11.3 Water Reuse, Plumbing Treatment Standards & Stormwater Infiltration

Key Takeaways

  • Table 382.70-1 requires NR 811 and 812 approved sources for drinking, cooking, food, medical and personal hygiene uses; reused water serves only listed nonpotable uses that meet their limits.

  • Water closet and urinal wastewater may not be reused for drinking water, except through DNR-permitted treatment works or a POWTS with in situ soil (SPS 382.34 (3) (a)).

  • Nonpotable water treatment devices are listed under NSF/ANSI 350 or 350-1 and need an onsite maintenance log (filters at intervals under 3 months; pumps, valves, tanks and backflow devices at start-up and at least every 12 months).

  • Stormwater infiltration systems need 5 feet of suitable soil to groundwater or bedrock (10 to 20% fines) or 3 feet (20% fines or more), 1 foot for roof runoff, and must drain within 72 hours.

  • Infiltration systems are set back 10 feet from buildings, 10 feet from POWTS tanks and storage tanks, 5 feet from POWTS dispersal components and property lines, and 15 feet from in-ground pools.

Last updated: October 2026

The reuse framework

SPS 382.34 (3) (a) allows graywater, stormwater, clear water, blackwater and other approved wastewater to be reused under SPS 382.70. One firm limit applies: wastewater from water closets and urinals may not be reused for drinking water, except through DNR-permitted treatment works or a POWTS with an in situ soil component. SPS 382.70 (3) requires every plumbing system to supply water suitable for its intended use that protects public health and the waters of the state.

Table 382.70-1: plumbing treatment standards (selected)

Intended useStandard at the outlet
Drinking, cooking, food processing, pharmaceutical and medical usesNR 811 and 812 approved sources
Personal hygiene, bathing, showeringNR 811 and 812 approved sources
Automatic fire protectionAs acceptable to the local authority
Swimming pool makeup waterNR 811 and 812 approved sources
Cooling waterpH 6 to 9; BOD5 under 50 mg/L; TSS under 30 mg/L; free chlorine 1.0 to 10.0 mg/L
Subsurface infiltration and irrigation using reuse waterOil and grease under 15; BOD5 under 30; TSS under 35 mg/L; fecal coliform under 200 cfu/100 mL; 12 in. of medium sand or finer above groundwater or bedrock
Subsurface irrigation using stormwaterOil and grease under 15; TSS under 60 mg/L
Surface or spray irrigation using stormwater and clearwaterBOD5 under 10; TSS under 5 mg/L
Surface irrigation (not food crops), vehicle and clothes washing, air conditioning, dust control, concretepH 6 to 9; BOD5 under 10; TSS under 5 mg/L; free chlorine 1.0 to 10.0 mg/L
Toilet and urinal flushingpH 6 to 9; TSS 5 mg/L or less; free chlorine 0.1 to 4.0 mg/L (see the table for BOD)
Uses not listedContact the department

Chlorine and pH limits apply only to reuse treatment devices. Stormwater standards are annual averages. Industrial and WPDES-permitted discharges are excluded.

Treatment devices and systems (SPS 382.70 (5))

Devices that treat nonpotable water for these uses must be listed under NSF/ANSI 350 or 350-1 (or approved under SPS 384.50), designed per SPS 382.34 (3) (a), and provided with three things.

1. A maintenance log kept onsite by the owner:

ActionInterval
Inspect, clean and replace filtersLess than 3 months
Verify treatment components meet standardsPer manufacturer and department
Pump, valve and pressure tank operationAt start-up and at least every 12 months
Clean storage tanks; check locksAt start-up and at least every 12 months
Labeling and markingsAt start-up and at least every 12 months
Mulch basinsAs needed to prevent ponding and runoff
Cross connection control inspection and testAt start-up and at least every 12 months

2. An onsite manual with a system diagram, operation and maintenance instructions, shutdown steps, manufacturer contacts, model number and sources for expendable parts.

3. Indelible labeling per NSF 350, visible after installation.

Connecting reuse to the building

  • Reuse piping and outlets are labeled with purple tags or bands (Table 382.40-1a) at no more than 25-foot intervals. Nonpotable hose bibbs are labeled and have removable handles.
  • The potable makeup to a reuse system is protected per SPS 382.41. Nonpotable water may feed a treatment device designed to meet Table 382.70-1 (SPS 382.40 (3) (a) 2.).
  • Water supply piping may be reused only for an equal or higher degree of hazard (SPS 382.22 (4) (b)).
  • Plan review: onsite residential and commercial water reuse treatment systems (Table 382.20-1 line 7), and stormwater and clearwater detention, treatment and infiltration systems serving public buildings (line 6), go to the department. Agent municipalities may review them if the department authorizes.
  • Underground stormwater reuse tanks are at least 8 feet from sanitary sewers (SPS 382.36 (7) (d) 9.).

Stormwater and clearwater subsurface infiltration (SPS 382.365)

TopicRequirement
Site and soil evaluationPer SPS 385.40 (3) (a) and 385.30 (1) (c), by a registered soil tester under SPS 305.33 or a licensed soil scientist; also DNR technical standards 1002 and 1004
InfluentTable 382.70-1 subsurface infiltration standards
In situ soil separation to groundwater or bedrock5 feet of suitable soil with 10 to 20% fines; 3 feet with 20% fines or more; measured to mounded groundwater where mounding applies
Roof runoff or equivalently treated waterAt least 1 foot of material finer than coarse sand
Engineered soil (bioretention)At least 24 inches (18 inches with documentation and approval), above any limiting factor
Groundwater mounding analysisRequired when the system is wider than 15 feet
Drain-downWithin 72 hours; surface ponding within 24 hours
OrientationLong dimension along the contour; level infiltrative surface below original grade (irrigation excepted)
Installation weatherNot on frozen soil; remove snow; stop if the soil rolls into a 1/4-inch wire

Setbacks (Table 382.365-4):

FeatureSetback
Building10 ft
Holding tank or stormwater collection tank10 ft
POWTS dispersal component5 ft
POWTS holding or treatment component10 ft
Property line5 ft
In-ground swimming pool15 ft
WellsNR 811 and 812

No substance may be discharged into an infiltration system that causes NR 140 groundwater limits to be exceeded at a point of standards application. Deleterious substances must be treated under SPS 382.34 first.

Worked example

A commercial building wants to flush its toilets with harvested roof water.

  1. The system is an onsite water reuse treatment system, so plans go to DSPS (Table 382.20-1 line 7).
  2. The treatment device must be NSF/ANSI 350 listed and deliver pH 6 to 9, TSS of 5 mg/L or less and free chlorine of 0.1 to 4.0 mg/L at the water closets.
  3. The flushing piping is purple-labeled.
  4. The potable makeup to the storage tank uses an air gap or other Table 382.41-1 protection.
  5. The owner keeps the onsite log: filters checked at least every 3 months, and pumps, valves, tank and backflow device annually.
Loading diagram...
Approving a reuse system
Test Your Knowledge

Which use does Table 382.70-1 restrict to NR 811 and 812 approved water sources?

A

Toilet and urinal flushing

B

Surface irrigation of lawns

C

Personal hygiene, bathing and showering

D

Cooling water

Test Your Knowledge

Under what standard must a nonpotable water treatment device for reuse be listed under SPS 382.70 (5)?

A

NSF/ANSI 61 and NSF/ANSI 372

B

NSF/ANSI 350 or 350-1

C

NSF/ANSI 44 softener standard

D

ASSE 1013 and CSA B64.4