0 + 1.0 + 1.0 = 8.0 wsfu.

Water heater sizing alternate (SPS 382.40 (6) (c))

For a water heater serving a single residence or living unit used by one household, an alternate method is allowed:

  1. Minimum heater flow rate = 0.65 x the calculated hot-water gpm from Tables 382.40-1b and 382.40-3.
  2. A storage heater's flow rate may be based on 70 percent usable storage plus recovery rate, with a 10-minute minimum draw.
  3. An instantaneous heater must deliver a rise that provides 110 degrees F at the terminal fixture.
  4. The method may not be used for heaters serving high-flow fixtures (more than 4 gpm at 80 psig), hose bibbs, hydrants or fixtures needing 1/2-inch or larger supplies, or for sizing hot-water distribution piping.

Exam traps

  • Mixing up dfu (drainage) and wsfu (supply) values.
  • Using the flushometer curve for a house; a house is predominantly flush tank.
  • Using the nonpublic table for a restaurant or office, where public values (water closet 3.0 tank or 6.5 flushometer) apply.
Loading diagram...
From fixtures to design flow
Test Your Knowledge

What total wsfu does Table 382.40-1b assign to a nonpublic bathroom group consisting of a bathtub, lavatory and gravity flush-tank water closet?

A

4.0 wsfu

B

6.0 wsfu

C

3.5 wsfu

D

8.0 wsfu

Test Your Knowledge

A building is predominantly flush-tank type and its total demand is 20 wsfu. What flow does Table 382.40-3 give?

A

35 gpm

B

27 gpm

C

20 gpm

D

14 gpm

Test Your Knowledge

How is the load from equipment that demands a continuous flow of water figured under SPS 382.40 (6) (b)?

A

At its anticipated flow rate in gallons per minute

B

At 2 wsfu for each gpm of continuous flow demand

C

At 1 wsfu for each gpm of continuous flow demand

D

It is ignored, because pipe sizing uses only fixture units