11.2 Manufactured Homes, Campgrounds, RV Parks & Dump Stations

Key Takeaways

  • A manufactured home water service terminates at least 6 inches above grade, and its sanitary and storm sewers at least 4 inches above grade but no higher than the water service.

  • Frost sleeves on manufactured home connections extend to within 6 inches of the buried horizontal pipe or 6 inches below frost depth and end at least 2 inches above grade.

  • A manufactured home drain connector has a minimum slope of 1/8 inch per foot; a manufactured home is rated at 11 dfu and 15 wsfu.

  • A campsite receptor is at least 4 inches, serves no more than 4 RVs, has a rim at least 4 inches above grade, needs no trap vent and is capped when unused.

  • A sanitary dump station has a 4-inch receptor with a hands-free self-closing cover, a 6-foot impervious pad sloped 1/4 inch per foot, and a labeled nonpotable washdown supply at least 50 feet from potable supplies.

Last updated: October 2026

Licensing and plan review

  • Restricted-service licensees and learners may install manufactured home community and campground or RV park water supply and drain systems, and the connection from the sewer or water service to the home manufacturer's connection (SPS 305.90 (1) (b) 1.).
  • Water supply and drain systems for manufactured home communities and campgrounds are on Table 382.20-2 line 6. Only agent municipalities that are cities of the first class may review them; otherwise DSPS does. Sanitary dump stations are on line 4.
  • Manufactured home connections use these load values: 11 dfu (Table 382.30-1), 15 wsfu (Table 382.40-1b), and 20 psig minimum flow pressure at the home's supply (SPS 382.40 (7) (d)).

Manufactured homes and communities (SPS 382.51)

Sanitary drain systems

RuleRequirement
Design basisBuilding sewer provisions of SPS 382.30
Drain connectorMinimum slope 1/8 inch per foot; aboveground drain material (SPS 384.30 (2) (a))
Sewer and community drain materialSanitary building sewer pipe (SPS 384.30 (2) (c))
Upstream point of the sewerIts connection with the home's drain connector
TerminationAbove surrounding finished grade
CleanoutsPer SPS 382.35, plus one where more than one home is served by a single drain
LocatingTracer wire or GPS for nonmetallic drains to municipal mains
TestingAs building sewers and private interceptor main sewers

Water supply systems

RuleRequirement
Downstream point of the water serviceConnection with the manufacturer's water distribution piping
Service and community main materialWater service and private main material (SPS 384.30 (4) (d))
Home water connectorWater distribution material (SPS 384.30 (4) (e))
Curb stopFor each home, terminating outside the home's perimeter
Building control valveAt least 6 inches above grade on the service or community supply
FlushingDesigned for periodic flushing at 3 ft/s (AWWA C651)
TestingAs water services and private mains

Connections at the home (SPS 382.51 (3))

  • Frost sleeves on water, sanitary and storm risers extend to within 6 inches of the top of the buried horizontal pipe, or at least 6 inches below predicted frost depth. They end at least 2 inches above grade and are made of building drain or sewer material.
  • Terminations: water at least 6 inches above grade; sanitary and storm at least 4 inches above grade and not higher than the water termination.
  • All connections are capped or plugged when no home is connected.

Worked example. A new manufactured home pad: the water riser ends 8 inches above grade, the sanitary riser 6 inches and the storm riser 5 inches. Water is at least 6, the drains at least 4, and neither drain is higher than the water, so all comply. If the sanitary riser were cut at 10 inches, it would be higher than the water riser and would fail.

Campgrounds and RV parks (SPS 382.37 (3))

Sanitary drain systems

  1. Each RV drain line discharges to a campsite receptor of at least 4 inches through an indirect waste pipe.
  2. One receptor serves no more than 4 RVs. If 2 or more drain lines share a receptor, install an increaser in the vertical standpipe.
  3. Receptor rim at least 4 inches above grade, and not higher than the site's water supply termination.
  4. No vent is required for the campsite receptor trap, which may sit below frost depth (SPS 382.32 (4) (b) 1. d.). Campsite receptors are 6 dfu with a 4-inch trap.
  5. Cap receptors when not in use.
  6. Use building sewer materials. Add a cleanout upstream of where more than one receptor joins a single drain.
  7. Provide tracer wire or GPS, and test as a building sewer.
  8. Pitch per Table 382.30-3 (SPS 382.30 (5) (d)).

Water supply systems

  1. An accessible control valve at the most upstream point, downstream of the municipal meter or pressure tank.
  2. Individual backflow protection at each campsite hose connection. Hose connection vacuum breakers may be used under continuous pressure only at campgrounds and marinas (SPS 382.41 (4) (c)).
  3. Campsite water risers end at least 18 inches above grade.
  4. Site water may serve only that campsite.
  5. A camping unit may be plumbed directly if its fixtures meet chs. SPS 382 and 384, or connected by NSF/ANSI 51 or 61 hose with individual backflow protection.
  6. Campsite hose connections need at least 15 psig flow pressure.
  7. Design for flushing at 3 ft/s, test as water services, and provide a locating method.

Sanitary dump stations (SPS 382.37 (2))

ItemRequirement
ReceptorAt least 4 inches, trapped; vented if inside an enclosed structure
CoverSelf-closing and operable without touching it with one's hands
PadImpervious, at least 6 feet in diameter, sloped 1/4 inch per foot to the receptor
Washdown waterPermanent supply with backflow protection, labeled not for drinking, at least 50 feet from a potable supply unless a variance is approved
TrapMay sit more than 3 feet below the receptor opening to reach below frost

Water-carried composting systems (SPS 382.37 (1))

Composting toilets that use water or another liquid to carry waste meet NSF 41, are listed, and are continuously ventilated, with vents terminating like plumbing vents. End product disposal follows 40 CFR Part 503. Liquids go to a public sewer or a POWTS, and the potable supply connection is protected under SPS 382.41. Dry composting toilets fall under ch. SPS 391 instead.

Loading diagram...
Manufactured home and campsite connections
Test Your Knowledge

How high above surrounding grade must the water service serving a manufactured home terminate under SPS 382.51 (3) (b)?

A

At least 2 inches

B

At least 6 inches

C

At least 12 inches

D

At least 18 inches

Test Your Knowledge

What is the maximum number of recreational vehicles one campsite receptor may serve under SPS 382.37 (3) (a)?

A

2

B

6

C

8

D

4

Test Your Knowledge

Which requirement applies to a sanitary dump station drain receptor under SPS 382.37 (2)?

A

A hands-free self-closing cover and an impervious pad at least 6 feet across

B

A 2-inch receptor with no trap, set flush with the surrounding gravel pad

C

A potable washdown hose bibb directly at the receptor with no backflow device

D

A hinged cover lifted by hand and a crushed-stone pad at least 4 feet across